Monessen Hearth CDV7 manual How to Use the Vent Graph, Refer to Page 24 for snorkel requirements

Page 17

Venting INSTALLATION INFORMATION

CDVSC7 & CDV7 Series Gas Fireplace

How to Use the Vent Graph

The Vent Graph should be read in conjunction with the following vent installation instructions to determine the re- lationship between the vertical and horizontal dimensions of the vent system.

1.Determine the height of the center of the horizontal vent pipe exiting through the outer wall. Using this di- mension on the Sidewall Vent Graph, Figure 13, locate the point intersecting with the slanted graph line.

2.From the point of this intersection, draw a vertical line to the bottom of the graph.

3.Select the indicated dimension, and position the fire- place in accordance with same.

EXAMPLE A:

If the vertical dimension from the floor of the unit is 11’ (3.4

m)the horizontal run to the face of the outer wall must not exceed 14’ (4.3 m).

EXAMPLE B:

If the vertical dimension from the floor of the unit is 7’ (2.1 m), the horizontal run to the face of the outer wall must not exceed 8’ (2.4 m).

Refer to Page 24 for snorkel requirements.

 

 

 

40

 

 

 

 

 

 

38

 

 

 

of

 

 

36

 

 

 

Center

 

 

34

 

 

 

 

 

32

 

 

 

the

 

 

30

 

 

 

to

 

 

28

 

 

 

Unit

Pipe

 

 

 

 

 

26

 

 

 

Dimension from the Floor of

the Horizontal Vent

 

24

 

 

 

 

22

 

 

 

 

20

 

 

 

 

18

 

 

 

 

16

 

 

 

 

14

 

 

eg: A

 

12

 

 

 

 

 

 

 

10

 

 

 

Vertical

 

 

 

 

 

 

X

8

 

 

 

 

6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

 

 

 

 

 

 

2

 

 

 

 

 

 

2

4

6

8 10 1214 16 1820

Horizontal Dimension From the Outside of Termination to

the Back of the Fireplace

X = 22" minimum for 33" Model

X = 25Z\v" minimum for 36", 42" and 47" Models (Floor to center of horizontal pipe)

Figure 13 -

Side Wall Venting Graph

69D3011

17

Image 17
Contents Cdvr CdvtDo not try to light any appliance Consumer Retain this manual for future refer- enceElectrical Wiring Pre-Installation InformationCheck Gas Pressure Signature Command System36 Operating Instructions Electronic IgnitionOwner Important Safety InformationInstaller Never connect unit to private non-utility Code ApprovalGas wells. This gas is commonly known As wellhead gasProduct Specifications Product featuresGAS Specifications & Orifice Size Cdvt Series GAS Specifications & Orifice Size Cdvr SeriesHigh Elevations GAS pressuresCDVR33V,E7 Fireplace dimensions & FramingFraming Dimensions CDVT36 V,E,SC7 CDVT42 V,E,SC7 CDVT47 V,E,SC7 CDVT33V,E,SC7Cold Climate Insulation Fireplace Location Mantel clearances ClearancesClearances to combustibles Finishing Material General Venting Venting Installation InformationInstallation precautions General Venting Information Termination Location Canadian Installations1 US Installations2Termination Clearances USA InstallationsCanadian Installations Twist Lock Pipes Rear Vent Installation onlyRefer to Page 24 for snorkel requirements How to Use the Vent GraphVent Pipe Clearances Venting installationStep Rear Wall Vent Installation Twist Lock PipeRear Wall Vent Application Top vent Sidewall Application Rear Wall Vent Installations Flex Vent PipeSince it is very im Portant That Venting SystemMaximum number of 90 elbows per side wall Always install horizontal venting on a level plane Vertical Sidewall Installation Twist Lock PipeVertical Sidewall installation flex vent pipe Do not back fill around snorkel Below Grade InstallationVertical THROUGH-THE-ROOF APPLICA- Tion Vertical THROUGH-THE-ROOF Installation Minimum Chimney Clearance Check gas type Fireplace installationInstall gas piping to fireplace / burner system location Natural Gas Leaks Electrical WiringDo not use open flame to check for gas Remote Wall mounted Switch Electrical installationDo not connect wall switch to 110 Remote Wall SwitchRemote Wall Switch. The appliance will Electronic Pilot Ignition WiringOptional Fan/Blower Systems Do not connect 110-120 VAC toMillivolt Operating Instructions Leak testingInitial lighting Never use an open flame to check for gas leakNever check for gas leak with open flame Approved leak testing methodPilot position Main burner switchLighting the burner If you do not follow these instruction Causing property damage, personalExactly, a fire or explosion may result Injury or loss of lifeElectrician. Main power must be off when Optional Accessory RequirementsConnecting to main electrical power supply Or performing service. All wiring shall beJunction BOX Wiring Electrical InstallationCommand Center Wall Installation Wall Switch InstallationElectrical Installation Optional FAN Blower Systems Blotsc Signature Command BlowerFK-12 Manual Blower Blot Automatic Thermostat BlowerOn next OPERATing Instructions Command CenterCommand Center FeaturesBattery Installation Function Operation Default Setting System CONFIGURATION/SETUPKey Combinations for System Settings Self Diagnostics Chart Command Center OperationsFUNCTIONS/OPERATION Function OperationGlass Frame Removal Rock wool placementLava rock and ember placement Log placementBurner, Pilot and Control Compart- ment Cleaning and maintenanceGlass Door Vent SystemLogs Rock woolPoSSIBLE Cause TroubleshootingStanding Pilot Ignition CDVSC7 & CDV7 Series Gas Fireplace YeS Electronic IgnitionOperationfault Diagnosis Action Signature Command SystemFirebox components Replacement partsCDVR33 CDVT33 CDVR36 CDVT36 CDVR42 CDVT42 CDVR47 CDVT47 Standing Pilot Millivolt control Accessories Description Qty Part Number Replacement PartsFuel Conversion Kits Millivolt Natural Gas to LP LP to Natural GasElectronic Ignition CDVSC7 & CDV7 Series Gas Fireplace13,14,15,16,17 CDVR33NSC7 CDVR33SC7 Description Model Number Vertical Venting7TBRHTK Horizontal VentingCDVSC7 & CDV7 Series Gas Fireplace CDVSC7 & CDV7 Series Gas Fireplace Carbon Monoxide Detector Requirements Five Year Warranty Lifetime WarrantyBasic Warranty If Warranty Service is NeededModel EnerGuide Ratings Fireplace Efficiency % Mhsc