Monessen Hearth CDV7 manual Vertical Sidewall installation flex vent pipe

Page 23

Venting installation

CDVSC7 & CDV7 Series Gas Fireplace

Step 6

Use appropriate length of pipe sections - telescopic or fixed - and install. The sections which go through the wall are packaged with the starter kit, and can be cut to suit if necessary.

Sealing vent pipe and firestop gaps with high tem- perature sealant will restrict cold air being drawn in around fireplace.

Step 7

Guide the vent terminations 4” and 7” collard into their respective vent pipes. Double check that the vent pipes overlap the collars by 2” (51 mm). Secure the termina- tion to the wall with screws provided and caulk around the wall plate to weatherproof. As an alternative to screw- ing the termination directly to the wall, you may also use expanding plugs or an approved exterior construction ad- hesive. You may also attach the termination with screws through the inner body into the 4” vent pipe, however for this method, you must extend the 4” pipe approximately 6” (152 mm) beyond the outer face of the wall.

Support horizontal pipes every 36” (914 mm) with metal pipe straps.

Vertical Sidewall installation - flex vent pipe

NOTE: The 40” (1016 mm) flex vent is used for 90° off the top of the unit then out the back wall.

Follow Step 1 and 2 on Page 22.

Step 3

Install the four (4) spacer springs on the 4” flex vent pipe. When installing the spacer springs around the 4” pipe, stretch the spring to approximately 15” (381 mm), wrap the spring around the pipe and interlock the ends of the spacer spring approximately 2” (51 mm). Measure 6C\v” (172 mm) from the end of the pipe. Place the next spring 5” (127 mm) from the previously installed spring. Place the next spring 6” (152 mm) from the last spring. Finally place the last spring 12” (305 mm) from the last spring installed. Figure 29

Step 4

Install the 4” (102 mm) flex vent pipe to the appliance col- lar as described on Page 14. Secure the end with the first spring 6C\v” (172 mm) from the flex pipe end to the unit.

Step 5

Slide the 7” (178 mm) flex vent pipe over the 4” flex vent pipe and secure the 7” collar as described on Page 14.

4” Flex Vent Pipe

 

12"

 

(305mm)

Spacer Spring

 

 

6"

 

(152mm)

 

5"

 

(127mm)

 

6C\v"

 

(172mm)

Figure 29 -

FP1474

 

Install Spacer Springs

 

Step 6

Bend the flex pipe horizontal so the bottom of the horizon- tal pipe measure 6Z\x” (165 mm) from the top of the unit immediately after the 90° formation. Figure 30. Be sure to follow the 1/2” (13 mm) rise in a 12” (305 mm) horizontal run rule.

Step 7

Install the 4” flex then 7” flex to the termination.

6Z\x" (165mm)

FP1475

Figure 30 -

Bend flex vent at 90° so horizontal portion is 6Z\x” (165 mm) off top of unit

69D3011

23

Image 23
Contents Consumer Retain this manual for future refer- ence CdvtCdvr Do not try to light any applianceOperating Instructions Electronic Ignition Pre-Installation InformationElectrical Wiring Check Gas Pressure Signature Command System36Owner Important Safety InformationInstaller As wellhead gas Code ApprovalNever connect unit to private non-utility Gas wells. This gas is commonly knownProduct Specifications Product featuresGAS pressures GAS Specifications & Orifice Size Cdvr SeriesGAS Specifications & Orifice Size Cdvt Series High ElevationsCDVR33V,E7 Fireplace dimensions & FramingFraming Dimensions CDVT36 V,E,SC7 CDVT42 V,E,SC7 CDVT47 V,E,SC7 CDVT33V,E,SC7Cold Climate Insulation Fireplace Location Mantel clearances ClearancesClearances to combustibles Finishing Material General Venting Venting Installation InformationInstallation precautions General Venting Information Termination Location Canadian Installations1 US Installations2Termination Clearances USA InstallationsCanadian Installations Twist Lock Pipes Rear Vent Installation onlyRefer to Page 24 for snorkel requirements How to Use the Vent GraphVent Pipe Clearances Venting installationStep Rear Wall Vent Installation Twist Lock PipeRear Wall Vent Application Venting System Rear Wall Vent Installations Flex Vent Pipe Top vent Sidewall Application Since it is very im Portant ThatMaximum number of 90 elbows per side wall Always install horizontal venting on a level plane Vertical Sidewall Installation Twist Lock PipeVertical Sidewall installation flex vent pipe Do not back fill around snorkel Below Grade InstallationVertical THROUGH-THE-ROOF APPLICA- Tion Vertical THROUGH-THE-ROOF Installation Minimum Chimney Clearance Check gas type Fireplace installationInstall gas piping to fireplace / burner system location Natural Gas Leaks Electrical WiringDo not use open flame to check for gas Remote Wall Switch Electrical installationRemote Wall mounted Switch Do not connect wall switch to 110Do not connect 110-120 VAC to Electronic Pilot Ignition WiringRemote Wall Switch. The appliance will Optional Fan/Blower SystemsNever use an open flame to check for gas leak Leak testingMillivolt Operating Instructions Initial lightingNever check for gas leak with open flame Approved leak testing methodPilot position Main burner switchLighting the burner Injury or loss of life Causing property damage, personalIf you do not follow these instruction Exactly, a fire or explosion may resultOr performing service. All wiring shall be Optional Accessory RequirementsElectrician. Main power must be off when Connecting to main electrical power supplyWall Switch Installation Electrical InstallationJunction BOX Wiring Command Center Wall InstallationElectrical Installation Optional FAN Blower Systems Blotsc Signature Command BlowerFK-12 Manual Blower Blot Automatic Thermostat BlowerOn next OPERATing Instructions Command CenterCommand Center FeaturesBattery Installation Function Operation Default Setting System CONFIGURATION/SETUPKey Combinations for System Settings Function Operation Command Center OperationsSelf Diagnostics Chart FUNCTIONS/OPERATIONGlass Frame Removal Rock wool placementLava rock and ember placement Log placementBurner, Pilot and Control Compart- ment Cleaning and maintenanceRock wool Vent SystemGlass Door LogsPoSSIBLE Cause TroubleshootingStanding Pilot Ignition CDVSC7 & CDV7 Series Gas Fireplace YeS Electronic IgnitionOperationfault Diagnosis Action Signature Command SystemFirebox components Replacement partsCDVR33 CDVT33 CDVR36 CDVT36 CDVR42 CDVT42 CDVR47 CDVT47 Standing Pilot Millivolt control LP to Natural Gas Replacement PartsAccessories Description Qty Part Number Fuel Conversion Kits Millivolt Natural Gas to LPElectronic Ignition CDVSC7 & CDV7 Series Gas Fireplace13,14,15,16,17 CDVR33NSC7 CDVR33SC7 Description Model Number Vertical Venting7TBRHTK Horizontal VentingCDVSC7 & CDV7 Series Gas Fireplace CDVSC7 & CDV7 Series Gas Fireplace Carbon Monoxide Detector Requirements If Warranty Service is Needed Lifetime WarrantyFive Year Warranty Basic WarrantyModel EnerGuide Ratings Fireplace Efficiency % Mhsc