Monessen Hearth HBDV300, HBDV400 Horizontal Termination Configuration, Horizontal Run Reduction

Page 21

VENT INSTALLATION

HORIZONTAL TERMINATION CONFIGURATION

(Continued)

If a 90° elbow is used in the horizontal vent run (level height maintained) the horizontal vent length is reduced by 36". See Figures 21 and 22, page 20. This does not apply if the 90° elbows are used to increase or redirect a vertical rise. See Figure 24.

Example: According to the vent graph (page 17) the maximum horizontal vent length in a system with a 7.5' vertical rise is 20’ (6m) and if a 90° elbow is required in the horizontal vent it must be reduced to 17' (5.2 m).

In Figures 23 and 24, Dimension A plus B must not be greater than 17' (5.2m).

The maximum number of 45° elbows permitted per side wall installation is two (2). These elbows can be installed in either the vertical or horizontal run.

For each 45° elbow installed in the horizontal run, the length of the horizontal run MUST be reduced by 18" (45cm). This does not apply if the 45° elbows are installed on the vertical part of the vent system.

 

90°

A

B

7'6"

Figure 23 - Horizontal Run Reduction

The maximum number of elbow degrees in a system is 270°. See Figure 25.

 

Example:

Elbow 1

=

90°

 

 

Elbow 2

=

45°

 

 

Elbow 3

=

45°

 

 

Elbow 4

=

90°

7' B

Total Angular Variation

=

270°

 

 

 

 

A 10'

1

 

 

 

 

 

 

 

 

2

 

 

 

 

3

 

 

 

 

4

 

 

 

90° Elbow = 3'

 

 

1

 

 

 

 

 

7'6"

 

 

2

 

 

 

3

 

A + B = 17' Maximum

 

 

 

 

 

4

 

 

 

 

 

 

1 + 2 + 3 + 4 = 270°

 

 

 

Figure 24 - Maximum Vent Run with Elbows

Figure 25 - Maximum Elbow Usage

54D5031

21

Image 21
Contents What to do if YOU Smell GAS ModelsContents Important Safety Information InstallerOwner Non-utility gas wells. This Never connect unit to privateGas is commonly known as Wellhead gasProduct Specifications Product Features and Code ApprovalCode Approval Listed Vented GAS Fireplace HeaterHigh Elevations PRE-INSTALLATION InformationOrifice SIZES, Pressures and BTUs Before YOU StartFireplace Framing Framing DimensionsFireplace Dimensions Fireplace DimensionsLocating Gas Fireplace Fireplace LocationClearances Clearances to CombustiblesMantel Clearances Securing Fireplace to Floor or Framing Insulation BoardInstallation Information Installation PrecautionsFinishing Material Combustible Clearances for Vent Pipe Vent InstallationAfter conversion to top vent Optional TOP Vent ApplicationConfiguration the 4 100mm flue pipe Should be concentric within the 65/8Installing a Vent System in AN Outside Chase Installation PlanningFor Horizontal Termination For Vertical TerminationMinimum Distances Horizontal Vent Termination LocationFeet HOW to USE the Vent GraphRear Through the Wall Applications Venting InstallationDo not recess vent termination Rear Wall Vent InstallationInto any wall. This will cause a fire hazardMaximum Three 3 90 Elbows Per Installation Horizontal Termination ConfigurationsHorizontal Run Reduction Horizontal Termination ConfigurationBelow Grade Installation Below Grade InstallationsSupport Straps for Horizontal Runs Vertical THROUGH-THE-ROOF ApplicationsFlat Ceiling Installation Installation for Vertical TerminationMinimum chimney clearance Start the flexible vent as follows Flex Vent InstallationTypical pipe connection Fireplace Installation Installing GAS Piping to Fireplace / Burner System LocationCheck GAS Type Gas Connection Do not use open flame to check Checking GAS Pressure and Electrical InstallationRemote Wall Mounted Switch Electrical InstallationRemote Wall Switch Optional DC Remote SystemsGlass Removal & Brick Installation Brick InstallationGlass Frame Removal Placement of Lava ROCK, Rock Wool and Logs Final InstallationLog #3 Log #2 Placement of Log 7 HBDV400 only Installing Universal AndironsOperating Instructions Millivolt Leak TestingWhat to do if YOU Smell GAS Initial LightingApproved Leak Testing Method Main Burner Switch Lighting the BurnerPilot Position BURNER, Pilot and Control Compartment Cleaning and MaintenancePilot Flame BurnerGlass Door Vent SystemLogs Rock WoolStanding Pilot Ignition Symptom Possible Cause ActionTroubleshooting Fireplace Components Replacement PartsCC=Cottage Clay CR=Cottage Red Millivolt Engine Vent Components Millivolt ComponentsRefer to illustrations on previous Vent ComponentsLogs Special Requirements Special Requirements 54D5031 54D5031 54D5031 Lifetime Warranty Five Year WarrantyBasic Warranty