Monessen Hearth HBDV400, HBDV300 manual Special Requirements

Page 50

SPECIAL REQUIREMENTS CONTINUED

NOTES

 

 

 

 

 

2.APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.

3.SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, “GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS.”

4.INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4.

(b)EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:

1.The equipment listed in Chapter 10 entitled “Equipment Not Required To Be Vented” in the most current edition of NFPA 54 as adopted by the Board; and

2.Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes.

(c)MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED. When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:

1.Detailed instructions for the installation of the venting system design or the venting system components; and

2.A complete parts list for the venting system design or venting system.

(d)MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED. When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies “special venting systems,” the following requirements shall be satisfied by the manufacturer:

1.The identification of each “special venting system” shall include either the listing of the website, phone number or manufacturer's address where the venting system installation instructions can be obtained; and

2.The “special venting systems” shall be Product Approved by the Board, and the instructions provided with that system shall include a parts list and detailed installation instructions.

(e)A copy of all installation instructions for the Product Approved side wall horizontally vented gas fueled equipment and all the venting instructions, parts lists, and/or all design instructions for the venting system shall remain with the appli- ance or equipment at the completion of the installation.

50

54D5031

Image 50
Contents Models What to do if YOU Smell GASContents Owner Important Safety InformationInstaller Gas is commonly known as Never connect unit to privateNon-utility gas wells. This Wellhead gasCode Approval Product Features and Code ApprovalProduct Specifications Listed Vented GAS Fireplace HeaterOrifice SIZES, Pressures and BTUs PRE-INSTALLATION InformationHigh Elevations Before YOU StartFraming Dimensions Fireplace FramingFireplace Dimensions Fireplace DimensionsFireplace Location Locating Gas FireplaceMantel Clearances ClearancesClearances to Combustibles Insulation Board Securing Fireplace to Floor or FramingFinishing Material Installation InformationInstallation Precautions Vent Installation Combustible Clearances for Vent PipeConfiguration the 4 100mm flue pipe Optional TOP Vent ApplicationAfter conversion to top vent Should be concentric within the 65/8For Horizontal Termination Installation PlanningInstalling a Vent System in AN Outside Chase For Vertical TerminationHorizontal Vent Termination Location Minimum DistancesHOW to USE the Vent Graph FeetVenting Installation Rear Through the Wall ApplicationsInto any wall. This will cause a Rear Wall Vent InstallationDo not recess vent termination fire hazardHorizontal Termination Configurations Maximum Three 3 90 Elbows Per InstallationHorizontal Termination Configuration Horizontal Run ReductionBelow Grade Installations Below Grade InstallationVertical THROUGH-THE-ROOF Applications Support Straps for Horizontal RunsInstallation for Vertical Termination Flat Ceiling InstallationMinimum chimney clearance Flex Vent Installation Start the flexible vent as followsTypical pipe connection Check GAS Type Fireplace InstallationInstalling GAS Piping to Fireplace / Burner System Location Gas Connection Checking GAS Pressure and Electrical Installation Do not use open flame to checkRemote Wall Switch Electrical InstallationRemote Wall Mounted Switch Optional DC Remote SystemsGlass Frame Removal Glass Removal & Brick InstallationBrick Installation Final Installation Placement of Lava ROCK, Rock Wool and LogsLog #3 Log #2 Installing Universal Andirons Placement of Log 7 HBDV400 onlyWhat to do if YOU Smell GAS Leak TestingOperating Instructions Millivolt Initial LightingApproved Leak Testing Method Pilot Position Main Burner SwitchLighting the Burner Pilot Flame Cleaning and MaintenanceBURNER, Pilot and Control Compartment BurnerLogs Vent SystemGlass Door Rock WoolSymptom Possible Cause Action Standing Pilot IgnitionTroubleshooting Replacement Parts Fireplace ComponentsCC=Cottage Clay CR=Cottage Red Millivolt Engine Millivolt Components Vent ComponentsVent Components Refer to illustrations on previousLogs Special Requirements Special Requirements 54D5031 54D5031 54D5031 Basic Warranty Lifetime WarrantyFive Year Warranty