Rinnai RV53E, RV53I installation manual Water Piping, Isolation Valves and Pressure Relief Valve

Page 18

Water Piping

Isolation Valves and Pressure Relief Valve

The isolation valves provide the ability to isolate the water heater from the structure’s plumbing and allow quick access to flush the heat exchanger. Check with local codes to determine if a pressure and temperature relief valve is required. The included valves meet American National Standard (ANSI Z21.10.3) / Canadian Standard (CSA 4.3) and are ANSI/NSF 65 approved for potable water.

Isolation Valve (Cold)

107000081

 

 

Isolation Valve (Hot)

107000083

 

 

RV53i Pressure Relief Valve (PRV)

107000085

 

 

RV53e Pressure Relief Valve (PRV)

107000086

 

 

Isolation Valves Installation Instructions:

1.Wrap the ends of the threaded water inlet & outlet on the tankless water heater,as well as the threaded end of the approved pressure relief valve with a minimum of 5 wraps of Teflon® tape.

2.Screw the pressure relief valve into the 3/4” threads opposite the wing handle on the HOT water service valve. (RED drain handle) (see Pressure Relief Valve Section for proper installation requirements)

3.Loosen the 3/4” union nut on the HOT water valve and connect to the HOT water outlet on the tankless water heater. If nut is removed, ensure that you realign the tailpiece accurately to the valve and that the black washer is positioned such that the raised metal edge of the valve is inside the washer.

4.Align the direction of the HOT water drain to the desired position.

5.Tighten the union assembly to the HOT water valve using approximately 15 foot lbs of torque.

6.Repeat steps 3-5 for the COLD water valve. (BLUE drain handle) for connection to the COLD water inlet on the tankless water heater.

7.Connect the INLET on the COLD water valve to the MAIN SOURCE of the water supply.

8.Connect the OUTLET on the HOT water valve to the HOT WATER plumbing system.

9.Ensure that both drain valve lever handles are in the closed position (perpendicular to the drain portion of the body).

Pressure Relief Valve Installation Instructions:

The PRV must be connected by the threaded connection opposite the wing handle on the hot water valve (designated by the RED drain handle) or the threaded connection on the side of the relocation fitting above the hot water valve. Installation must maintain a ¾” port size with no shut off valve or line restriction in-between the appliance and the PRV. The discharge line from the PRV should pitch downward and terminate 6” above drains where discharge will be clearly visible. The discharge end of the line shall be plain (unthreaded) and a minimum of ¾” in diameter. The discharge line material must be suitable for water at least 180º Fahrenheit and can be no more than 30 feet in length and contain no more than 4 elbows or bends. No valve of any type may be installed in the discharge line of the pressure relief valve.

Pressure Relief Valve Maintenance:

For proper care of this approved pressure relief valve, it is recommended that the valve is manually operated once a year. In doing so, it will be necessary to

take precautions with regard to the discharge of potentially scalding hot water under pressure. Ensure discharge has a place to flow. Contact with your body or other property may cause damage or harm. Please note that only the PRV in this package is certified by CSA International as an approved item.

18

RV53i & RV53e Operation and Installation Manual

Image 18
Contents Result causing property damage, personal injury or death ANS Z21.10.3 CSATable of Contents Specifications ModelSafety Behaviors and Practices Safety Features Consumer Safety InformationSafety Definitions Description of OperationHow to Set the Temperature Operating InstructionsModel Temperature Settings Available ºF Temperature Controller SettingsTemperature Options Without a Temperature Controller MCC-91 Temperature ControllerUsing the Water Smart / Bath Fill Function Setting the Water VolumeOverview Filling the Tub Setting Controller to MuteSetting the Clock Models MC-91 and MCC-91Maintenance Error Codes Code Fault RemedyCode Trouble Shooting for Common Issues Accessing Operating InformationWater Quality Flushing the Heat Exchanger Error Code LC or Circulating PumpInstallation Instructions General InstructionsClearances from Appliance Attachment of the Water HeaterRV53iRV53e RV53i Electrical ConnectionGas Piping RV53ePipe Sizing Procedure Example Pressure Relief Valve Maintenance Isolation Valves Installation InstructionsPressure Relief Valve Installation Instructions Water PipingPressure Relief Valve Freeze ProtectionWhen the water heater or external piping has frozen Freeze Protection MethodsManual draining of the water heater Freeze Protection Piping KEYError Indication or Air Handler Control Switch RV53i Recommended Piping for Basic InstallationRinnai Water Heater Recommended Piping for Circulation Systems For this applicationIntake / Exhaust Guidelines Installation requirementsVenting Instructions RV53i CondensateMaximum Vent Length Vent ProductsManufacturer Product Parts Flue Installation Concentric Venting RV53i Description Canadian Installations US Installations Flue Terminal Clearances ANS Z21.10.3, CSAAdditional Clearances RV53iNumber Connected Accessories Necessary Water Heaters Connecting Multiple Water HeatersHigh Altitude Installations GuidelinesCanada only Location Temperature Controller InstallationConfigurations Cable Lengths and SizeTemperature Controller Mounting the Controller RV53iMounting the Controller RV53e For Your Safety Read Before Operating Operating InstructionsTechnical Data Pressure Drop CurveOutlet Flow Data Space Heating Temperature SettingReplacement PumpsDimensions RV53eLadder Diagrams What is covered? Warranty InformationLimited Warranty Consumer SupportHow do I get service? What is not covered? What will Rinnai do?Limitation on warranties State Regulations Important In the State of Massachusetts 248 CMR 4.00Instructions d’installation Instructions dutilisationSupport à la clientele Instructions dutilisation Temp. d’eauModel Arrangements de température disponibles ºF Plages de température avec un contrôleur de températureOptions de température sans contrôleur de température Les températures suggérées sont deEntretien Instructions dinstallation Instructions généralesÉcartements par rapport à lappareil Fixation du chauffe-eauInstallation à altitude élevée Tuyauterie de gazInstructions générales Valve de dégagement de pression Instructions d’Installation Tuyauterie deauValve à Bille / Valve de dégagement de pression Qualité de leau Soupape de sûretéNiveau maximum Tuyauterie recommandée pour installation de base LégendeInstructions de ventilation RV53i Consignes pour aspiration/évacuationCondensat Longueur maximum de ventilation Produits de ventilationConstructeur Produit Pièces Espacements pour terminaison de cheminée ANS Z21.10.3, CSA Installation de conduit de cheminée RV53i Instructions dutilisation VanneMa ualmanuelleValveDiagramme en escalier FUS TherGarantie limitée Support à la clientèleLinformation de garantie Quest-ce qui est couvert ?Que fait Rinnai pour exercer la garantie ? Limitation sur les garantiesU287-1821X0100