Monessen Hearth HBDV400, HBDV300 manual Horizontal Termination Configurations

Page 20

VENT INSTALLATION

HORIZONTAL TERMINATION CONFIGURATIONS

Since it is very important that the venting system maintain its balance between the combustion air intake and the flue gas exhaust, certain limitations as to vent configurations apply and must be strictly adhered to.

The Vent Graph, showing the relationship between vertical and horizontal side wall venting, will help to determine the vari- ous dimensions allowable. See Figure 13, page 17.

NOTE: Horizontal sections of this vent system require a minimum of 3" clearances to combustibles at the top of the flue and 1" clearance at the sides and bottom until the flue penetrates the outside wall. A minimum 1" clearance all around the flue is acceptable at this point of penetration.

Vertical sections of this vent system require a minimum of 1" clearance to combustibles on all sides of the pipe.

When vent exits through foundations less than 20" below outcrop, the termination must be flush up with outcropped wall above.

It is best to locate the fireplace in such a way that minimizes the number of offsets and horizontal vent length.

The horizontal vent run refers to the total length of vent pipe from the flue collar of the fireplace (or the top of the Transition Elbow) to the face of the outer wall.

WARNING

When installing the appliance as a rear vent unit, the 90° or 45° transition elbow attached directly to the rear of the unit is NOT INCLUDED in the following criteria and calculations, and unless specifically mentioned should be ignored when calculating venting layouts.

The maximum number of 90° elbows per side wall installation is three (3). See Figure 21.

If a 90° elbow is fitted directly on top of the fireplace flange the maximum horizontal vent run before the termination or a vertical rise is 36” (914 mm). See Figure 22.

3 x 90° Elbows

3 x 90°

Elbows

Figure 21 - Maximum Three (3) 90° Elbows

Per Installation

36" Max.

36"

Max.

Figure 22 - Maximum Horizontal Run with No Rise

20

54D5031

Image 20
Contents Models What to do if YOU Smell GASContents Owner Important Safety InformationInstaller Never connect unit to private Non-utility gas wells. ThisGas is commonly known as Wellhead gasProduct Features and Code Approval Product SpecificationsCode Approval Listed Vented GAS Fireplace HeaterPRE-INSTALLATION Information High ElevationsOrifice SIZES, Pressures and BTUs Before YOU StartFraming Dimensions Fireplace FramingFireplace Dimensions Fireplace DimensionsFireplace Location Locating Gas FireplaceMantel Clearances ClearancesClearances to Combustibles Insulation Board Securing Fireplace to Floor or FramingFinishing Material Installation InformationInstallation Precautions Vent Installation Combustible Clearances for Vent PipeOptional TOP Vent Application After conversion to top ventConfiguration the 4 100mm flue pipe Should be concentric within the 65/8Installation Planning Installing a Vent System in AN Outside ChaseFor Horizontal Termination For Vertical TerminationHorizontal Vent Termination Location Minimum DistancesHOW to USE the Vent Graph FeetVenting Installation Rear Through the Wall ApplicationsRear Wall Vent Installation Do not recess vent terminationInto any wall. This will cause a fire hazardHorizontal Termination Configurations Maximum Three 3 90 Elbows Per InstallationHorizontal Termination Configuration Horizontal Run ReductionBelow Grade Installations Below Grade InstallationVertical THROUGH-THE-ROOF Applications Support Straps for Horizontal RunsInstallation for Vertical Termination Flat Ceiling InstallationMinimum chimney clearance Flex Vent Installation Start the flexible vent as followsTypical pipe connection Check GAS Type Fireplace InstallationInstalling GAS Piping to Fireplace / Burner System Location Gas Connection Checking GAS Pressure and Electrical Installation Do not use open flame to checkElectrical Installation Remote Wall Mounted SwitchRemote Wall Switch Optional DC Remote SystemsGlass Frame Removal Glass Removal & Brick InstallationBrick Installation Final Installation Placement of Lava ROCK, Rock Wool and LogsLog #3 Log #2 Installing Universal Andirons Placement of Log 7 HBDV400 onlyLeak Testing Operating Instructions MillivoltWhat to do if YOU Smell GAS Initial LightingApproved Leak Testing Method Pilot Position Main Burner SwitchLighting the Burner Cleaning and Maintenance BURNER, Pilot and Control CompartmentPilot Flame BurnerVent System Glass DoorLogs Rock WoolSymptom Possible Cause Action Standing Pilot IgnitionTroubleshooting Replacement Parts Fireplace ComponentsCC=Cottage Clay CR=Cottage Red Millivolt Engine Millivolt Components Vent ComponentsVent Components Refer to illustrations on previousLogs Special Requirements Special Requirements 54D5031 54D5031 54D5031 Basic Warranty Lifetime WarrantyFive Year Warranty