CDVSC7 & CDV7 Series Gas Fireplace | troubleshooting | ||
Standing Pilot Ignition |
| ||
SYMPTOM | poSSIBLE CAUSE | ACTION | |
|
|
|
|
1. | Spark ignitor will | A. Wire disconnected. | A. Open door and check to make sure wire is connected to |
| not light pilot after |
| ignitor. |
| repeated triggering of | B. Defective ignitor. | B. Check for spark at electrode and pilot. If no spark and |
| piezo. |
| electrode wire is properly connected, replace pilot |
|
|
| assembly. |
|
| C. No gas or low gas pres- | C. Check remote/manual shut off valve from fireplace. Low |
|
| sure. | pressure can be caused by bent lines, restricted lines, |
|
|
| low pressure line pressure. Consult with plumber or gas |
|
|
| supplier. |
|
| D. No Propane/LPG in tank | D. Check Propane/LPG tank. Refill tank. |
|
|
| |
2. Pilot will not stay lit | A. Defective thermocouple | A. Check that thermocouple flame impinges on thermo- | |
| after carefully follow- |
| couple. Clean and/or adjust pilot for maximum flame |
| ing lighting instruc- |
| impingement. Ensure that the thermocouple connection |
| tions. |
| at the gas valve is fully inserted and tight. |
|
|
| Disconnect the thermocouple from the valve, place one |
|
|
| millivolt lead wire on the tip of the thermocouple and the |
|
|
| other meter lead wire on the thermocouple copper lead. |
|
|
| Start the pilot and hold the valve knob in. If the millivolt |
|
|
| reading is less than 15 mV, replace pilot assembly. |
|
|
| B. If thermocouple is producing more than 15 mV, replace |
|
| B. Defective valve | faulty valve. |
|
|
|
|
3. | Pilot burning, valve |
| A. Check switch and wire for proper connection. Place |
A. Defective switch, wall | jumper wires across terminals of switch. If burner comes | ||
| knob turned to “ON”, | switch, remote control or | on, replace defective switch.If the switch is OK, repeat |
| switch is turned to | wire | the same procedure on remote control If burner comes |
| “ON” or “RS”, but |
| on, replace remote control. |
| burner will not ignite. |
| Place jumper wire across wire at gas valves (terminals |
|
|
| marked TH and TP/TH). If burner comes on, wires are |
|
|
| faulty or connections are bad. Replace wire. |
|
|
| B. If pilot flame is not close enough to the thermopile, adjust |
|
| B. Pilot flame too small | pilot flame. |
|
|
| C. Check thermopile wire connections to make sure all |
|
| C. Defective or malfunction- | are tight and that the thermopile is fully inserted into |
|
| ing thermopile | pilot assembly. Check thermopile with a millivolt meter. |
|
|
| Connect leads to TP and TP/TH terminals on the control |
|
|
| valve. If meter reading is below 325 mV, replace pilot |
|
|
| assembly. |
|
|
| D. Turn valve knob to “On” and switch to “ON.” Take a read- |
|
| D. Defective valve | ing at the thermopile leads (TP & TP/TH) on the valve. |
|
|
| If the meter reads greater than 175 mV and the burner |
does not light, replace defective valve.
50 | 69D3011 |