Nordyne G6RC 90+, G6RL 90+, G6RD 93+ Horizontal Venting, Alternate Horizontal Vent Installation

Page 19

5.The vent termination for a 1-pipe installa- tion shall be a minimum of 3 ft. above any forced air inlet within 10 ft.

6.The vent termination shall be located at least 4 ft. horizontally from any electric meter, gas meter, regulator and any relief equipment. These distances apply ONLY to U.S. installations. In Canada, the Canadian Fuel Gas Code takes precedence.

7.Avoid areas where condensate drainage may cause problems by dropping on plant- ers or patios, etc. Also ensure that exhaust gases will not impinge on windows or build- ing surfaces, which may be compromised or damaged by condensation. Do not install the vent terminal such that exhaust is di- rected into window wells, stairwells, under decks or into alcoves or similar recessed areas, and do not terminate above any public walkways.

8.Select the point of wall penetration where the minimum 1/4 inch per foot of slope up can be maintained.

!CAUTION:

For optimum performance, vent fur- nace through wall which experiences the least exposure to winter winds.

Horizontal Venting

Vent and combustion air intake terminations must be as shown in Figure 19.

!WARNING:

Ensure that the combustion air vent and the exhaust vent are configured as shown in Figure 19. Improper vent termination can cause recirculation of the flue gases. This may result in fur- nace vibration. In severe cases, the furnace will cycle due to the intermit- tent contact between the flame and the flame sensor. If you note oscillations occurring, check the vent configura- tion. Make sure that the exhaust vent does not have a 90 degree termination.

Vent Configuration to

 

Provide 12" Minimum

 

height above

 

 

Snow Level.

12" Min.

 

 

 

 

19" Max.

 

Outside

Support

12" Above

Wall

 

 

Normally

 

 

Pipe

 

Expected

1/2"

Snow

Coupling

Level

Armaflex

 

 

 

Insulation or

 

 

Equivalent

 

Figure 18. Alternate Horizontal Vent

Installation

For horizontal venting, one of the following kits is recommended:

 

2" PVC

3" PVC

Through-the-Wall

9023730

9023750

Exterior Vent

Mounting Kit

 

 

Neutralizer Kit - All

9023730

9023730

Models

 

 

For Canadian installations please refer to the Canadian Installation Code (CAN/CGA-B149.1 or 2) and/or local codes.

The kit consists of two face plates and an insulating gasket to seal the exterior surface. A hole sized closely to the pipe diameter must first be cut through the wall. A short length of pipe is then cut such that it can penetrate the wall and be held in place by closely fitting standard cou- plings. The face plates are retained on both sides of the wall by the couplings, and the gasket is retained against the wall by the outer face plate. Face plates must be fastened to the wall and the outside one must be flashed as appro- priate to prevent entry of water.

When the above kits are not used the following steps are required:

1.Check the hole size cut through the exterior wall. Insure that the hole diameter is less than the diameter of the couplings to be used.

2.Extend the vent pipe through the wall ap- proximately 1" and seal the area between the wall and pipe.

19

Image 19
Contents What to do if YOU Smell GAS Installation InstructionsPage Table of Contents Upflow G6RC & G6RD Furnaces DimensionsDownflow G6RL Furnace High 1910 1860 1780 1700 1620 1520 1420 Furnace Airflow DataModel Input Motor Number Btuh Speed Clearances to Combustible Materials Installation Requirements Requirements and CodesDownflow Warning G6RL Models Horizontal InstallationsSupply AIR Plenum Installation LocationFurnace on a Concrete Slab Circulating AIR SupplyVenting and Combustion AIR Requirements Return AirFree Area Minimum40,000 100 sq. 60,000 80,000 Air From Inside Air Requirements For One-Pipe InstallationInstallation In An Unconfined Space Installation In a Confined SpaceAir Directly Through An Exterior Wall Venting RequirementsVent Pipe Material Vent Pipe Length and DiameterPipe Routing and Support Vent Pipe InstallationSolution ExampleG6RL Downflow Furnaces G6RC & G6RD Upflow FurnacesG6RC & G6RD Upflow Furnaces G6RC & G6RD UpflowFurnaces G6RL Downflow FurnacesVent Termination Clearances Location of Outdoor TerminationsHorizontal Venting Alternate Horizontal Vent InstallationVent Freezing Protection Vertical VentingConcentric Vent Termination Vertical Vent Termination Drainage of Condensate from FurnaceLeak Check GAS Supply and PipingLP/Propane Gas Sea Level and High Altitude Conversion ConversionHigh Altitude Application Natural Gas High Altitude ConversionLine Voltage Wiring Electrical WiringAbove Sea Level START-UP and AdjustmentsLow Voltage Wiring Furnace Rating Orifice Drill Size Plate Input Btu/h NatVerifying and Adjusting Firing Rate Start-Up ProcedureElectrical Data Verifying Burner Operation Verifying and Adjusting Temperature RiseGas Flow Rate GAS Flow Rate Cubic Feet PER HourDescription of Components Verifying Operation of the Supply Air Limit SwitchFor G6RC, G6RD and G6RL Residential Furnaces G6RC, G6RD and G6RL Integrated Control Board System DiagramSystem Operation Information MaintenanceLocation of Major Components G6RL Downflow FurnaceCooling Mode Heating ModeSequence of Operation Furnace Fails to Operate Fan ModeTwinning of Two Furnaces Fuel Type INSTALLATION/PERFORMANCE Check List¢707931*¤