Monessen Hearth HBDV400, HBDV300 manual Flex Vent Installation, Start the flexible vent as follows

Page 26
Figure 1 —
Typical appliance connection
and adapter outer
1¾ in. flexible pipe
collar overlap

FLEX VENT INSTALLATION

1.Flexible UL1777 listed venting may be used in any venting application where rigid direct vent components can be used.

All restrictions, clearances and allowances that pertain to the rigid piping apply to the flexible venting. Flex kits may not be modified. Flex kits may be added to the end of a vent run made of rigid vent sections using pipe manufacturer’s approved flex to pipe adapters. This may occur only if doing so does not violate any of the venting length, height, routing, horizontal to vertical ratio requirements or clearance considerations detailed in this manual.

2.The flex adapter starter kit (DVFA/8) is used to attach flex venting to the appliance starting collar. It includes 4" inner and 7" outer adapter rings (refer to Figure 1).

The inner and outer adaptor rings are required to start all flex runs.

Never install damaged or torn flexible venting.

Over tightening clamps may rip, tear, or otherwise damage flexible venting.

The adaptor kit does not include individual pipe sections which may be purchased separately. (UL1777 listed type flex venting only.)

DVFA/8 inner adapter outer adapter

Appliance starting

collar

UL1777

Flex vent

Securing screws

(3 places

equidistant just

above gear

clamp)

Gear clamps

3. Start the flexible vent as follows—

A. Installing the inner flex adaptor and pipe (see Figure 1). 1. Insert the long side of the 4" inner ring inte exhaust

pipe, gently tap to seat into place, and secure with screws.

2.Slide the small gear clamp over the inner flexible vent pipe, and push out of the way.

3.Pull and extend the inner flexible vent.

4.Slide the inner vent onto the adapter collar, for a minimum 1¾" overlap.

5.Locate the clamp at approximately ¾" from the flex end and tighten.

6.Secure the clamped inner section with three self tapping screws, drilled equidistance, just above the clamp perimeter.

B.Installing the outer flex pipe (refer to Figure 1).

1.Firmly insert the outer adapter ring into the outer appliance starting collar and secure with screws.

2.Slide the large gear clamp over the outer flexible vent pipe, and push out of the way.

3.Pull and extend the outer flexible vent.

4.Slide the outer vent onto the appliance collar outer adapter for a minimum 1¾" overlap.

5.Locate the clamp at approximately ¾" from the flex end and tighten.

6.Secure the clamped outer section with three self tapping screws, drilled equidistant, just above the clamp perimeter.

C.Routing UL1777 flex pipe.

1.Always maintain the required clearance when routing the flex vent assembly.

2. Install firestop spacers (see Figure 3) when penetrating ceilings,

attic spaces, or walls.

UL1777

5" radius

 

NOTE

Flex vent pipe spacers: Refer to manufacturer’s

specifications for correct positioning of the spacer springs to maintain proper distance between inside and outside pipe.

Flex vent

Figure 2 —

Minimum radius for flex vent section

26

54D5031

Image 26
Contents Models What to do if YOU Smell GASContents Owner Important Safety InformationInstaller Gas is commonly known as Never connect unit to privateNon-utility gas wells. This Wellhead gasCode Approval Product Features and Code ApprovalProduct Specifications Listed Vented GAS Fireplace HeaterOrifice SIZES, Pressures and BTUs PRE-INSTALLATION InformationHigh Elevations Before YOU StartFraming Dimensions Fireplace FramingFireplace Dimensions Fireplace DimensionsFireplace Location Locating Gas FireplaceMantel Clearances ClearancesClearances to Combustibles Insulation Board Securing Fireplace to Floor or FramingFinishing Material Installation InformationInstallation Precautions Vent Installation Combustible Clearances for Vent PipeConfiguration the 4 100mm flue pipe Optional TOP Vent ApplicationAfter conversion to top vent Should be concentric within the 65/8For Horizontal Termination Installation PlanningInstalling a Vent System in AN Outside Chase For Vertical TerminationHorizontal Vent Termination Location Minimum DistancesHOW to USE the Vent Graph FeetVenting Installation Rear Through the Wall ApplicationsInto any wall. This will cause a Rear Wall Vent InstallationDo not recess vent termination fire hazardHorizontal Termination Configurations Maximum Three 3 90 Elbows Per InstallationHorizontal Termination Configuration Horizontal Run ReductionBelow Grade Installations Below Grade InstallationVertical THROUGH-THE-ROOF Applications Support Straps for Horizontal RunsInstallation for Vertical Termination Flat Ceiling InstallationMinimum chimney clearance Flex Vent Installation Start the flexible vent as followsTypical pipe connection Check GAS Type Fireplace InstallationInstalling GAS Piping to Fireplace / Burner System Location Gas Connection Checking GAS Pressure and Electrical Installation Do not use open flame to checkRemote Wall Switch Electrical InstallationRemote Wall Mounted Switch Optional DC Remote SystemsGlass Frame Removal Glass Removal & Brick InstallationBrick Installation Final Installation Placement of Lava ROCK, Rock Wool and LogsLog #3 Log #2 Installing Universal Andirons Placement of Log 7 HBDV400 onlyWhat to do if YOU Smell GAS Leak TestingOperating Instructions Millivolt Initial LightingApproved Leak Testing Method Pilot Position Main Burner SwitchLighting the Burner Pilot Flame Cleaning and MaintenanceBURNER, Pilot and Control Compartment BurnerLogs Vent SystemGlass Door Rock WoolSymptom Possible Cause Action Standing Pilot IgnitionTroubleshooting Replacement Parts Fireplace ComponentsCC=Cottage Clay CR=Cottage Red Millivolt Engine Millivolt Components Vent ComponentsVent Components Refer to illustrations on previousLogs Special Requirements Special Requirements 54D5031 54D5031 54D5031 Basic Warranty Lifetime WarrantyFive Year Warranty