Nordyne G6RL 90+ Vent Pipe Installation, Example, Solution, Pipe Routing and Support, Vent Table

Page 15

with piping of selected diameter and number of elbows. This table applies to the length and num- ber of elbows for each pipe. To use the table, the furnace input rate, the centerline length and the number of elbows on each pipe must be known. Choose the diameter for which the tabulated length is equal to or greater than required.

Proper use of the table is illustrated by the following example:

Example:

An 80,000 Btuh furnace is to be installed in a "one-pipe" system with 40 feet of vent piping. There are four elbows, including those exterior to the building.

Solution:

Consulting Table 5, in the single pipe length column for an 80,000 Btuh furnace, the maxi- mum allowable length of 2" is 60 feet with one elbow. Select 2-1/2 or 3" pipe. For three addi- tional elbows, deduct 2.5 ft. for each elbow, or

7.5ft. for a maximum installed vent length of

52.5ft.

Condensing furnace combustion products have very little buoyancy, so Table 5 is to be used without consideration of any vertical rise in the piping.

NOTE: Always use the same or larger size piping for combustion air as is used for the exhaust vent.

Vent Pipe Installation

Pipe Routing and Support

Route piping as directly as possible between the furnace and the outdoors and remember that routing affects pipe size requirements per the preceding section. If a two pipe system is used, locate the combustion air intake and the vent exhaust in the same atmospheric pressure zone

-i.e. both must exit the building though the same portion of exterior wall or roof. Vent piping must be sloped upwards not less than 1/4" per foot in the direction from the furnace to the terminal. This is to ensure that any condensate flows back to the furnace (where it can be disposed of through the condensate disposal system).

The quality of outdoor air must also be consid- ered. Be sure that the combustion air intake is not located near a source of solvent fumes or other chemicals which can cause corrosion of the furnace combustion system.

!CAUTION:

Combustion air must not be drawn from a corrosive atmosphere.

APPLICATION

SINGLE PIPE LENGTH (ft.)

DIRECT VENT, DUAL PIPE LENGTH (ft.)

 

with 1 long radius elbows*.

with 1 long radius elbows on each pipe.*

PVC,CPVC or ABS

Outlet

Outlet

Inlet/Outlet

Inlet/Outlet

Inlet/Outlet

SCH. 40 Pipe Size

2"

3"

2"

2"

3"

2"

3"

3"

Models

 

 

 

 

 

 

 

 

G6RC,D,L

80

150

40

40

50

50

90

90

040

 

 

 

 

 

 

 

 

Models

 

 

 

 

 

 

 

 

G6RC,D,L

60

150

30

30

35

35

90

90

060 & 080

 

 

 

 

 

 

 

 

Models

 

 

 

 

 

 

 

 

G6RC,D,L

30

150

15

15

25

25

90

90

100 & 120

 

 

 

 

 

 

 

 

*NOTES

1.Subtract 2.5 ft. for each additional 2" elbow and 3.5 ft. for each additional 3" elbow.

2.Two 45 degree elbows are equivalent to one 90 degree elbow.

3.One short radius elbow is equivalent to two long radius elbows

4.Do not include termination elbows in calculation of vent length

5.This table is applicable for elevations from sea level to 2000 ft. For higher elevations decrease vent pipe lengths by 8% per 1000 ft. of altitude.

6.Only the above pipe materials are approved for use with G6 Condensing Furnaces.

Table 5. Vent Table

15

Image 15
Contents What to do if YOU Smell GAS Installation InstructionsPage Table of Contents Upflow G6RC & G6RD Furnaces DimensionsDownflow G6RL Furnace High 1910 1860 1780 1700 1620 1520 1420 Furnace Airflow DataModel Input Motor Number Btuh Speed Clearances to Combustible Materials Installation Requirements Requirements and CodesDownflow Warning G6RL Models Horizontal InstallationsSupply AIR Plenum Installation LocationFurnace on a Concrete Slab Circulating AIR SupplyVenting and Combustion AIR Requirements Return AirMinimum Free Area40,000 100 sq. 60,000 80,000 Air From Inside Air Requirements For One-Pipe InstallationInstallation In An Unconfined Space Installation In a Confined SpaceAir Directly Through An Exterior Wall Venting RequirementsVent Pipe Material Vent Pipe Length and DiameterPipe Routing and Support Vent Pipe InstallationSolution ExampleG6RL Downflow Furnaces G6RC & G6RD Upflow FurnacesG6RC & G6RD Upflow Furnaces G6RC & G6RD UpflowFurnaces G6RL Downflow FurnacesVent Termination Clearances Location of Outdoor TerminationsHorizontal Venting Alternate Horizontal Vent InstallationVertical Venting Vent Freezing ProtectionConcentric Vent Termination Vertical Vent Termination Drainage of Condensate from FurnaceLeak Check GAS Supply and PipingLP/Propane Gas Sea Level and High Altitude Conversion ConversionHigh Altitude Application Natural Gas High Altitude ConversionLine Voltage Wiring Electrical WiringAbove Sea Level START-UP and AdjustmentsLow Voltage Wiring Furnace Rating Orifice Drill Size Plate Input Btu/h NatStart-Up Procedure Verifying and Adjusting Firing RateElectrical Data Verifying Burner Operation Verifying and Adjusting Temperature RiseGas Flow Rate GAS Flow Rate Cubic Feet PER HourDescription of Components Verifying Operation of the Supply Air Limit SwitchFor G6RC, G6RD and G6RL Residential Furnaces G6RC, G6RD and G6RL Integrated Control Board System DiagramSystem Operation Information MaintenanceLocation of Major Components G6RL Downflow FurnaceHeating Mode Cooling ModeSequence of Operation Fan Mode Furnace Fails to OperateTwinning of Two Furnaces Fuel Type INSTALLATION/PERFORMANCE Check List¢707931*¤