Space Heating

If the water heater is to be used for both water (potable) heating and space heating then the following apply.

The piping and components connected to the water heater shall be suitable for use with potable water.

Toxic chemicals, such as used for boiler treatment, shall not be introduced into the potable water.

The water heater shall not be connected to any heating system or components previously used with a nonpotable water heating appliance.

When the system requires water for space heating at temperatures higher than required for other uses, a means such as a mixing valve shall be installed to temper the water for other uses in order to reduce the scald hazard potential.

Space heating applications are considered commercial applications for warranty purposes.

Temperature Setting

When using this appliance to provide domestic hot water it is recommended that the domestic hot water temperature be reduced to acceptable temperatures in accordance with local codes. In the absence of local codes it is recommended that the domestic hot water temperature be set to 140º F (60º C) or lower in accordance with UPC 501.6 by using mixing valves or the temperature controller for the water heater.

Pumps

Only use pumps of brass or stainless steel construction. Do not use pumps of iron construction as they will oxidize and clog the inlet filter on the appliance.

Pumps circulating water through the water heater must be sized to overcome the pressure loss through the water heater, the heating system, and any additional plumbing pressure losses. The pressure drop curve based on the water heater model is provided in this manual.

Replacement

When replacing an existing space heating application’s water heating source (boiler, tank water heater, tankless water heater, etc.) with Rinnai water heaters, ensure that the water heaters are sized to adequately provide the necessary BTU input for the desired space heating application. Rinnai water heaters are designed to maintain a constant outlet temperature and will supply only the necessary amount of BTU’s to maintain that temperature. Depending on the application the maximum BTU rating of the unit may not be achieved. Contact Rinnai’s Applications Engineering Department for assistance at (800) 621-9419 ext. 4490.

Iron Components

Do not use Rinnai water heaters directly for space heating applications involving iron radiators or applications with any iron components. Iron components may oxidize creating rust that will clog the inlet filter of the Rinnai water heater.

36

RV53i & RV53e Operation and Installation Manual

Image 36
Contents Result causing property damage, personal injury or death ANS Z21.10.3 CSATable of Contents Specifications ModelConsumer Safety Information Safety DefinitionsSafety Behaviors and Practices Safety Features Description of OperationHow to Set the Temperature Operating InstructionsTemperature Controller Settings Temperature Options Without a Temperature ControllerModel Temperature Settings Available ºF MCC-91 Temperature ControllerUsing the Water Smart / Bath Fill Function Setting the Water VolumeOverview Setting Controller to Mute Setting the ClockFilling the Tub Models MC-91 and MCC-91Maintenance Error Codes Code Fault RemedyCode Trouble Shooting for Common Issues Accessing Operating InformationWater Quality Flushing the Heat Exchanger Error Code LC or Circulating PumpInstallation Instructions General InstructionsClearances from Appliance Attachment of the Water HeaterRV53iRV53e Electrical Connection Gas PipingRV53i RV53ePipe Sizing Procedure Example Isolation Valves Installation Instructions Pressure Relief Valve Installation InstructionsPressure Relief Valve Maintenance Water PipingPressure Relief Valve Freeze ProtectionWhen the water heater or external piping has frozen Freeze Protection MethodsManual draining of the water heater Freeze Protection Piping KEYError Indication or Air Handler Control Switch RV53i Recommended Piping for Basic InstallationRinnai Water Heater Recommended Piping for Circulation Systems For this applicationInstallation requirements Venting Instructions RV53iIntake / Exhaust Guidelines CondensateMaximum Vent Length Vent ProductsManufacturer Product Parts Flue Installation Concentric Venting RV53i Description Canadian Installations US Installations Flue Terminal Clearances ANS Z21.10.3, CSAAdditional Clearances RV53iConnecting Multiple Water Heaters High Altitude InstallationsNumber Connected Accessories Necessary Water Heaters GuidelinesCanada only Temperature Controller Installation ConfigurationsLocation Cable Lengths and SizeTemperature Controller Mounting the Controller RV53iMounting the Controller RV53e For Your Safety Read Before Operating Operating InstructionsTechnical Data Pressure Drop CurveOutlet Flow Data Temperature Setting ReplacementSpace Heating PumpsDimensions RV53eLadder Diagrams Warranty Information Limited WarrantyWhat is covered? Consumer SupportHow do I get service? What is not covered? What will Rinnai do?Limitation on warranties State Regulations Important In the State of Massachusetts 248 CMR 4.00Instructions d’installation Instructions dutilisationSupport à la clientele Instructions dutilisation Temp. d’eauPlages de température avec un contrôleur de température Options de température sans contrôleur de températureModel Arrangements de température disponibles ºF Les températures suggérées sont deEntretien Instructions dinstallation Instructions généralesÉcartements par rapport à lappareil Fixation du chauffe-eauInstallation à altitude élevée Tuyauterie de gazInstructions générales Valve de dégagement de pression Instructions d’Installation Tuyauterie deauValve à Bille / Valve de dégagement de pression Qualité de leau Soupape de sûretéNiveau maximum Tuyauterie recommandée pour installation de base LégendeInstructions de ventilation RV53i Consignes pour aspiration/évacuationCondensat Longueur maximum de ventilation Produits de ventilationConstructeur Produit Pièces Espacements pour terminaison de cheminée ANS Z21.10.3, CSA Installation de conduit de cheminée RV53i Instructions dutilisation VanneMa ualmanuelleValveDiagramme en escalier FUS TherSupport à la clientèle Linformation de garantieGarantie limitée Quest-ce qui est couvert ?Que fait Rinnai pour exercer la garantie ? Limitation sur les garantiesU287-1821X0100