Monessen Hearth HBDV400, HBDV300 manual Venting Installation, Rear Through the Wall Applications

Page 18

VENTING INSTALLATION

REAR (THROUGH THE WALL) APPLICATIONS

When installed as a rear vent unit this appliance may be vented directly to a termination located on the rear wall behind the appliance

The maximum horizontal distance between the rear of the appliance and the outside of termination is 20" (508 m). See Figure 15.

Only one 45° elbow is allowed in these installations.

Maximum 20"

Top View Flat Installation

Figure 15 - Rear Vent Application,

Maximum Horizontal Distance

Sealant is not required to assemble HBDV/DVBH fireplace venting. Do not use silicone sealant at the flue exhaust connections.

1.Find the pipe section’s direction label. The label arrow shall be pointed away from the fire- box and toward the termination. Firmly insert the initial rigid section/elbow into the firebox outer collar. Simpson “GS” and Selkirk “DT” outer walls are hemmed and will snap into the collar’s tabs. Attach Simpson’s DirectVent Pro by fully inserting into the collar and securing with self tapping screws. The screws shall only penetrate the flue outer wall.

Refer to vent manufacturer’s installation instructions to properly assemble flue.

2.Locate and cut the vent opening in the wall. For combustible walls first frame in opening.

Combustible Interior Walls: Cut a 111/2"H x 91/2" W hole through the interior wall.

Combustible Exterior Walls: Cut a 91/2"H x 91/2"W square hole through the exterior wall frame. See Figure 17.

Noncombustible Walls: Hole opening should be 71/2" (190mm) in diameter.

3.The center of the hole should line up with the center line of the horizontal rigid vent pipe end. Pipe shall always run level or uphill on horizontal runs. Never run pipe down hill. See Figure 17.

Female

Locking Lugs

Note: Horizontal runs of vent must be supported every three feet (914mm). Use wall straps for this purpose.

Male Slots

Figure 16 - Rigid Vent Pipe Connections

91/2"

(241mm)

91/2"

(241mm)

33/4"

(92mm)

71/2"

(190mm)

Figure 17 - Exterior Wall Framing Dimensions

18

54D5031

Image 18
Contents Models What to do if YOU Smell GASContents Important Safety Information InstallerOwner Gas is commonly known as Never connect unit to privateNon-utility gas wells. This Wellhead gasCode Approval Product Features and Code ApprovalProduct Specifications Listed Vented GAS Fireplace HeaterOrifice SIZES, Pressures and BTUs PRE-INSTALLATION InformationHigh Elevations Before YOU StartFraming Dimensions Fireplace FramingFireplace Dimensions Fireplace DimensionsFireplace Location Locating Gas FireplaceClearances Clearances to CombustiblesMantel Clearances Insulation Board Securing Fireplace to Floor or FramingInstallation Information Installation PrecautionsFinishing Material Vent Installation Combustible Clearances for Vent PipeConfiguration the 4 100mm flue pipe Optional TOP Vent ApplicationAfter conversion to top vent Should be concentric within the 65/8For Horizontal Termination Installation PlanningInstalling a Vent System in AN Outside Chase For Vertical TerminationHorizontal Vent Termination Location Minimum DistancesHOW to USE the Vent Graph FeetVenting Installation Rear Through the Wall ApplicationsInto any wall. This will cause a Rear Wall Vent InstallationDo not recess vent termination fire hazardHorizontal Termination Configurations Maximum Three 3 90 Elbows Per InstallationHorizontal Termination Configuration Horizontal Run ReductionBelow Grade Installations Below Grade InstallationVertical THROUGH-THE-ROOF Applications Support Straps for Horizontal RunsInstallation for Vertical Termination Flat Ceiling InstallationMinimum chimney clearance Flex Vent Installation Start the flexible vent as followsTypical pipe connection Fireplace Installation Installing GAS Piping to Fireplace / Burner System LocationCheck GAS Type Gas Connection Checking GAS Pressure and Electrical Installation Do not use open flame to checkRemote Wall Switch Electrical InstallationRemote Wall Mounted Switch Optional DC Remote SystemsGlass Removal & Brick Installation Brick InstallationGlass Frame Removal Final Installation Placement of Lava ROCK, Rock Wool and LogsLog #3 Log #2 Installing Universal Andirons Placement of Log 7 HBDV400 onlyWhat to do if YOU Smell GAS Leak TestingOperating Instructions Millivolt Initial LightingApproved Leak Testing Method Main Burner Switch Lighting the BurnerPilot Position Pilot Flame Cleaning and MaintenanceBURNER, Pilot and Control Compartment BurnerLogs Vent SystemGlass Door Rock WoolSymptom Possible Cause Action Standing Pilot IgnitionTroubleshooting Replacement Parts Fireplace ComponentsCC=Cottage Clay CR=Cottage Red Millivolt Engine Millivolt Components Vent ComponentsVent Components Refer to illustrations on previousLogs Special Requirements Special Requirements 54D5031 54D5031 54D5031 Lifetime Warranty Five Year WarrantyBasic Warranty