AIR FOR COMBUSTION AND VENTILATION
Determining
5
AIR FOR COMBUSTION AND VENTILATION
Continued
DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION
Determining if You Have a Confined or Unconfined Space
Use this work sheet to determine if you have a confined or unconfined space.
Space: Includes the room in which you will install heater plus any adjoining rooms with doorless passageways or ventilation grills between the rooms.
1.Determine the volume of the space (length x width x height). Length x Width x Height = ___________ cu. ft. (m3) (volume of space)
Example: Space size 20 ft. (6.1 m) (length) x 16 ft. (4.88 m) (width) x 8 ft. (2.44 m) (ceiling height) = 2560 cu. ft. (72.6m3) (volume of space)
If additional ventilation to adjoining room is supplied with grills or open- ings, add the volume of these rooms to the total volume of the space.
2.Multiply the space volume by 20 to determine the maximum Btu/Hr (kW) the space can support.
__________ (volume of space) x 20 = [Maximum Btu/Hr (kW) the
space can support]
Example: 2560 cu. ft. (72.6m3) (volume of space) x 20 = 51,200 [maximum Btu/Hr (kW) the space can support]
3.Add the Btu/Hr of all fuel burning appliances in the space.
| _____________ Btu/Hr (kW) | |
Gas water heater* |
| _____________ Btu/Hr (kW) |
Gas furnace |
| _____________ Btu/Hr (kW) |
Vented gas heater |
| _____________ Btu/Hr (kW) |
Gas fireplace logs |
| _____________ Btu/Hr (kW) |
Other gas appliances* + | _____________ Btu/Hr (kW) | |
Total | = | _____________ Btu/Hr (kW) |
*Do not include
Example: |
|
|
Gas water heater |
| 40,000 (11.7) |
| _____________ Btu/Hr (kW) | |
+ | 20,000 (5.9) | |
_____________ Btu/Hr (kW) | ||
Total | = | 60,000 (17.6) |
_____________ Btu/Hr (kW) |
4.Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.
__________________ Btu/Hr (kW) (maximum the space can support)
__________________ Btu/Hr (kW) (actual amount of Btu/Hr used)
Example: 51,200 Btu/Hr (15kW) (maximum the space can support)
60,000 Btu/Hr (17.6kW) [actual amount of Btu/Hr (kW) used]
The space in the above example is a confined space because the actual Btu/Hr (kW) used is more than the maximum Btu/Hr (kW) the space can support. You must provide additional fresh air. Your options are as follows:
A.Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoining room or add ventilation grills between rooms. See Ventilation Air From Inside Building, page 6.
B.Vent room directly to the outdoors. See Ventilation Air From Out- doors, page 6.
C.Install a lower Btu/Hr (kW) heater, if lower Btu/Hr (kW) size makes room unconfined.
If the actual Btu/Hr used is less than the maximum Btu/Hr (kW) the space can support, the space is an unconfined space. You will need no additional fresh air ventilation.
WARNING: If the area in which the heater may be operated is smaller than that defined as an unconfined space or if the building is of unusually tight construc- tion, provide adequate combustion and ventilation air by one of the methods described in CAN/CGA B149.1 Natural Gas Installation Code or CAN/CGA B149.2 Propane Installation Code or applicable local code.
For more information, visit www.desatech.com