Monessen Hearth CDV7 manual Termination Clearances, USA Installations, Canadian Installations

Page 15
Figure 9 -
Termination Clearances

Venting INSTALLATION INFORMATION

CDVSC7 & CDV7 Series Gas Fireplace

Termination Clearances

Termination clearances for buildings with combustible and noncombustible exteriors.

Inside Corner

 

 

 

 

 

G =

G

 

 

 

Combustible

 

 

 

 

 

6" (152 mm)

 

 

 

 

 

 

V Noncombustible 2" (51 mm)

Outside Corner

 

F =

 

 

Combustible

 

6"

(152 mm)

V

Noncombustible

2"

(51 mm)

 

 

F

 

Alcove Applications*

D

C C

V

E

O

Balcony -

with no side wall

M

V

M =

Combustible &

Noncombustible

12" (305 mm)

Balcony -

with perpendicular side wall

M

V

P

Combustible &

Noncombustible

M = 24" (610 mm)

P = 20” (508 mm)

E = Min. 6” (152 mm) for non-vinyl sidewalls Min. 12” (305 mm) for vinyl sidewalls

O = 8’ (2.4 m) Min.

No.

 

 

 

of Caps

DMin.

CMax.

 

 

 

 

 

1

3’ (914 mm)

2 x DActual

 

2

6’ (1.8 m)

1 x DActual

 

 

 

 

 

3

9’ (2.7 m)

2/3 x DActual

 

 

 

 

 

4

12’ (3.7 m)

1/2 x DActual

 

DMin. = # of Termination caps x 3

 

CMax. = (2 / # termination caps) x DActual

584-15

 

 

 

*NOTE: Termination in an alcove space (spaces open only on one side and with an overhang) is permitted with the dimensions specified for vinyl or non-vinyl siding and soffits. 1. There must be a 3’ (914 mm) minimum between termination caps. 2. All mechanical air intakes within 10’ (1 m) of a termination cap must be a minimum of 3’ (914 mm) below the termination cap. 3. All gravity air intakes within 3’ (914 mm) of a termination cap must be a minimum of 1’ (305 mm) below the termination cap.

General Information Assembling Vent Pipes

USA Installations

The venting system must conform to local codes and/or the current National Fuel Code ANSI Z223.1/NFPA 54.

Only venting components manufactured by MHSC may be used in Direct Vent systems.

Canadian Installations

The venting system must be installed in accordance with the current CSA-B149.1 installation code.

Flex Vent Pipes

Before joining the flex vent pipe to the unit, apply a bead of high temperature sealant* (provided) to the 4” pipe exiting the fireplace. Secure flex vent pipe in place with a hose clamp (provided).

*Be sure the flex pipe overlaps at least 1” (25 mm) onto the collars of the fireplace and termination. If the termi- nation has an internal bead, be sure to overlap and se- cure 1” (25 mm) past the bead.

*Be sure the vent is actually crushed before proceeding. Apply a tug to be sure the vent will not slip off the collars. Repeat process with 7” flex vent pipe. The same proce- dure must be performed on the vent side.

Apply High Temperature

Sealant

FP2290

Hose Clamp

Figure 10 -

Apply high temperature sealant to 4” and 7” pipes.

69D3011

15

Image 15
Contents Consumer Retain this manual for future refer- ence CdvtCdvr Do not try to light any applianceOperating Instructions Electronic Ignition Pre-Installation InformationElectrical Wiring Check Gas Pressure Signature Command System36Important Safety Information InstallerOwner As wellhead gas Code ApprovalNever connect unit to private non-utility Gas wells. This gas is commonly knownProduct Specifications Product featuresGAS pressures GAS Specifications & Orifice Size Cdvr SeriesGAS Specifications & Orifice Size Cdvt Series High ElevationsFireplace dimensions & Framing Framing DimensionsCDVR33V,E7 CDVT36 V,E,SC7 CDVT42 V,E,SC7 CDVT47 V,E,SC7 CDVT33V,E,SC7Cold Climate Insulation Fireplace Location Clearances Clearances to combustiblesMantel clearances Finishing Material Venting Installation Information Installation precautionsGeneral Venting General Venting Information Termination Location Canadian Installations1 US Installations2USA Installations Canadian InstallationsTermination Clearances Twist Lock Pipes Rear Vent Installation onlyRefer to Page 24 for snorkel requirements How to Use the Vent GraphVent Pipe Clearances Venting installationRear Wall Vent Installation Twist Lock Pipe Rear Wall Vent ApplicationStep Venting System Rear Wall Vent Installations Flex Vent PipeTop vent Sidewall Application Since it is very im Portant ThatMaximum number of 90 elbows per side wall Always install horizontal venting on a level plane Vertical Sidewall Installation Twist Lock PipeVertical Sidewall installation flex vent pipe Below Grade Installation Vertical THROUGH-THE-ROOF APPLICA- TionDo not back fill around snorkel Vertical THROUGH-THE-ROOF Installation Minimum Chimney Clearance Fireplace installation Install gas piping to fireplace / burner system locationCheck gas type Natural Gas Electrical Wiring Do not use open flame to check for gasLeaks Remote Wall Switch Electrical installationRemote Wall mounted Switch Do not connect wall switch to 110Do not connect 110-120 VAC to Electronic Pilot Ignition WiringRemote Wall Switch. The appliance will Optional Fan/Blower SystemsNever use an open flame to check for gas leak Leak testingMillivolt Operating Instructions Initial lightingNever check for gas leak with open flame Approved leak testing methodMain burner switch Lighting the burnerPilot position Injury or loss of life Causing property damage, personalIf you do not follow these instruction Exactly, a fire or explosion may resultOr performing service. All wiring shall be Optional Accessory RequirementsElectrician. Main power must be off when Connecting to main electrical power supplyWall Switch Installation Electrical InstallationJunction BOX Wiring Command Center Wall InstallationElectrical Installation Optional FAN Blower Systems Blotsc Signature Command BlowerFK-12 Manual Blower Blot Automatic Thermostat BlowerOn next OPERATing Instructions Command CenterFeatures Battery InstallationCommand Center System CONFIGURATION/SETUP Key Combinations for System SettingsFunction Operation Default Setting Function Operation Command Center OperationsSelf Diagnostics Chart FUNCTIONS/OPERATIONGlass Frame Removal Rock wool placementLava rock and ember placement Log placementBurner, Pilot and Control Compart- ment Cleaning and maintenanceRock wool Vent SystemGlass Door LogsTroubleshooting Standing Pilot IgnitionPoSSIBLE Cause CDVSC7 & CDV7 Series Gas Fireplace YeS Electronic IgnitionOperationfault Diagnosis Action Signature Command SystemFirebox components Replacement partsCDVR33 CDVT33 CDVR36 CDVT36 CDVR42 CDVT42 CDVR47 CDVT47 Standing Pilot Millivolt control LP to Natural Gas Replacement PartsAccessories Description Qty Part Number Fuel Conversion Kits Millivolt Natural Gas to LPElectronic Ignition CDVSC7 & CDV7 Series Gas Fireplace13,14,15,16,17 CDVR33NSC7 CDVR33SC7 Description Model Number Vertical Venting7TBRHTK Horizontal VentingCDVSC7 & CDV7 Series Gas Fireplace CDVSC7 & CDV7 Series Gas Fireplace Carbon Monoxide Detector Requirements If Warranty Service is Needed Lifetime WarrantyFive Year Warranty Basic WarrantyModel EnerGuide Ratings Fireplace Efficiency % Mhsc