Sequence of Operation

Operating sequences for the heating, cooling, and fan modes are described below. Refer to the wiring diagrams (Figures 26 and 27) and the low voltage field wiring diagram (Figure 24).

Heating Mode:

1.On a call for heat the thermostat closes, applying 24 VAC to the W terminal on the control board.

2.The control board checks for continuity on the 24 VAC limit control circuit (over-tem- perature limit switch, flame rollout switches and blocked vent switch in series). If an open limit is detected the control board will energize the inducer and the conditioned air blower. All other system functions will be inoperable until the limit circuit closes. While the limit is open, the red LED will pulse at a rate of 1 blink per unit time.

3.The furnace control checks for continuity across the pressure switch (24 VAC). If the pressure switch is closed the heat mode sequence will not continue. If it remains closed for 10 seconds the red LED will blink 3 times repetitively until the fault condition clears.

4.The inducer is energized.

5.The pressure switch will close. If the pres- sure switch does not close after 10 seconds the fault LED will blink 2 times repetitively and the inducer will continue to run until the switch is closed.

6.The inducer will pre-purge for 30 seconds and then the ignitor will start its warm-up. After 30 seconds of ignitor warm-up the gas valve (24 VAC) will open. The ignitor circuit stays energized for 6 seconds after the gas valve opens.

7.The furnace control must prove flame via the flame sensor six seconds after the gas valve opens. If flame is sensed, all burners are on and the ignitor cools off. If no flame is sensed, the gas valve closes immediately and the inducer continues to run. A second trial for ignition (step 6) begins if no flame is sensed. On the fifth try for ignition, the furnace control is locked out and the red LED will blink 4 times repetitively. The ther- mostat must be opened for at least ten seconds to reset the furnace control after a lock out. Otherwise, the furnace will attempt another ignition sequence in 1 hour.

8.The furnace control energizes the circulat- ing air blower on the heating speed 30 seconds after the gas valve circuit is ener- gized .

9.When the thermostat has been satisfied, gas valve is de-energized.

10.The inducer is de-energized after a 30 second postpurge.

11.The furnace control keeps the circulating air blower energized for 120 seconds (factory set) or 60, 90, or 180 seconds (field adjust- able). (See Figure 25.)

12.Abnormal conditions: If a limit opens during operation, the inducer and circulating air blower continue to operate. The gas valve is de-energized immediately. The blowers continue to operate until the limit closes. When the limit closes the inducer blower is de-energized immediately. The circulating air blower continues to operate for the speci- fied delay (factory set at 120 seconds).

Cooling Mode:

1.On a call for cooling the thermostat closes, applying 24 VAC to the G and Y terminals on the furnace control. This closes the compressor contactor.

2.The furnace control energizes the circulat- ing blower (115 VAC) on the cooling speed.

3.When the thermostat is satisfied, the G and Y terminals on the control board are de-energized opening the compressor con- tactor.

4.The circulating air blower is de-energized after a 90 second delay.

33

Image 33
Contents What to do if YOU Smell GAS Installation InstructionsPage Table of Contents Upflow G6RC & G6RD Furnaces DimensionsDownflow G6RL Furnace High 1910 1860 1780 1700 1620 1520 1420 Furnace Airflow DataModel Input Motor Number Btuh Speed Clearances to Combustible Materials Installation Requirements Requirements and CodesSupply AIR Plenum Installation Horizontal InstallationsLocation Downflow Warning G6RL ModelsFurnace on a Concrete Slab Circulating AIR SupplyVenting and Combustion AIR Requirements Return AirMinimum Free Area40,000 100 sq. 60,000 80,000 Installation In An Unconfined Space Air Requirements For One-Pipe InstallationInstallation In a Confined Space Air From InsideVent Pipe Material Venting RequirementsVent Pipe Length and Diameter Air Directly Through An Exterior WallSolution Vent Pipe InstallationExample Pipe Routing and SupportG6RL Downflow Furnaces G6RC & G6RD Upflow FurnacesFurnaces G6RC & G6RD UpflowG6RL Downflow Furnaces G6RC & G6RD Upflow FurnacesVent Termination Clearances Location of Outdoor TerminationsHorizontal Venting Alternate Horizontal Vent InstallationVertical Venting Vent Freezing ProtectionConcentric Vent Termination Vertical Vent Termination Drainage of Condensate from FurnaceLeak Check GAS Supply and PipingHigh Altitude Application ConversionNatural Gas High Altitude Conversion LP/Propane Gas Sea Level and High Altitude ConversionLine Voltage Wiring Electrical WiringLow Voltage Wiring START-UP and AdjustmentsFurnace Rating Orifice Drill Size Plate Input Btu/h Nat Above Sea LevelStart-Up Procedure Verifying and Adjusting Firing RateElectrical Data Verifying Burner Operation Verifying and Adjusting Temperature RiseGas Flow Rate GAS Flow Rate Cubic Feet PER HourDescription of Components Verifying Operation of the Supply Air Limit SwitchFor G6RC, G6RD and G6RL Residential Furnaces G6RC, G6RD and G6RL Integrated Control Board System DiagramSystem Operation Information MaintenanceLocation of Major Components G6RL Downflow FurnaceHeating Mode Cooling ModeSequence of Operation Fan Mode Furnace Fails to OperateTwinning of Two Furnaces Fuel Type INSTALLATION/PERFORMANCE Check List¢707931*¤