Rinnai RV53I, RV53E installation manual Flue Terminal Clearances ANS Z21.10.3, CSA

Page 27

Flue Terminal Clearances (ANS Z21.10.3, CSA 4.3)

INSIDE

CORNER DETAIL

G

H

D

E

B

L

A

C

FIXED

CLOSED

OPERABLE

 

B

B

FIXED

CLOSED

 

OPERABLE

B

J

 

 

B

 

A

I M

K

X AIR SUPPLY INLET

V

F

B

VENT TERMINAL

AREA WHERE TERMINAL IS NOT PERMITTTED

Ref

Description

Canadian Installations

US Installations

 

 

 

 

A

Clearance above grade, veranda, porch, deck, or balcony

12 inches (30 cm)

12 inches (30 cm)

 

 

 

 

B

Clearance to window or door that may be opened

36 inches (91 cm)

12 inches (30 cm)

 

 

 

 

C

Clearance to permanently closed window

*

*

 

 

 

 

 

Vertical clearance to ventilated soffit, located above the terminal

 

 

D

within a horizontal distance of 2 feet (61 cm) from the center line

*

*

 

of the terminal

 

 

 

 

 

 

E

Clearance to unventilated soffit

*

*

 

 

 

 

F

Clearance to outside corner

*

*

 

 

 

 

G

Clearance to inside corner

*

*

 

 

 

 

H

Clearance to each side of center line extended above meter/

3 feet (91 cm) within a height

 

15 feet (4.5 m) above the

*

regulator assembly

 

meter/regulator assembly

 

 

 

 

 

 

 

 

I

Clearance to service regulator vent outlet

36 inches (91 cm)

*

 

 

 

 

J

Clearance to nonmechanical air supply inlet to building or the

36 inches (91 cm)

12 inches (30 cm)

combustion air inlet to any other appliance

 

 

 

 

 

 

 

K

Clearance to a mechanical air supply inlet

6 feet (1.83 m)

3 feet (91 cm) above if within

10 feet (3 m) horizontally

 

 

 

 

 

 

 

L

Clearance above paved sidewalk or paved driveway located on

7 feet (2.13 m) 1

*

public property

 

 

 

 

 

 

 

M

Clearance under veranda, porch, deck, or balcony

12 inches (30 cm) 2

*

 

 

 

 

1A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwellings and serves both dwellings.

2Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.

For clearances not specified in ANSI Z223.1/NFPA 54 or CSA B149.1, clearances are in accordance with local installation codes and the requirements of the gas supplier.

Clearance to opposite wall is 24 inches (60 cm) for Canada and US.

RV53i & RV53e Operation and Installation Manual

27

Image 27
Contents ANS Z21.10.3 CSA Result causing property damage, personal injury or deathTable of Contents Model SpecificationsDescription of Operation Consumer Safety InformationSafety Definitions Safety Behaviors and Practices Safety FeaturesOperating Instructions How to Set the TemperatureMCC-91 Temperature Controller Temperature Controller SettingsTemperature Options Without a Temperature Controller Model Temperature Settings Available ºFUsing the Water Smart / Bath Fill Function Setting the Water VolumeOverview Models MC-91 and MCC-91 Setting Controller to MuteSetting the Clock Filling the TubMaintenance Code Fault Remedy Error CodesCode Trouble Shooting for Common Issues Accessing Operating InformationWater Quality Circulating Pump Flushing the Heat Exchanger Error Code LC orGeneral Instructions Installation InstructionsClearances from Appliance Attachment of the Water HeaterRV53iRV53e RV53e Electrical ConnectionGas Piping RV53iPipe Sizing Procedure Example Water Piping Isolation Valves Installation InstructionsPressure Relief Valve Installation Instructions Pressure Relief Valve MaintenanceFreeze Protection Pressure Relief ValveWhen the water heater or external piping has frozen Freeze Protection MethodsManual draining of the water heater KEY Freeze Protection PipingError Indication or Air Handler Control Switch RV53i Recommended Piping for Basic InstallationRinnai Water Heater For this application Recommended Piping for Circulation SystemsCondensate Installation requirementsVenting Instructions RV53i Intake / Exhaust GuidelinesMaximum Vent Length Vent ProductsManufacturer Product Parts Flue Installation Concentric Venting RV53i Flue Terminal Clearances ANS Z21.10.3, CSA Description Canadian Installations US InstallationsRV53i Additional ClearancesGuidelines Connecting Multiple Water HeatersHigh Altitude Installations Number Connected Accessories Necessary Water HeatersCanada only Cable Lengths and Size Temperature Controller InstallationConfigurations LocationMounting the Controller RV53i Temperature ControllerMounting the Controller RV53e Operating Instructions For Your Safety Read Before OperatingTechnical Data Pressure Drop CurveOutlet Flow Data Pumps Temperature SettingReplacement Space HeatingRV53e DimensionsLadder Diagrams Consumer Support Warranty InformationLimited Warranty What is covered?How do I get service? What is not covered? What will Rinnai do?Limitation on warranties Important In the State of Massachusetts 248 CMR 4.00 State RegulationsInstructions d’installation Instructions dutilisationSupport à la clientele Temp. d’eau Instructions dutilisationLes températures suggérées sont de Plages de température avec un contrôleur de températureOptions de température sans contrôleur de température Model Arrangements de température disponibles ºFEntretien Instructions générales Instructions dinstallationFixation du chauffe-eau Écartements par rapport à lappareilInstallation à altitude élevée Tuyauterie de gazInstructions générales Valve de dégagement de pression Instructions d’Installation Tuyauterie deauValve à Bille / Valve de dégagement de pression Qualité de leau Soupape de sûretéNiveau maximum Légende Tuyauterie recommandée pour installation de baseInstructions de ventilation RV53i Consignes pour aspiration/évacuationCondensat Longueur maximum de ventilation Produits de ventilationConstructeur Produit Pièces Espacements pour terminaison de cheminée ANS Z21.10.3, CSA Installation de conduit de cheminée RV53i VanneMa ualmanuelleValve Instructions dutilisationFUS Ther Diagramme en escalierQuest-ce qui est couvert ? Support à la clientèleLinformation de garantie Garantie limitéeLimitation sur les garanties Que fait Rinnai pour exercer la garantie ?U287-1821X0100