Nordyne G6RL 90+, G6RC 90+ Verifying and Adjusting Temperature Rise, Verifying Burner Operation

Page 27

Use the following procedure to determine the firing rate:

1.Shut off all other gas fired appliances.

2.Start the furnace and allow it to run for at least three minutes.

3.Measure the time (in seconds) required for the gas meter to complete one revolution.

4.Convert the time per revolution to cubic feet of gas per hour using Table 12.

5.Multiply the gas flow rate in cubic feet per hour by the heating value of the gas in Btu per cubic foot to obtain the firing rate in Btuh. Example:

Time for 1 revolution of a gas meter with a 1 cubic foot dial = 40 seconds.

From Table 9 read 90 cubic feet per hour of gas.

Heating value of the gas (obtained from gas supplier) = 1040 Btu per cubic foot.

Firing rate = 1040 x 90 = 93,600 Btuh.

6.Adjustments to the firing rate can be made by adjusting the gas manifold pressure. See the High Altitude Application section for additional information of firing rate at elevations above 2000 ft.

The manifold pressure must be set to the appro- priate value for your installation. Refer to either Table 7 for natural gas or Table 8 for LP/propane gas to verify the manifold pressure setting re- quired for your particular installation. To adjust the manifold pressure, remove the regulator cap and turn the adjusting screw clockwise to in- crease pressure or counterclockwise to reduce pressure. Replace the regulator cap after adjust- ments are complete.

!CAUTION:

Do not re-drill the burner orifices. If the orifice size must be changed, use only new orifices.

Verifying and Adjusting

Temperature Rise

Verify that the temperature rise through the furnace is within the range specified on the furnace rating plate. Temperature rises outside the specified range could result in premature heat exchanger failure.

Place thermometers in the return and supply air stream as close to the furnace as possible. The

thermometer on the supply air side must be shielded from direct radiation from the heat exchanger to avoid false readings. Adjust all registers and duct dampers to the desired posi- tion and run the furnace for fifteen minutes before taking any temperature readings. The temperature rise is the difference between the supply and return air temperatures.

For typical duct systems, the temperature rise will fall within the range specified on the rating plate with the blower speed at the factory recom- mended setting. If the temperature rise mea- sured is outside the range specified, it may be necessary to change the blower speed. Lower blower speeds will increase the temperature rise and higher blower speeds will decrease the temperature rise.

The furnace is equipped with a multispeed mo- tor. Heating and cooling speed selection is made by moving the leads on the integrated control board located in the furnace. The wiring diagram on the furnace and Figures 25, 26 and 27 show the speed taps for adjusting motor speed.

If it is desired that the blower operate at the same speed for heating and cooling, tape off the terminal of the unused blower wire. Install the jumper wire, found in the plastic instruction bag, across the HEAT and COOL taps on the control board. Reconnect the desired blower tap to the piggyback quick connect.

The blower control is designed to start the circulating air blower 30 seconds after the gas valve is opened. The blower control is factory wired to turn the blower motor off 120 seconds after the gas valve is closed. This timing can be changed using the BLOWER OFF timing switch opposite the terminal block on the control board. (See Figure 25.)

Verifying Burner Operation

To verify operation of the burners, make sure that the blower compartment door is in place and that there is power to the furnace. Set the thermostat above room temperature and ob- serve the ignition sequence. The flame can be observed through the small clear window on the burner box. The burner flame should carry over between all burners. The flames should be blue, without yellow tips. Flames should extend from each burner without lifting, curling, or floating. After verifying ignition, set the thermostat below room temperature and verify that the burner flame extinguishes completely.

27

Image 27
Contents What to do if YOU Smell GAS Installation InstructionsPage Table of Contents Upflow G6RC & G6RD Furnaces DimensionsDownflow G6RL Furnace High 1910 1860 1780 1700 1620 1520 1420 Furnace Airflow DataModel Input Motor Number Btuh Speed Clearances to Combustible Materials Installation Requirements Requirements and CodesDownflow Warning G6RL Models Horizontal InstallationsSupply AIR Plenum Installation LocationFurnace on a Concrete Slab Circulating AIR SupplyVenting and Combustion AIR Requirements Return AirMinimum Free Area40,000 100 sq. 60,000 80,000 Air From Inside Air Requirements For One-Pipe InstallationInstallation In An Unconfined Space Installation In a Confined SpaceAir Directly Through An Exterior Wall Venting RequirementsVent Pipe Material Vent Pipe Length and DiameterPipe Routing and Support Vent Pipe InstallationSolution ExampleG6RL Downflow Furnaces G6RC & G6RD Upflow FurnacesG6RC & G6RD Upflow Furnaces G6RC & G6RD UpflowFurnaces G6RL Downflow FurnacesVent Termination Clearances Location of Outdoor TerminationsHorizontal Venting Alternate Horizontal Vent InstallationVertical Venting Vent Freezing ProtectionConcentric Vent Termination Vertical Vent Termination Drainage of Condensate from FurnaceLeak Check GAS Supply and PipingLP/Propane Gas Sea Level and High Altitude Conversion ConversionHigh Altitude Application Natural Gas High Altitude ConversionLine Voltage Wiring Electrical WiringAbove Sea Level START-UP and AdjustmentsLow Voltage Wiring Furnace Rating Orifice Drill Size Plate Input Btu/h NatStart-Up Procedure Verifying and Adjusting Firing RateElectrical Data Verifying Burner Operation Verifying and Adjusting Temperature RiseGas Flow Rate GAS Flow Rate Cubic Feet PER HourDescription of Components Verifying Operation of the Supply Air Limit SwitchFor G6RC, G6RD and G6RL Residential Furnaces G6RC, G6RD and G6RL Integrated Control Board System DiagramSystem Operation Information MaintenanceLocation of Major Components G6RL Downflow FurnaceHeating Mode Cooling ModeSequence of Operation Fan Mode Furnace Fails to OperateTwinning of Two Furnaces Fuel Type INSTALLATION/PERFORMANCE Check List¢707931*¤