CDVSC7 & CDV7 Series Gas Fireplace

check gas type

Use proper gas type for the fireplace you are installing. If you have conflicting gas type, do not install fireplace. See dealer where you purchased the fireplace for proper fireplace for your gas type or con- version kit.

Install gas piping to fireplace / burner system location

WARNING

A qualified installer or service person must connect appliance to gas supply. Follow all local codes.

CAUTION

For propane/LP units, never connect fireplace directly to the propane/LP supply. This burner system requires an external regulator (not supplied). Install the external regulator between the burner system and propane/LP

installation items needed

Before installing fireplace and burner system, make sure you have the items listed below.

External regulator

Piping (check local codes)

Sealant (resistant to propane/LP gas)

 

(supplied by installer)

Equipment shutoff valve*

Test gauge connection*

Sediment trap (recommended)

Tee joint

Pipe wrench

approved flexible gas line with gas connector (if allowed by local codes — not provided)

*A CSA design-certified equipment shutoff valve with 1/8" NPT tap is an acceptable alternative to test gauge connection. Purchase the CSA design-certified equipment shutoff valve from your dealer.

For propane/LP connections only, the installer must supply an external regulator. The external regulator will reduce incoming gas pressure. You must reduce incoming gas pressure to between 11 and 13 inches of water. If you do not reduce incoming gas pressure, burner system regulator damage could occur. Install external regulator with the vent pointing down as shown in Figure 40. Pointing the vent down protects it from freezing rain or sleet.

 

100 lb. (min)

 

Use only new black iron or steel pipe. Internally

 

 

tinned copper or copper tubing can be used

External

Propane/LP

 

Regulator

Supply Tank

CAUTION

per National Fuel Code, Section 2.6.3, providing

 

 

gas meets hydrogen sulfide limits, and where

 

 

permitted by local codes. Gas piping system

 

 

must be sized to provide minimum inlet

 

 

pressure (listed on data plate) at the maximum

 

 

 

 

Vent Pointing

 

flow rate (BTU/hr). Undue pressure loss will

 

 

occur if the pipe is too small.

 

Down

 

 

 

When using copper of flex connectors use only fittings

 

 

approved for gas connections. The gas control inlet is

 

 

3/8" NPT.

 

FP1977

 

 

Figure 40 -

External Regulator with Vent Pointing Down (Propane/LP Only)

69D3011

27

Image 27
Contents Consumer Retain this manual for future refer- ence CdvtCdvr Do not try to light any applianceOperating Instructions Electronic Ignition Pre-Installation InformationElectrical Wiring Check Gas Pressure Signature Command System36Important Safety Information InstallerOwner As wellhead gas Code ApprovalNever connect unit to private non-utility Gas wells. This gas is commonly knownProduct Specifications Product featuresGAS pressures GAS Specifications & Orifice Size Cdvr SeriesGAS Specifications & Orifice Size Cdvt Series High ElevationsFireplace dimensions & Framing Framing DimensionsCDVR33V,E7 CDVT36 V,E,SC7 CDVT42 V,E,SC7 CDVT47 V,E,SC7 CDVT33V,E,SC7Cold Climate Insulation Fireplace Location Clearances Clearances to combustiblesMantel clearances Finishing Material Venting Installation Information Installation precautionsGeneral Venting General Venting Information Termination Location Canadian Installations1 US Installations2USA Installations Canadian InstallationsTermination Clearances Twist Lock Pipes Rear Vent Installation onlyRefer to Page 24 for snorkel requirements How to Use the Vent GraphVent Pipe Clearances Venting installationRear Wall Vent Installation Twist Lock Pipe Rear Wall Vent ApplicationStep Venting System Rear Wall Vent Installations Flex Vent PipeTop vent Sidewall Application Since it is very im Portant ThatMaximum number of 90 elbows per side wall Always install horizontal venting on a level plane Vertical Sidewall Installation Twist Lock PipeVertical Sidewall installation flex vent pipe Below Grade Installation Vertical THROUGH-THE-ROOF APPLICA- TionDo not back fill around snorkel Vertical THROUGH-THE-ROOF Installation Minimum Chimney Clearance Fireplace installation Install gas piping to fireplace / burner system locationCheck gas type Natural Gas Electrical Wiring Do not use open flame to check for gasLeaks Remote Wall Switch Electrical installationRemote Wall mounted Switch Do not connect wall switch to 110Do not connect 110-120 VAC to Electronic Pilot Ignition WiringRemote Wall Switch. The appliance will Optional Fan/Blower SystemsNever use an open flame to check for gas leak Leak testingMillivolt Operating Instructions Initial lightingNever check for gas leak with open flame Approved leak testing methodMain burner switch Lighting the burnerPilot position Injury or loss of life Causing property damage, personalIf you do not follow these instruction Exactly, a fire or explosion may resultOr performing service. All wiring shall be Optional Accessory RequirementsElectrician. Main power must be off when Connecting to main electrical power supplyWall Switch Installation Electrical InstallationJunction BOX Wiring Command Center Wall InstallationElectrical Installation Optional FAN Blower Systems Blotsc Signature Command BlowerFK-12 Manual Blower Blot Automatic Thermostat BlowerOn next OPERATing Instructions Command CenterFeatures Battery InstallationCommand Center System CONFIGURATION/SETUP Key Combinations for System SettingsFunction Operation Default Setting Function Operation Command Center OperationsSelf Diagnostics Chart FUNCTIONS/OPERATIONGlass Frame Removal Rock wool placementLava rock and ember placement Log placementBurner, Pilot and Control Compart- ment Cleaning and maintenanceRock wool Vent SystemGlass Door LogsTroubleshooting Standing Pilot IgnitionPoSSIBLE Cause CDVSC7 & CDV7 Series Gas Fireplace YeS Electronic IgnitionOperationfault Diagnosis Action Signature Command SystemFirebox components Replacement partsCDVR33 CDVT33 CDVR36 CDVT36 CDVR42 CDVT42 CDVR47 CDVT47 Standing Pilot Millivolt control LP to Natural Gas Replacement PartsAccessories Description Qty Part Number Fuel Conversion Kits Millivolt Natural Gas to LPElectronic Ignition CDVSC7 & CDV7 Series Gas Fireplace13,14,15,16,17 CDVR33NSC7 CDVR33SC7 Description Model Number Vertical Venting7TBRHTK Horizontal VentingCDVSC7 & CDV7 Series Gas Fireplace CDVSC7 & CDV7 Series Gas Fireplace Carbon Monoxide Detector Requirements If Warranty Service is Needed Lifetime WarrantyFive Year Warranty Basic WarrantyModel EnerGuide Ratings Fireplace Efficiency % Mhsc