VENT INSTALLATION

VERTICAL (THROUGH-THE-ROOF) APPLICATIONS

This Gas Fireplace has been approved for,

Vertical installations up to 40' (12m) in height. Up to a 10' (3m) horizontal vent run can be installed within the vent system using a maximum of two 90° elbows. See Figure 28.

NOTE: Horizontal sections of this vent system require a minimum of 3" clearances to combustibles at the top of the flue and 1" clearance at the sides and bottom until the flue penetrates the outside wall. A minimum 1" clearance all around the flue is acceptable at this point of penetration.

Vertical sections of this vent system require a minimum of

 

 

 

 

 

 

10'

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1" clearance to combustibles on all sides of the pipe.

40' Maximum Height

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Maximum

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Support

8' Minimum Height

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Support Straps

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10'

 

 

 

 

 

 

 

 

Straps

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Every 3'

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Every

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Maximum

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5'Vertical

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40' Maximum Height

 

 

 

Support Straps

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8' Minimum Height

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Every 3'

 

 

 

Figure 28 - Support Straps for Horizontal Runs

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Up to two 45° elbows may be used within the horizontal run. For each 45° elbow used on the horizontal plane, the maximum horizontal length must be reduced by 18" (450mm).

Example: Maximum horizontal length No elbows = 10’ (3m)

1x45° elbows = 8.5’ (2.6m) 2x45° elbows = 7’ (2.1m)

A minimum of an 8' (2.5m) vertical rise is required.

Two sets of 45°elbows offsets may be used within the vertical sections. From 0 to a maximum of 8' (2.5 m) of vent pipe can be used between elbows. See Figure 29.

The maximum angular variation allowed in the system is 270°. See Figure 29.

1

2

3

4

1

2

Example:

Elbow 1

=

90°

 

 

 

 

 

Elbow 2

=

45°

 

 

3

 

 

Elbow 3

=

45°

 

 

4

 

 

Elbow 4

=

90°

 

 

 

Total Angular Variation

=

270°

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Figure 29 - Maximum Elbow Usage

54D5031

23

Image 23
Contents What to do if YOU Smell GAS ModelsContents Owner Important Safety InformationInstaller Wellhead gas Never connect unit to privateNon-utility gas wells. This Gas is commonly known asListed Vented GAS Fireplace Heater Product Features and Code ApprovalProduct Specifications Code ApprovalBefore YOU Start PRE-INSTALLATION InformationHigh Elevations Orifice SIZES, Pressures and BTUsFireplace Framing Framing DimensionsFireplace Dimensions Fireplace DimensionsLocating Gas Fireplace Fireplace LocationMantel Clearances ClearancesClearances to Combustibles Securing Fireplace to Floor or Framing Insulation BoardFinishing Material Installation InformationInstallation Precautions Combustible Clearances for Vent Pipe Vent InstallationShould be concentric within the 65/8 Optional TOP Vent ApplicationAfter conversion to top vent Configuration the 4 100mm flue pipeFor Vertical Termination Installation PlanningInstalling a Vent System in AN Outside Chase For Horizontal TerminationMinimum Distances Horizontal Vent Termination LocationFeet HOW to USE the Vent GraphRear Through the Wall Applications Venting Installationfire hazard Rear Wall Vent InstallationDo not recess vent termination Into any wall. This will cause aMaximum Three 3 90 Elbows Per Installation Horizontal Termination ConfigurationsHorizontal Run Reduction Horizontal Termination ConfigurationBelow Grade Installation Below Grade InstallationsSupport Straps for Horizontal Runs Vertical THROUGH-THE-ROOF ApplicationsFlat Ceiling Installation Installation for Vertical TerminationMinimum chimney clearance Start the flexible vent as follows Flex Vent InstallationTypical pipe connection Check GAS Type Fireplace InstallationInstalling GAS Piping to Fireplace / Burner System Location Gas Connection Do not use open flame to check Checking GAS Pressure and Electrical InstallationOptional DC Remote Systems Electrical InstallationRemote Wall Mounted Switch Remote Wall SwitchGlass Frame Removal Glass Removal & Brick InstallationBrick Installation Placement of Lava ROCK, Rock Wool and Logs Final InstallationLog #3 Log #2 Placement of Log 7 HBDV400 only Installing Universal AndironsInitial Lighting Leak TestingOperating Instructions Millivolt What to do if YOU Smell GASApproved Leak Testing Method Pilot Position Main Burner SwitchLighting the Burner Burner Cleaning and MaintenanceBURNER, Pilot and Control Compartment Pilot FlameRock Wool Vent SystemGlass Door LogsStanding Pilot Ignition Symptom Possible Cause ActionTroubleshooting Fireplace Components Replacement PartsCC=Cottage Clay CR=Cottage Red Millivolt Engine Vent Components Millivolt ComponentsRefer to illustrations on previous Vent ComponentsLogs Special Requirements Special Requirements 54D5031 54D5031 54D5031 Basic Warranty Lifetime WarrantyFive Year Warranty