FIREPLACE INSTALLATION

CHECK GAS TYPE

Use proper gas type for the fireplace you are installing. If you have conflicting gas type, do not install fireplace. See dealer where you purchased the fireplace for proper fireplace for your gas type or conversion kit.

INSTALLING GAS PIPING TO FIREPLACE / BURNER SYSTEM LOCATION

INSTALLATION ITEMS NEEDED

Before installing fireplace and burner system, make sure you have the items listed below.

External regulator (supplied by installer)

Piping (check local codes)

Sealant (resistant to propane/LP gas)

Equipment shutoff valve*

Test gauge connection*

Sediment trap (recommended)

Tee joint

Pipe wrench

 

 

approved flexible gas line with gas connector (if allowed by local codes — not provided)

*A CSA design-certified equipment shutoff valve with 1/8" NPT tap is an acceptable alternative to test gauge connection. Purchase the CSA design-certified equipment shutoff valve from your dealer.

For propane/LP connections only, the installer must supply an external regulator. The external regulator will reduce incoming gas pressure. You must reduce incoming gas pressure to between 11 and 13 inches of water. If you do not reduce incoming gas pressure, burner system regulator damage could occur. Install external regulator with the vent pointing down as shown in Figure 39. Pointing the vent down protects it from freezing rain or sleet.

WARNING

A qualified installer or service person must connect appliance to gas supply. Follow all local codes.

CAUTION

For propane/LP units, never connect fireplace directly to the propane/LP supply. This burner system requires an external regulator (not supplied). Install the external regulator between the burner system and propane/LP supply.

External

100 lb. (min)

Regulator

Propane/LP

 

Supply Tank

Vent

Pointing

Down

Figure 39 - External Regulator with Vent Pointing

Down (Propane/LP Only)

 

Use only new black iron or steel pipe.

 

Internally tinned copper or copper

CAUTION

tubing can be used per National Fuel

Code, section 2.6.3, providing gas

 

 

meets hydrogen sulfide limits, and

 

where permitted by local codes. Gas

 

piping system must be sized to provide

 

minimum inlet pressure (listed on

 

data plate) at the maximum flow rate

 

(BTU/hr). Undue pressure loss will

 

occur if the pipe is too small.

 

 

When using copper of flex connectors use only fittings approved for gas connections. The gas control inlet is 3/8" NPT.

28

54D5031

Image 28
Contents Models What to do if YOU Smell GASContents Installer Important Safety InformationOwner Never connect unit to private Non-utility gas wells. ThisGas is commonly known as Wellhead gasProduct Features and Code Approval Product SpecificationsCode Approval Listed Vented GAS Fireplace HeaterPRE-INSTALLATION Information High ElevationsOrifice SIZES, Pressures and BTUs Before YOU StartFraming Dimensions Fireplace FramingFireplace Dimensions Fireplace DimensionsFireplace Location Locating Gas FireplaceClearances to Combustibles ClearancesMantel Clearances Insulation Board Securing Fireplace to Floor or FramingInstallation Precautions Installation InformationFinishing Material Vent Installation Combustible Clearances for Vent PipeOptional TOP Vent Application After conversion to top ventConfiguration the 4 100mm flue pipe Should be concentric within the 65/8Installation Planning Installing a Vent System in AN Outside ChaseFor Horizontal Termination For Vertical TerminationHorizontal Vent Termination Location Minimum DistancesHOW to USE the Vent Graph FeetVenting Installation Rear Through the Wall ApplicationsRear Wall Vent Installation Do not recess vent terminationInto any wall. This will cause a fire hazardHorizontal Termination Configurations Maximum Three 3 90 Elbows Per InstallationHorizontal Termination Configuration Horizontal Run ReductionBelow Grade Installations Below Grade InstallationVertical THROUGH-THE-ROOF Applications Support Straps for Horizontal RunsInstallation for Vertical Termination Flat Ceiling InstallationMinimum chimney clearance Flex Vent Installation Start the flexible vent as followsTypical pipe connection Installing GAS Piping to Fireplace / Burner System Location Fireplace InstallationCheck GAS Type Gas Connection Checking GAS Pressure and Electrical Installation Do not use open flame to checkElectrical Installation Remote Wall Mounted SwitchRemote Wall Switch Optional DC Remote SystemsBrick Installation Glass Removal & Brick InstallationGlass Frame Removal Final Installation Placement of Lava ROCK, Rock Wool and LogsLog #3 Log #2 Installing Universal Andirons Placement of Log 7 HBDV400 onlyLeak Testing Operating Instructions MillivoltWhat to do if YOU Smell GAS Initial LightingApproved Leak Testing Method Lighting the Burner Main Burner SwitchPilot Position Cleaning and Maintenance BURNER, Pilot and Control CompartmentPilot Flame BurnerVent System Glass DoorLogs Rock WoolSymptom Possible Cause Action Standing Pilot IgnitionTroubleshooting Replacement Parts Fireplace ComponentsCC=Cottage Clay CR=Cottage Red Millivolt Engine Millivolt Components Vent ComponentsVent Components Refer to illustrations on previousLogs Special Requirements Special Requirements 54D5031 54D5031 54D5031 Five Year Warranty Lifetime WarrantyBasic Warranty