Monessen Hearth HBDV300, HBDV400 manual HOW to USE the Vent Graph, Feet

Page 17

VENT INSTALLATION

TERMINATION CLEARANCES FOR BUILDINGS WITH COMBUSTIBLE

AND NONCOMBUSTIBLE EXTERIORS

G

 

 

G=6" (152mm)

 

V

Inside Corner

G

V

G = Combustible 24"(610mm) Noncombustible 18"(457mm)

V

F F=6" (152mm)

Outside Corner

H

V

J

Combustible &

Noncombustible

H = 24" (610mm)

J = 20" (508mm)

 

D

C

C

 

V

E

C = Maximum depth of 48" (1219mm) for alcove location

D = Minimum width for back wall of alcove location Combustible - 38" (965mm) Noncombustible - 24" (610mm)

E = Clearance from corner in alcove location

Combustible - 6" (152mm) Noncombustible - 2" (51mm)

Balcony with No Side Wall

Balcony with Perpendicular

Alcove Location

 

Side Wall

 

Figure 13 - Allowable Venting Chart

HOW TO USE THE VENT GRAPH

The Vent Graph should be read in conjunction with the following vent installation instructions to determine the relationship between the vertical and horizontal dimensions of the vent system.

1.Determine the height of the center of the horizontal vent pipe exiting through the outer wall. Using this dimension on the Sidewall Vent Graph below, locate the point intersecting with the slanted graph line.

2.From the point of this intersection, draw a vertical line to the bottom of the graph.

3.Select the indicated dimension, and position the fireplace in accordance with same.

Example: If the vertical dimension from the floor of the fireplace is 11' (3.4m) the horizontal run to the face of the outer wall must not exceed 14' (4.3m).

Example: If the vertical dimension from the floor of the unit is 7’ (2.14m), the horizontal run to the face of the outer wall must not exceed 81/2' (2.6m).

Sidewall Vent Graph showing the relationship between vertical and horizontal dimensions for a Direct Vent flue system.

40

 

 

 

 

Vertical

38

 

 

 

 

36

 

 

 

 

34

 

Dimensions in

 

 

 

Dimension

32

 

 

Feet

 

30

 

 

 

 

 

 

 

28

 

 

 

 

26

 

 

 

 

 

 

 

Horizontal Vent Pipe

From the Floor of Unit

24

 

 

 

22

 

 

 

20

 

 

 

18

 

 

 

16

 

 

 

14

 

 

eg: A

12

 

 

 

 

 

 

to

10

 

 

 

 

 

 

 

 

the

8

 

 

 

 

 

 

 

 

Center

6

 

 

 

 

4

 

 

 

 

2

 

 

 

 

of

 

 

 

 

the

2

4

6

8 10 12 14 16 18 20

 

 

 

Horizontal Dimension From the Outside of Termination to the Back of the Fireplace

Figure 13 - Rear Wall Venting Graph

54D5031

17

Image 17
Contents What to do if YOU Smell GAS ModelsContents Owner Important Safety InformationInstaller Non-utility gas wells. This Never connect unit to privateGas is commonly known as Wellhead gasProduct Specifications Product Features and Code ApprovalCode Approval Listed Vented GAS Fireplace HeaterHigh Elevations PRE-INSTALLATION InformationOrifice SIZES, Pressures and BTUs Before YOU StartFireplace Framing Framing DimensionsFireplace Dimensions Fireplace DimensionsLocating Gas Fireplace Fireplace LocationMantel Clearances ClearancesClearances to Combustibles Securing Fireplace to Floor or Framing Insulation BoardFinishing Material Installation InformationInstallation Precautions Combustible Clearances for Vent Pipe Vent InstallationAfter conversion to top vent Optional TOP Vent ApplicationConfiguration the 4 100mm flue pipe Should be concentric within the 65/8Installing a Vent System in AN Outside Chase Installation PlanningFor Horizontal Termination For Vertical TerminationMinimum Distances Horizontal Vent Termination LocationFeet HOW to USE the Vent GraphRear Through the Wall Applications Venting InstallationDo not recess vent termination Rear Wall Vent InstallationInto any wall. This will cause a fire hazardMaximum Three 3 90 Elbows Per Installation Horizontal Termination ConfigurationsHorizontal Run Reduction Horizontal Termination ConfigurationBelow Grade Installation Below Grade InstallationsSupport Straps for Horizontal Runs Vertical THROUGH-THE-ROOF ApplicationsFlat Ceiling Installation Installation for Vertical TerminationMinimum chimney clearance Start the flexible vent as follows Flex Vent InstallationTypical pipe connection Check GAS Type Fireplace InstallationInstalling GAS Piping to Fireplace / Burner System Location Gas Connection Do not use open flame to check Checking GAS Pressure and Electrical InstallationRemote Wall Mounted Switch Electrical InstallationRemote Wall Switch Optional DC Remote SystemsGlass Frame Removal Glass Removal & Brick InstallationBrick Installation Placement of Lava ROCK, Rock Wool and Logs Final InstallationLog #3 Log #2 Placement of Log 7 HBDV400 only Installing Universal AndironsOperating Instructions Millivolt Leak TestingWhat to do if YOU Smell GAS Initial LightingApproved Leak Testing Method Pilot Position Main Burner SwitchLighting the Burner BURNER, Pilot and Control Compartment Cleaning and MaintenancePilot Flame BurnerGlass Door Vent SystemLogs Rock WoolStanding Pilot Ignition Symptom Possible Cause ActionTroubleshooting Fireplace Components Replacement PartsCC=Cottage Clay CR=Cottage Red Millivolt Engine Vent Components Millivolt ComponentsRefer to illustrations on previous Vent ComponentsLogs Special Requirements Special Requirements 54D5031 54D5031 54D5031 Basic Warranty Lifetime WarrantyFive Year Warranty