Monessen Hearth HBDV400, HBDV300 manual Below Grade Installations

Page 22

VENT INSTALLATION

BELOW GRADE INSTALLATIONS

When it is not possible to meet the required vent terminal clearances of 12" above grade level, a snorkel kit is recommended. It allows installation depth down to 7" (178mm) below grade level. The 7" (178mm) is measured from the center of the horizontal vent pipe as it penetrates through the wall.

Ensure that sidewall venting clearances are observed. If venting system is installed below ground, we recommend a window well with adequate and proper drainage to be installed around the termination area.

If installing a snorkel, a minimum 24" vertical rise is necessary. The maximum horizontal run with the 24” vertical pipe is 36". This measurement is taken from the collar of the fireplace (or transition elbow) to the face of the exterior wall. See the Sidewall Venting Graph for extended horizontal run if the vertical exceeds 24".

1.Establish vent hole through the wall. See Figure 16, page 18.

2.Remove soil to a depth of approximately 16" below base of snorkel. Install drain pipe. Install window well (not supplied). Refill hole with 12" of coarse gravel leaving a clearance of approximately 4" below snorkel. See Figure 26.

3.Install vent system.

4.Ensure a watertight seal is made around the vent pipe coming through the wall.

5.Apply high temperature sealant caulking (supplied) around the 4" and 7" snorkel collars.

6.Slide the snorkel into the vent pipes and secure to the wall.

7.Level the soil so as to maintain a 4" clearance below snorkel. See Figure 26.

WARNING

Do not back fill around snorkel.

A clearance of at least 4" must be maintained between the snorkel and the soil.

If the foundation is recessed, use recess brackets (not supplied) for securing lower portion of the snorkel. Fasten brackets to wall first, then secure to snorkel with self drilling #8x1/2 sheet metal screws. It will be necessary to extend vent pipes out as far as the protruding wall face. See Figure 27.

 

Screws

 

 

Firestop

Minimum

 

 

 

 

 

 

4" Clearance

 

Snorkel

 

Ground

 

 

Window Well

Foundation

 

24"

Recess

Wall Screws

Gravel

Minimum

 

 

Drain

 

 

 

Watertight Seal

 

 

 

 

 

Foundation Wall

Around Pipe

Sheet Metal

 

 

Screws

 

 

 

Figure 26 - Below Grade Installation

Figure 27 - Snorkel Installation,

Recessed Foundation

22

54D5031

Image 22
Contents Models What to do if YOU Smell GASContents Installer Important Safety InformationOwner Gas is commonly known as Never connect unit to privateNon-utility gas wells. This Wellhead gasCode Approval Product Features and Code ApprovalProduct Specifications Listed Vented GAS Fireplace HeaterOrifice SIZES, Pressures and BTUs PRE-INSTALLATION InformationHigh Elevations Before YOU StartFraming Dimensions Fireplace FramingFireplace Dimensions Fireplace DimensionsFireplace Location Locating Gas FireplaceClearances to Combustibles ClearancesMantel Clearances Insulation Board Securing Fireplace to Floor or FramingInstallation Precautions Installation InformationFinishing Material Vent Installation Combustible Clearances for Vent PipeConfiguration the 4 100mm flue pipe Optional TOP Vent ApplicationAfter conversion to top vent Should be concentric within the 65/8For Horizontal Termination Installation PlanningInstalling a Vent System in AN Outside Chase For Vertical TerminationHorizontal Vent Termination Location Minimum DistancesHOW to USE the Vent Graph FeetVenting Installation Rear Through the Wall ApplicationsInto any wall. This will cause a Rear Wall Vent InstallationDo not recess vent termination fire hazardHorizontal Termination Configurations Maximum Three 3 90 Elbows Per InstallationHorizontal Termination Configuration Horizontal Run ReductionBelow Grade Installations Below Grade InstallationVertical THROUGH-THE-ROOF Applications Support Straps for Horizontal RunsInstallation for Vertical Termination Flat Ceiling InstallationMinimum chimney clearance Flex Vent Installation Start the flexible vent as followsTypical pipe connection Installing GAS Piping to Fireplace / Burner System Location Fireplace InstallationCheck GAS Type Gas Connection Checking GAS Pressure and Electrical Installation Do not use open flame to checkRemote Wall Switch Electrical InstallationRemote Wall Mounted Switch Optional DC Remote SystemsBrick Installation Glass Removal & Brick InstallationGlass Frame Removal Final Installation Placement of Lava ROCK, Rock Wool and LogsLog #3 Log #2 Installing Universal Andirons Placement of Log 7 HBDV400 onlyWhat to do if YOU Smell GAS Leak TestingOperating Instructions Millivolt Initial LightingApproved Leak Testing Method Lighting the Burner Main Burner SwitchPilot Position Pilot Flame Cleaning and MaintenanceBURNER, Pilot and Control Compartment BurnerLogs Vent SystemGlass Door Rock WoolSymptom Possible Cause Action Standing Pilot IgnitionTroubleshooting Replacement Parts Fireplace ComponentsCC=Cottage Clay CR=Cottage Red Millivolt Engine Millivolt Components Vent ComponentsVent Components Refer to illustrations on previousLogs Special Requirements Special Requirements 54D5031 54D5031 54D5031 Five Year Warranty Lifetime WarrantyBasic Warranty