Monessen Hearth HBDV300, HBDV400 manual Vent Installation, Combustible Clearances for Vent Pipe

Page 13

VENT INSTALLATION

WARNING

This fireplace must be vented to the outside. The venting system must NEVER be attached to a chimney serving a separate solid fuel burning appliance. Each gas appliance must use a separate vent system. Do not use common vent systems.

WARNING

Horizontal sections of this vent system require a minimum of 3" clearances to combustibles at the top of the flue and 1" clearance at the sides and bottom until the flue penetrates the outside wall. A minimum 1" clearance all around the flue is acceptable at this point of penetration.

Vertical sections of this vent system require a minimum of 1" clearance to combustibles on all sides of the pipe.

A Minimum of 3" Clearance to the Top Is Required Along Horizontal Length until Flue Pipe Penetrates Outside Wall.

A Minimum 1" Clearance to Combustibles Permitted All Around Flue at Outside Wall

3"

1"

 

1"

 

1"

3"

1"

 

 

1"

Figure 7 - Combustible Clearances for Vent Pipe

54D5031

13

Image 13
Contents What to do if YOU Smell GAS ModelsContents Installer Important Safety InformationOwner Non-utility gas wells. This Never connect unit to privateGas is commonly known as Wellhead gasProduct Specifications Product Features and Code ApprovalCode Approval Listed Vented GAS Fireplace HeaterHigh Elevations PRE-INSTALLATION InformationOrifice SIZES, Pressures and BTUs Before YOU StartFireplace Framing Framing DimensionsFireplace Dimensions Fireplace DimensionsLocating Gas Fireplace Fireplace LocationClearances to Combustibles ClearancesMantel Clearances Securing Fireplace to Floor or Framing Insulation BoardInstallation Precautions Installation InformationFinishing Material Combustible Clearances for Vent Pipe Vent InstallationAfter conversion to top vent Optional TOP Vent ApplicationConfiguration the 4 100mm flue pipe Should be concentric within the 65/8Installing a Vent System in AN Outside Chase Installation PlanningFor Horizontal Termination For Vertical TerminationMinimum Distances Horizontal Vent Termination LocationFeet HOW to USE the Vent GraphRear Through the Wall Applications Venting InstallationDo not recess vent termination Rear Wall Vent InstallationInto any wall. This will cause a fire hazardMaximum Three 3 90 Elbows Per Installation Horizontal Termination ConfigurationsHorizontal Run Reduction Horizontal Termination ConfigurationBelow Grade Installation Below Grade InstallationsSupport Straps for Horizontal Runs Vertical THROUGH-THE-ROOF ApplicationsFlat Ceiling Installation Installation for Vertical TerminationMinimum chimney clearance Start the flexible vent as follows Flex Vent InstallationTypical pipe connection Installing GAS Piping to Fireplace / Burner System Location Fireplace InstallationCheck GAS Type Gas Connection Do not use open flame to check Checking GAS Pressure and Electrical InstallationRemote Wall Mounted Switch Electrical InstallationRemote Wall Switch Optional DC Remote SystemsBrick Installation Glass Removal & Brick InstallationGlass Frame Removal Placement of Lava ROCK, Rock Wool and Logs Final InstallationLog #3 Log #2 Placement of Log 7 HBDV400 only Installing Universal AndironsOperating Instructions Millivolt Leak TestingWhat to do if YOU Smell GAS Initial LightingApproved Leak Testing Method Lighting the Burner Main Burner SwitchPilot Position BURNER, Pilot and Control Compartment Cleaning and MaintenancePilot Flame BurnerGlass Door Vent SystemLogs Rock WoolStanding Pilot Ignition Symptom Possible Cause ActionTroubleshooting Fireplace Components Replacement PartsCC=Cottage Clay CR=Cottage Red Millivolt Engine Vent Components Millivolt ComponentsRefer to illustrations on previous Vent ComponentsLogs Special Requirements Special Requirements 54D5031 54D5031 54D5031 Five Year Warranty Lifetime WarrantyBasic Warranty