Monessen Hearth CDV7 Rear Wall Vent Installations Flex Vent Pipe, Top vent Sidewall Application

Page 20

CDVSC7 & CDV7 Series Gas Fireplace

Venting installation

Finish Wall

 

Vent

 

Termination

Figure 17 -

FP2294

Side View of Final Unit Location

 

Rear Wall Vent Installations - Flex Vent Pipe

Follow Steps 1 and 2 on Page 19.

Step 3

Install the 4” (102 mm) flex vent pipe to the appliance col- lars described in “General Information Assembling Vent Pipes”, Page 12. If the installation requires a 45° angle, grasp the vent pipe close to the appliance collar and bend to 45°. DO NOT exceed 45°. Figure 18

Install the 7” vent pipe in the same manner as Step 2. NOTE: There must be a 1/2” (13 mm) rise in a 12” (305

mm)length of flex vent.

Step 4

Assemble the flex vent to the collars on the termination as you did on the appliance.

Termination

Flex Section

Appliance Collars

FP1473

Figure 18 -

Grasp the vent pipe close to the collar and bend to 45° angle. do not exceed 45°.

20

Rise

FP1472

Figure 19 -

There must be a 1/2" rise per foot length

Top vent Sidewall Application

NOTE: For all top vent installations where a 90° elbow is the first pipe piece towards a sidewall termination (up and out), an open-center ringed flue restrictor must be installed onto the top edge of the firebox flue adapter. To create this open-center re-

strictor, twist and break off the center rib of the supplied flue restrictor. The installed part should appear similar to that show n in Figure 20.

Since it is very im-

portant

that

the

FP2303

Figure 20 -

venting

system

Top Vent Vertical Sidewall

maintain its balance

Restrictor

between

the

com-

 

bustion air intake and the flue gas exhaust, certain limitations as to vent configurations apply and must be strictly adhered to.

The Vent Graph, showing the relationship between verti- cal and horizontal side wall venting, will help to determine the various dimensions allowable.

Minimum clearance between vent pipes and combus- tible materials is 3" (76 mm) on top, and 1" (25 mm) on the bottom and sides unless otherwise noted.

When vent termination exits through foundations less than 20” (508 mm) below siding outcrop, the vent pipe must flush up with the siding.

It is best to locate the fireplace in such a way that mini- mizes the number of offsets and horizontal vent length.

The horizontal vent run refers to the total length of vent pipe from the flue collar of the fireplace (or the top of the Transition Elbow) to the face of the outer wall.

Horizontal plane means no vertical rise exists on this por- tion of the vent assembly.

When installing the appliance as a rear vent unit, the 90° or 45° Transition Elbow attached directly to the rear of the unit is NOT INCLUDED in the following cri- teria and calculations, and unless specifically men- tioned should be ignored when calculating venting

layouts.

69D3011

Image 20
Contents Cdvt CdvrDo not try to light any appliance Consumer Retain this manual for future refer- encePre-Installation Information Electrical WiringCheck Gas Pressure Signature Command System36 Operating Instructions Electronic IgnitionOwner Important Safety InformationInstaller Code Approval Never connect unit to private non-utilityGas wells. This gas is commonly known As wellhead gasProduct features Product SpecificationsGAS Specifications & Orifice Size Cdvr Series GAS Specifications & Orifice Size Cdvt SeriesHigh Elevations GAS pressuresCDVR33V,E7 Fireplace dimensions & FramingFraming Dimensions CDVT33V,E,SC7 CDVT36 V,E,SC7 CDVT42 V,E,SC7 CDVT47 V,E,SC7Cold Climate Insulation Fireplace Location Mantel clearances ClearancesClearances to combustibles Finishing Material General Venting Venting Installation InformationInstallation precautions Canadian Installations1 US Installations2 General Venting Information Termination LocationTermination Clearances USA InstallationsCanadian Installations Rear Vent Installation only Twist Lock PipesHow to Use the Vent Graph Refer to Page 24 for snorkel requirementsVenting installation Vent Pipe ClearancesStep Rear Wall Vent Installation Twist Lock PipeRear Wall Vent Application Rear Wall Vent Installations Flex Vent Pipe Top vent Sidewall ApplicationSince it is very im Portant That Venting SystemMaximum number of 90 elbows per side wall Vertical Sidewall Installation Twist Lock Pipe Always install horizontal venting on a level planeVertical Sidewall installation flex vent pipe Do not back fill around snorkel Below Grade InstallationVertical THROUGH-THE-ROOF APPLICA- Tion Vertical THROUGH-THE-ROOF Installation Minimum Chimney Clearance Check gas type Fireplace installationInstall gas piping to fireplace / burner system location Natural Gas Leaks Electrical WiringDo not use open flame to check for gas Electrical installation Remote Wall mounted SwitchDo not connect wall switch to 110 Remote Wall SwitchElectronic Pilot Ignition Wiring Remote Wall Switch. The appliance willOptional Fan/Blower Systems Do not connect 110-120 VAC toLeak testing Millivolt Operating InstructionsInitial lighting Never use an open flame to check for gas leakApproved leak testing method Never check for gas leak with open flamePilot position Main burner switchLighting the burner Causing property damage, personal If you do not follow these instructionExactly, a fire or explosion may result Injury or loss of lifeOptional Accessory Requirements Electrician. Main power must be off whenConnecting to main electrical power supply Or performing service. All wiring shall beElectrical Installation Junction BOX WiringCommand Center Wall Installation Wall Switch InstallationElectrical Installation Blotsc Signature Command Blower Optional FAN Blower SystemsBlot Automatic Thermostat Blower FK-12 Manual BlowerOn next Command Center OPERATing InstructionsCommand Center FeaturesBattery Installation Function Operation Default Setting System CONFIGURATION/SETUPKey Combinations for System Settings Command Center Operations Self Diagnostics ChartFUNCTIONS/OPERATION Function OperationRock wool placement Glass Frame RemovalLog placement Lava rock and ember placementCleaning and maintenance Burner, Pilot and Control Compart- mentVent System Glass DoorLogs Rock woolPoSSIBLE Cause TroubleshootingStanding Pilot Ignition CDVSC7 & CDV7 Series Gas Fireplace Electronic Ignition YeSSignature Command System Operationfault Diagnosis ActionReplacement parts Firebox componentsCDVR33 CDVT33 CDVR36 CDVT36 CDVR42 CDVT42 CDVR47 CDVT47 Standing Pilot Millivolt control Replacement Parts Accessories Description Qty Part NumberFuel Conversion Kits Millivolt Natural Gas to LP LP to Natural GasCDVSC7 & CDV7 Series Gas Fireplace Electronic Ignition13,14,15,16,17 CDVR33NSC7 CDVR33SC7 Vertical Venting Description Model NumberHorizontal Venting 7TBRHTKCDVSC7 & CDV7 Series Gas Fireplace CDVSC7 & CDV7 Series Gas Fireplace Carbon Monoxide Detector Requirements Lifetime Warranty Five Year WarrantyBasic Warranty If Warranty Service is NeededMhsc Model EnerGuide Ratings Fireplace Efficiency %