Monessen Hearth CDV7 Rear Wall Vent Application, Rear Wall Vent Installation Twist Lock Pipe

Page 19

Venting installation

CDVSC7 & CDV7 Series Gas Fireplace

Rear Wall Vent Application

When installed as a rear vent unit this appliance may be vented directly to a termination located on the rear wall behind the appliance.

Only MHSC venting components are approved to be used in these applications (Refer to ‘Venting Compo- nents’ listed for different installation requirements).

The maximum horizontal distance between the rear of the appliance (or end of the transition elbow in a cor- ner application) and the outside face of the rear wall is 20” (508 mm). Figure 14

Only one 45° elbow is allowed in these installations.

Minimum clearances between vent pipe and combus- tible materials are as follows:

Top - 3” (76 mm)

-except at outside wall 1" (25 mm)

Sides - 1” (25 mm)

Bottom - 1” (25 mm)

Rear Vent Top

View

20”

(508 mm)

Max.

Figure 15 -

Rear Vent Application, No Elbows

REAR WALL VENT INSTALLATION - TWIST LOCK PIPE

Step 1

Locate and cut the vent opening in the wall.

For combustible walls first frame in opening. Figure 16

NOTE: When using flex vent, the opening will have to be measured according to the 1” (25 mm) rise in 24” (610 mm) vertical run.

Combustible Walls: Cut a 9B\,”H x 9B\,” W (244 x 244

mm)hole through the exterior wall and frame as shown. Figure 16

Noncombustible Walls: Hole opening should be 7Z\x” (191 mm) diameter.

Vent Opening for Combustible Walls

9B\,

(244 mm) Min.

9B\,

(244 mm)

Min.

 

 

Framing Detail

Fireplace Hearth

 

Opening for Noncombustible Wall

7Z\x

(190 mm)

FP2293

Figure 16 - Fireplace Hearth

Locate vent opening on wall

Step 2

Secure firestop to the inside frame, center in the 9B\," x 9B\," vent opening.

Step 3

Measure the horizontal length requirement for the venting including a 2” (51 mm) overlap, i.e. from the elbow to the outside wall face plus 2” (51 mm). Figure 15

Step 4

Install the 4” (102 mm) vent to the appliance collar and secure with 3 sheet metal screws. Install the 7” (178 mm) vent pipe to the appliance collar and secure with 3 sheet metal screws. It is not necessary to seal this connection. If a 45° elbow is being used attach the elbow to the appli- ance in the same manner then attach the venting to the elbow.

It is critical that there is no downward slope away from the appliance when connecting the vent or elbow.

Step 5

Guide the venting through the vent hole as you place the appliance in its installed position. Guide the 4” (102 mm) and 7” (178 mm) collar of the vent termination into the outer ends of the venting. Do not force the termination. If the vent pipes do not align with the termination, remove and realign the venting at the appliance flue collars. Fig- ure 17. Attach the termination to the wall as outlined in the instruction sheet supplied with the termination.

69D3011

19

Image 19
Contents Consumer Retain this manual for future refer- ence CdvtCdvr Do not try to light any applianceOperating Instructions Electronic Ignition Pre-Installation InformationElectrical Wiring Check Gas Pressure Signature Command System36Installer Important Safety InformationOwner As wellhead gas Code ApprovalNever connect unit to private non-utility Gas wells. This gas is commonly knownProduct Specifications Product featuresGAS pressures GAS Specifications & Orifice Size Cdvr SeriesGAS Specifications & Orifice Size Cdvt Series High ElevationsFraming Dimensions Fireplace dimensions & FramingCDVR33V,E7 CDVT36 V,E,SC7 CDVT42 V,E,SC7 CDVT47 V,E,SC7 CDVT33V,E,SC7Cold Climate Insulation Fireplace Location Clearances to combustibles ClearancesMantel clearances Finishing Material Installation precautions Venting Installation InformationGeneral Venting General Venting Information Termination Location Canadian Installations1 US Installations2Canadian Installations USA InstallationsTermination Clearances Twist Lock Pipes Rear Vent Installation onlyRefer to Page 24 for snorkel requirements How to Use the Vent GraphVent Pipe Clearances Venting installationRear Wall Vent Application Rear Wall Vent Installation Twist Lock PipeStep Venting System Rear Wall Vent Installations Flex Vent PipeTop vent Sidewall Application Since it is very im Portant ThatMaximum number of 90 elbows per side wall Always install horizontal venting on a level plane Vertical Sidewall Installation Twist Lock PipeVertical Sidewall installation flex vent pipe Vertical THROUGH-THE-ROOF APPLICA- Tion Below Grade InstallationDo not back fill around snorkel Vertical THROUGH-THE-ROOF Installation Minimum Chimney Clearance Install gas piping to fireplace / burner system location Fireplace installationCheck gas type Natural Gas Do not use open flame to check for gas Electrical WiringLeaks Remote Wall Switch Electrical installationRemote Wall mounted Switch Do not connect wall switch to 110Do not connect 110-120 VAC to Electronic Pilot Ignition WiringRemote Wall Switch. The appliance will Optional Fan/Blower SystemsNever use an open flame to check for gas leak Leak testingMillivolt Operating Instructions Initial lightingNever check for gas leak with open flame Approved leak testing methodLighting the burner Main burner switchPilot position Injury or loss of life Causing property damage, personalIf you do not follow these instruction Exactly, a fire or explosion may resultOr performing service. All wiring shall be Optional Accessory RequirementsElectrician. Main power must be off when Connecting to main electrical power supplyWall Switch Installation Electrical InstallationJunction BOX Wiring Command Center Wall InstallationElectrical Installation Optional FAN Blower Systems Blotsc Signature Command BlowerFK-12 Manual Blower Blot Automatic Thermostat BlowerOn next OPERATing Instructions Command CenterBattery Installation FeaturesCommand Center Key Combinations for System Settings System CONFIGURATION/SETUPFunction Operation Default Setting Function Operation Command Center OperationsSelf Diagnostics Chart FUNCTIONS/OPERATIONGlass Frame Removal Rock wool placementLava rock and ember placement Log placementBurner, Pilot and Control Compart- ment Cleaning and maintenanceRock wool Vent SystemGlass Door LogsStanding Pilot Ignition TroubleshootingPoSSIBLE Cause CDVSC7 & CDV7 Series Gas Fireplace YeS Electronic IgnitionOperationfault Diagnosis Action Signature Command SystemFirebox components Replacement partsCDVR33 CDVT33 CDVR36 CDVT36 CDVR42 CDVT42 CDVR47 CDVT47 Standing Pilot Millivolt control LP to Natural Gas Replacement PartsAccessories Description Qty Part Number Fuel Conversion Kits Millivolt Natural Gas to LPElectronic Ignition CDVSC7 & CDV7 Series Gas Fireplace13,14,15,16,17 CDVR33NSC7 CDVR33SC7 Description Model Number Vertical Venting7TBRHTK Horizontal VentingCDVSC7 & CDV7 Series Gas Fireplace CDVSC7 & CDV7 Series Gas Fireplace Carbon Monoxide Detector Requirements If Warranty Service is Needed Lifetime WarrantyFive Year Warranty Basic WarrantyModel EnerGuide Ratings Fireplace Efficiency % Mhsc