Gas Piping

Pipe Sizing Procedure - Example

The gas supply must be capable of handling the entire gas load at the location. Gas line sizing is based on gas type, the pressure drop in the system, the gas pressure supplied, and gas line type. For gas pipe sizing in the United States, refer to the National Fuel Gas Code, NFPA 54. For Canadian gas pipe sizing, refer to the Natural Gas and Propane Installation Code CAN/CSA B149.1. The below information is provided as an example. The appropriate table from the applicable code must be used.

1.For some tables, you will need to determine the cubic feet per hour of gas required by dividing the gas input by the heating value of the gas (available from the local gas company). The gas input needs to include all gas products at the location and the maximum BTU usage at full load when all gas products are in use.

Gas Input of all gas products (BTU / HR)

Cubic Feet per Hour (CFH) =

Heating Value of Gas (BTU / FT 3 )

2.Use the table for your gas type and pipe type to find the pipe size required. The pipe size must be able to provide the required cubic feet per hour of gas or the required BTU/hour.

Example: The heating value of natural gas for your location is 1000 BTU/FT3. The gas input of the RV53i is 150,000 BTU/HR. Additional appliances at the location require 114,000 BTU/hr. Therefore the cubic feet per hour = (150,000 + 114,000) / 1000 = 264 FT3/HR. If the pipe length is 10 feet then the 3/4 inch pipe size is capable of supplying 264 FT3/HR of natural gas.

Length

 

Pipe Size (inches)

 

3/4

1

1 1/4

1 1/2

 

10

273

514

1060

1580

20

188

353

726

1090

30

151

284

583

873

40

129

243

499

747

50

114

215

442

662

60

104

195

400

600

70

95

179

368

552

80

89

167

343

514

 

 

 

 

 

90

83

157

322

482

 

 

 

 

 

100

79

148

304

455

 

 

 

 

 

125

70

131

269

403

 

 

 

 

 

150

63

119

244

366

 

 

 

 

 

175

58

109

224

336

 

 

 

 

 

200

54

102

209

313

 

 

 

 

 

Length

 

Pipe Size (inches)

 

 

 

 

 

1/2

3/4

1

1 1/4

 

 

 

 

 

 

10

291

608

1150

2350

 

 

 

 

 

20

200

418

787

1620

 

 

 

 

 

30

160

336

632

1300

 

 

 

 

 

40

137

287

541

1110

 

 

 

 

 

50

122

255

480

985

 

 

 

 

 

60

110

231

434

892

 

 

 

 

 

80

101

212

400

821

 

 

 

 

 

100

94

197

372

763

 

 

 

 

 

125

89

185

349

716

 

 

 

 

 

150

84

175

330

677

 

 

 

 

 

175

74

155

292

600

 

 

 

 

 

200

67

140

265

543

 

 

 

 

 

RV53i & RV53e Operation and Installation Manual

17

Image 17
Contents ANS Z21.10.3 CSA Result causing property damage, personal injury or deathTable of Contents Model SpecificationsSafety Definitions Consumer Safety InformationSafety Behaviors and Practices Safety Features Description of OperationOperating Instructions How to Set the TemperatureTemperature Options Without a Temperature Controller Temperature Controller SettingsModel Temperature Settings Available ºF MCC-91 Temperature ControllerOverview Using the Water Smart / Bath Fill FunctionSetting the Water Volume Setting the Clock Setting Controller to MuteFilling the Tub Models MC-91 and MCC-91Maintenance Code Fault Remedy Error CodesCode Water Quality Trouble Shooting for Common IssuesAccessing Operating Information Circulating Pump Flushing the Heat Exchanger Error Code LC orGeneral Instructions Installation InstructionsRV53iRV53e Clearances from ApplianceAttachment of the Water Heater Gas Piping Electrical ConnectionRV53i RV53ePipe Sizing Procedure Example Pressure Relief Valve Installation Instructions Isolation Valves Installation InstructionsPressure Relief Valve Maintenance Water PipingFreeze Protection Pressure Relief ValveManual draining of the water heater When the water heater or external piping has frozenFreeze Protection Methods KEY Freeze Protection PipingRinnai Water Heater Error Indication or Air Handler Control Switch RV53iRecommended Piping for Basic Installation For this application Recommended Piping for Circulation SystemsVenting Instructions RV53i Installation requirementsIntake / Exhaust Guidelines CondensateManufacturer Product Parts Maximum Vent LengthVent Products Flue Installation Concentric Venting RV53i Flue Terminal Clearances ANS Z21.10.3, CSA Description Canadian Installations US InstallationsRV53i Additional ClearancesHigh Altitude Installations Connecting Multiple Water HeatersNumber Connected Accessories Necessary Water Heaters GuidelinesCanada only Configurations Temperature Controller InstallationLocation Cable Lengths and SizeMounting the Controller RV53i Temperature ControllerMounting the Controller RV53e Operating Instructions For Your Safety Read Before OperatingOutlet Flow Data Technical DataPressure Drop Curve Replacement Temperature SettingSpace Heating PumpsRV53e DimensionsLadder Diagrams Limited Warranty Warranty InformationWhat is covered? Consumer SupportLimitation on warranties How do I get service? What is not covered?What will Rinnai do? Important In the State of Massachusetts 248 CMR 4.00 State RegulationsSupport à la clientele Instructions d’installationInstructions dutilisation Temp. d’eau Instructions dutilisationOptions de température sans contrôleur de température Plages de température avec un contrôleur de températureModel Arrangements de température disponibles ºF Les températures suggérées sont deEntretien Instructions générales Instructions dinstallationFixation du chauffe-eau Écartements par rapport à lappareilInstructions générales Installation à altitude élevéeTuyauterie de gaz Valve à Bille / Valve de dégagement de pression Valve de dégagement de pression Instructions d’InstallationTuyauterie deau Niveau maximum Qualité de leauSoupape de sûreté Légende Tuyauterie recommandée pour installation de baseCondensat Instructions de ventilation RV53iConsignes pour aspiration/évacuation Constructeur Produit Pièces Longueur maximum de ventilationProduits de ventilation Espacements pour terminaison de cheminée ANS Z21.10.3, CSA Installation de conduit de cheminée RV53i VanneMa ualmanuelleValve Instructions dutilisationFUS Ther Diagramme en escalierLinformation de garantie Support à la clientèleGarantie limitée Quest-ce qui est couvert ?Limitation sur les garanties Que fait Rinnai pour exercer la garantie ?U287-1821X0100