CDVSC7 & CDV7 Series Gas Fireplace

troubleshooting

electronic Ignition

START

1.Turn gas supply off.

2.Turn ON/OFF switch to “ON” Power to module (24V Normal)

YES

Is there a spark across ignitor sensor gap?

YES

Turn on gas.

Does pilot burner light?

YES

Does spark stop when pilot is lit?

YES

Does main burner light?

YES

Does system run until ON/OFF switch is in “OFF” position?

YES

END OF TROUBLESHOOTING

 

 

 

Check: Line voltage (120VAC)

 

 

 

NO

Low voltage transformer (19.5 minimum VAC)

ON/OFF switch

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Wiring connections

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Unplug ignition lead and

 

 

 

 

NO

check spark at module

 

 

 

 

(24VAC normal).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Is spark OK?

 

NO

 

Replace module

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

yeS

 

 

 

 

 

 

 

 

 

 

 

 

 

A.Check ignition cable ground wiring, ceramic insulator and gap. Correct if necessary.

B.Does ignition cable show signs of melting or buckling? Take protective action to shield cable and boot from excessive temperatures.

 

A. Are all manual gas valves open?

NO

Are supply tubing and pressure good?

Are pilot burner orifies blocked?

 

B.Check electrical connections between module and pilot operator on gas control.

C.Check for 24VAC across PV-MVPV terminals. If voltage is correct, replace gas control.

If voltage is not correct, replace module.

 

 

NOTE: If module goes into lockout, reset system.

NO

A. Check continuity of ignition cable and ground wire.

B. Clean flame rod.

 

 

 

 

C. Check electrical connections between flame rod and

 

 

module.

 

 

D. Is ceramic flame rod insulator cracked?

 

 

E. Is pilot flame a steady blue? Does flame cover flame rod?

 

 

If not, adjust pilot flame. Replace module if problem

 

 

persists.

 

 

 

A.Check for 24VAC across MV-MVPV terminal. Replace module if there is no voltage.

NO

B. Are electrical connections between module and gas

control good?

 

 

If connections are good, replace gas control or gas

 

control operator.

 

NOTE: If module goes into lockout, reset system.

 

 

A. Check continuity of ignition cable and ground wire.

NO

NOTE: If ground is poor or erratic, shutdown may

occasionally occur even though operation is normal

 

 

at time of checkout.

 

B.Is pilot flame a steady blue? Does flame cover flame rod? If above checks out, replace module.

52

69D3011

Image 52
Contents Cdvt CdvrDo not try to light any appliance Consumer Retain this manual for future refer- encePre-Installation Information Electrical WiringCheck Gas Pressure Signature Command System36 Operating Instructions Electronic IgnitionInstaller Important Safety InformationOwner Code Approval Never connect unit to private non-utilityGas wells. This gas is commonly known As wellhead gasProduct features Product SpecificationsGAS Specifications & Orifice Size Cdvr Series GAS Specifications & Orifice Size Cdvt SeriesHigh Elevations GAS pressuresFraming Dimensions Fireplace dimensions & FramingCDVR33V,E7 CDVT33V,E,SC7 CDVT36 V,E,SC7 CDVT42 V,E,SC7 CDVT47 V,E,SC7Cold Climate Insulation Fireplace Location Clearances to combustibles ClearancesMantel clearances Finishing Material Installation precautions Venting Installation InformationGeneral Venting Canadian Installations1 US Installations2 General Venting Information Termination LocationCanadian Installations USA InstallationsTermination Clearances Rear Vent Installation only Twist Lock PipesHow to Use the Vent Graph Refer to Page 24 for snorkel requirementsVenting installation Vent Pipe ClearancesRear Wall Vent Application Rear Wall Vent Installation Twist Lock PipeStep Rear Wall Vent Installations Flex Vent Pipe Top vent Sidewall ApplicationSince it is very im Portant That Venting SystemMaximum number of 90 elbows per side wall Vertical Sidewall Installation Twist Lock Pipe Always install horizontal venting on a level planeVertical Sidewall installation flex vent pipe Vertical THROUGH-THE-ROOF APPLICA- Tion Below Grade InstallationDo not back fill around snorkel Vertical THROUGH-THE-ROOF Installation Minimum Chimney Clearance Install gas piping to fireplace / burner system location Fireplace installationCheck gas type Natural Gas Do not use open flame to check for gas Electrical WiringLeaks Electrical installation Remote Wall mounted SwitchDo not connect wall switch to 110 Remote Wall SwitchElectronic Pilot Ignition Wiring Remote Wall Switch. The appliance willOptional Fan/Blower Systems Do not connect 110-120 VAC toLeak testing Millivolt Operating InstructionsInitial lighting Never use an open flame to check for gas leakApproved leak testing method Never check for gas leak with open flameLighting the burner Main burner switchPilot position Causing property damage, personal If you do not follow these instructionExactly, a fire or explosion may result Injury or loss of lifeOptional Accessory Requirements Electrician. Main power must be off whenConnecting to main electrical power supply Or performing service. All wiring shall beElectrical Installation Junction BOX WiringCommand Center Wall Installation Wall Switch InstallationElectrical Installation Blotsc Signature Command Blower Optional FAN Blower SystemsBlot Automatic Thermostat Blower FK-12 Manual BlowerOn next Command Center OPERATing InstructionsBattery Installation FeaturesCommand Center Key Combinations for System Settings System CONFIGURATION/SETUPFunction Operation Default Setting Command Center Operations Self Diagnostics ChartFUNCTIONS/OPERATION Function OperationRock wool placement Glass Frame RemovalLog placement Lava rock and ember placementCleaning and maintenance Burner, Pilot and Control Compart- mentVent System Glass DoorLogs Rock woolStanding Pilot Ignition TroubleshootingPoSSIBLE Cause CDVSC7 & CDV7 Series Gas Fireplace Electronic Ignition YeSSignature Command System Operationfault Diagnosis ActionReplacement parts Firebox componentsCDVR33 CDVT33 CDVR36 CDVT36 CDVR42 CDVT42 CDVR47 CDVT47 Standing Pilot Millivolt control Replacement Parts Accessories Description Qty Part NumberFuel Conversion Kits Millivolt Natural Gas to LP LP to Natural GasCDVSC7 & CDV7 Series Gas Fireplace Electronic Ignition13,14,15,16,17 CDVR33NSC7 CDVR33SC7 Vertical Venting Description Model NumberHorizontal Venting 7TBRHTKCDVSC7 & CDV7 Series Gas Fireplace CDVSC7 & CDV7 Series Gas Fireplace Carbon Monoxide Detector Requirements Lifetime Warranty Five Year WarrantyBasic Warranty If Warranty Service is NeededMhsc Model EnerGuide Ratings Fireplace Efficiency %