Monessen Hearth CDV7 manual System CONFIGURATION/SETUP, Key Combinations for System Settings

Page 44

CDVSC7 & CDV7 Series Gas FireplaceSIGNATURE COMMAND SYSTEM OPERATION INSTRUCTIONS

SYSTEM CONFIGURATION/SETUP

All System configuration/setup is done on the Command Center.

NOTE: When using On/Off wall switch, the switch must be in the ON position to perform all configuration set ups at the command center.

Intermittent/Standing Pilot Setup (Default intermittent)

1.Holding the ON button on the Command Center while turning on the master switch will toggle between stand- ing pilot and intermittent pilot.

2.After the above operation, one beep (for standing pilot) or two beeps (for intermittent pilot) will be given as confirmation.

Six-hour Safety Shutdown Option (Default ON)

1.The system comes preset from the factory with a six (6) hour shutdown from its last command of operation. This is done to prevent the fireplace from continuing to operate if unattended. You may disable this feature if you wish.

NOTE: By disabling this feature, your fireplace may continue to operate unattended.

2.When the master switch is in the ON position (“-”), pressing the ON button and the OFF button on the Com- mand Center simultaneously will toggle between enabling and disabling the six-hour shutdown option.

3.After the above operation, one beep (for enabling the six-hour shutdown option) or two beeps (for disabling the six-hour shutdown option) will be given as confirmation.

Remote Transmitter Learn Function (Default OFF)

1.The RF receiver button located on the Control Board must be in the on position before the learn function can begin. Use paper clip to depress button. One beep for RF receiver ON or two beeps for RF receiver OFF will be given as confirmation. Refer to Figure 60 for location.

2.After the RF receiver is on, holding the OFF button on the Command Center while turning on the master switch will activate the learn function for the transmitter.

3.After the above operation, two beeps will be given and the green LED on the Command Center will flash for 10 seconds.

4.During the 10 seconds, press the OFF button on a transmitter to learn. Another two beeps will be given to confirm a successful learning. Refer to transmitter instructions for remote operations.

Shutting Off the Standing Pilot (Temporary Shut Off)

To shut off the standing pilot for service or summer shut down, press and hold the ON button on the Command Center for 3 seconds when the master switch is in the ON position (“-”) and the main burner is off.

Note: Pilot will resume the next time system is turned on.

Key Combinations for System Settings

NOTE: When On/Off wall switch is used, it must be in the On position to perform all system setups.

Function

operation

Default Setting

Intermittent/Standing

Hold the ON button while turning on the master switch

Intermittent

Pilot Setup

(Beep once for standing pilot, twice for intermittent pilot)

Pilot

Standing Pilot Temp.

Hold the ON button 3 seconds (when the master switch

 

Shutoff

on the main burner is off)

 

RF Remote Receiver

Push the RF receiver On/Off button on the control board

RF OFF

On/Off

Beep once for ON and beep twice for OFF

 

Learn Remote

Hold the OFF button while turning on the master switch

 

Transmitter

(Beep twice then press any handheld remote button)

 

6-hour safety

Press the ON button and OFF button simultaneously

ON

shutdown setup

(Beep once for ON, twice for OFF)

 

 

 

 

44

69D3011

Image 44
Contents Cdvt CdvrDo not try to light any appliance Consumer Retain this manual for future refer- encePre-Installation Information Electrical WiringCheck Gas Pressure Signature Command System36 Operating Instructions Electronic IgnitionOwner Important Safety InformationInstaller Code Approval Never connect unit to private non-utilityGas wells. This gas is commonly known As wellhead gasProduct features Product SpecificationsGAS Specifications & Orifice Size Cdvr Series GAS Specifications & Orifice Size Cdvt SeriesHigh Elevations GAS pressuresCDVR33V,E7 Fireplace dimensions & FramingFraming Dimensions CDVT33V,E,SC7 CDVT36 V,E,SC7 CDVT42 V,E,SC7 CDVT47 V,E,SC7Cold Climate Insulation Fireplace Location Mantel clearances ClearancesClearances to combustibles Finishing Material General Venting Venting Installation InformationInstallation precautions Canadian Installations1 US Installations2 General Venting Information Termination LocationTermination Clearances USA InstallationsCanadian Installations Rear Vent Installation only Twist Lock PipesHow to Use the Vent Graph Refer to Page 24 for snorkel requirementsVenting installation Vent Pipe ClearancesStep Rear Wall Vent Installation Twist Lock PipeRear Wall Vent Application Rear Wall Vent Installations Flex Vent Pipe Top vent Sidewall ApplicationSince it is very im Portant That Venting SystemMaximum number of 90 elbows per side wall Vertical Sidewall Installation Twist Lock Pipe Always install horizontal venting on a level planeVertical Sidewall installation flex vent pipe Do not back fill around snorkel Below Grade InstallationVertical THROUGH-THE-ROOF APPLICA- Tion Vertical THROUGH-THE-ROOF Installation Minimum Chimney Clearance Check gas type Fireplace installationInstall gas piping to fireplace / burner system location Natural Gas Leaks Electrical WiringDo not use open flame to check for gas Electrical installation Remote Wall mounted SwitchDo not connect wall switch to 110 Remote Wall SwitchElectronic Pilot Ignition Wiring Remote Wall Switch. The appliance willOptional Fan/Blower Systems Do not connect 110-120 VAC toLeak testing Millivolt Operating InstructionsInitial lighting Never use an open flame to check for gas leakApproved leak testing method Never check for gas leak with open flamePilot position Main burner switchLighting the burner Causing property damage, personal If you do not follow these instructionExactly, a fire or explosion may result Injury or loss of lifeOptional Accessory Requirements Electrician. Main power must be off whenConnecting to main electrical power supply Or performing service. All wiring shall beElectrical Installation Junction BOX WiringCommand Center Wall Installation Wall Switch InstallationElectrical Installation Blotsc Signature Command Blower Optional FAN Blower SystemsBlot Automatic Thermostat Blower FK-12 Manual BlowerOn next Command Center OPERATing InstructionsCommand Center FeaturesBattery Installation Function Operation Default Setting System CONFIGURATION/SETUPKey Combinations for System Settings Command Center Operations Self Diagnostics ChartFUNCTIONS/OPERATION Function OperationRock wool placement Glass Frame RemovalLog placement Lava rock and ember placementCleaning and maintenance Burner, Pilot and Control Compart- mentVent System Glass DoorLogs Rock woolPoSSIBLE Cause TroubleshootingStanding Pilot Ignition CDVSC7 & CDV7 Series Gas Fireplace Electronic Ignition YeSSignature Command System Operationfault Diagnosis ActionReplacement parts Firebox componentsCDVR33 CDVT33 CDVR36 CDVT36 CDVR42 CDVT42 CDVR47 CDVT47 Standing Pilot Millivolt control Replacement Parts Accessories Description Qty Part NumberFuel Conversion Kits Millivolt Natural Gas to LP LP to Natural GasCDVSC7 & CDV7 Series Gas Fireplace Electronic Ignition13,14,15,16,17 CDVR33NSC7 CDVR33SC7 Vertical Venting Description Model NumberHorizontal Venting 7TBRHTKCDVSC7 & CDV7 Series Gas Fireplace CDVSC7 & CDV7 Series Gas Fireplace Carbon Monoxide Detector Requirements Lifetime Warranty Five Year WarrantyBasic Warranty If Warranty Service is NeededMhsc Model EnerGuide Ratings Fireplace Efficiency %