Liebert 3000 manual Operating Status, View/Set Control Setpoints, System Setup, Cold Start Delay

Page 28

Operation with Advanced Microprocessor with Graphics Control

3.5Operating Status

The Operating Status is intended to provide the user with displayed information about what the con- trol is calling for the system to do.

NOTE

There may be some time lapse before a specific component matches the displayed number.

For example: The display indicates the chilled water valve is 68% open. On a new call for cooling, it takes several seconds for the valve to travel from full closed to 68% open. So when the display reads 68%, it may take a few seconds for the valve to actually open 68%. Also, if the display indicates a com- pressor is operating but the compressor has not turned on yet, it may be off because of the short cycle control (see 4.4.1 - Short Cycle Control).

3.6View/Set Control Setpoints

Control setpoints can be reviewed and/or changed through the display. Refer to the following table to see the list of default setpoints and their allowable ranges.

Table 8

Default setpoints and ranges

 

 

 

 

 

 

Setpoint

Default

Range

 

 

 

Temperature Setpoint

72°F

40 to 90°F (5 to 32°C)

 

 

 

Temperature Sensitivity

2.0°F

1 to 9.9°F (0.6 to 5.6°C)

 

 

 

Humidity Setpoint

50%

20 to 80% RH

 

 

 

Humidity Sensitivity

5%

1 to 30% RH

 

 

 

High Temperature Alarm

80°F

35 to 95°F (2 to 35°C)

 

 

 

Low Temperature Alarm

65°F

35 to 95°F (2 to 35°C)

 

 

 

High Humidity Alarm

60%

15 to 85% RH

 

 

 

Low Humidity Alarm

40%

15 to 85% RH

 

 

 

 

3.7System Setup

Selecting SYSTEM SETUP will step to the following menu:

SETUP OPERATION

SELECT OPTIONS

CALIBRATE SENSORS

CALIBRATE VALVE ACTUATOR

SELECT CONTROL ALGORITHM (chilled water or SCR Reheats only)

SELECT HUMIDITY SENSING MODE

SET STATUS DISPLAY

CHANGE PASSWORDS

3.7.1Setup Operation

The SETUP OPERATION menu permits the review and/or adjustment of the unit configuration. This may include:

Cold Start Delay

This feature, also referred to as Positive Start or Winter Start Kit, allows for the low pressure switch to be ignored for the programmed time during a cold start of the compressor. Entering a “0” for this time will bypass this feature. A “1” will bypass the low pressure switch for one minute, a “2” for two minutes, etc. The programmed value can be from 0 to 3 minutes. This delay is factory set to 0 for water cooled, glycol cooled, and GLYCOOL units. Typically, only air cooled units need a “Winter Start” time.

20

Image 28
Contents Liebert Challenger Page Table of Contents Run Diagnostics Alarm Descriptions Component Operation and MaintenanceHumidifier Figures Page System Descriptions Compressorized SystemsGlycool Chilled Glycol Cooling Systems Chilled Water SystemsStart-Up Procedure Basics Advanced microprocessor control panelAdvanced microprocessor a control for Challenger Status Display Status/Alarm DataMain Menu MENU/ESC Setpoints/Setup Default setpoints and rangesRun Hours Log Analog SensorsSetup System Setup OperationSelect Options Show DIP SwitchesCalibrate Sensors Setup Alarms Alarm default time delaysDefault Time Alarm Delay secondsStandard Custom Alarm Messages Humidity HUM Control MethodSet Status Display Analog SetupCalibrate Actuator Run Diagnostics Show InputsTest Outputs Test Control BoardChange Passwords Date and TimeControl Circuit Board LCD Display ContrastDIP Switches Non-Volatile MemoryControl Outputs Control output LEDsOperation with Advanced Microprocessor with Graphics Control Advanced microprocessor with graphics control menu View/Set Alarms See 3.7.7 Set Status DisplaySetup Alarms Setup Water Detect Floor Plan Setup Custom AlarmsView Water Detect Floor Plan for Optional LTM1000/LT750 System Setup Cold Start DelayOperating Status View/Set Control SetpointsAuto Restart Delay Default Settings and RangesIR Flush Overfill infrared humidifiers only Chilled Water/Hot Water/Econ-O-Coil FlushCalibrate Valve Actuator Select Control Algorithm Chilled Water and SCR Reheats onlyRun Diagnostics Select Humidity Sensing ModeShow Inputs Plot Graphs Setting optionsModify Plot Scales Analog/Digital Inputs View Run Hours LogView Total Run Hours View 24 Hour Run Time HistoryLCD Contrast Nonvolatile Memory Temperature Control Cooling/Heating Required, in Percent %Response to Control Types Proportional Control PID Control Chilled Water or SCR Reheats onlyGlycool Cooling Dual Cooling SourceChilled Water Cooling Cooling/dehumidification load status responseHumidity Control Heating Operation Electric ReheatHot Water Reheat SCR Electric Reheat Requires Special Control SoftwareHumidification Operation System Activation Control TypesProportional Control Time between peaks x 5% Load Control Features Additional FeaturesConnecting the Analog Sensors Short Cycle ControlInstallation-LT750 DIP Switch Settings FaultWater Detection Display LT750 Environmental UnitPhysical Connections SetupCalibration Communications Liebert Monitoring Devices and SoftwareStandard Alarms Change FilterCustom Alarms High TemperatureCompressor Overload High Head PressureHigh Temperature and Low Temperature Simultaneously Humidifier Problem Infrared HumidifiersLoss of Power Low TemperatureOptional/Custom Alarms System Testing Firestat Smoke DetectorWater Detection Sensor Liebert unit Recommended Liquitect location Floor drainZone leak detection kit installation scenarios FiltersRemote Shutdown Distance From UnitBlower Package Fan Impellers and BearingsBelt Air DistributionRefrigeration System Suction PressureDischarge Pressure SuperheatThermostatic Expansion Valve Operation AdjustmentHot Gas Bypass Valve Operation Outdoor fan/condenser configuration Air Cooled CondenserRegulating Valve Water/Glycol Cooled Condensers Coaxial CondenserValve spring guide Glycol Solution Maintenance Adjusting Collar NutCompressor Functional Check Compressor ReplacementMechanical Failure Compressor Replacement Procedure Electrical FailureCleaning the Pan HumidifierInfrared Humidifier Removing the PanAutoflush Infrared Humidifier Cleaning System Autoflush OperationAutoflush Controls Steam Generating HumidifierOperation ControlsReplacing the Canister Humidifier canister part numbersPart Capacity Number Voltage Lbs/hr kg/hr 200-460Circuit Board Adjustments Drain Tempering FeatureChilled water troubleshooting Blower troubleshootingSymptom Possible Cause Check or Remedy Compressor and refrigeration system troubleshooting Compressor and refrigeration system troubleshooting Dehumidification troubleshooting Glycol pump troubleshootingInfrared humidifier troubleshooting See 6.4.8 Compressor Functional Check and TableSteam generating humidifier troubleshooting Reheat troubleshooting Filters Steam Generating Humidifier Blower SectionCompressor Air Cooled Condenser if applicableFilters Water/Glycol Condenser if applicableGlycol Pump Electrical PanelSemiannual Maintenance Inspection Checklist Page Ne t ItiTi n That
Related manuals
Manual 76 pages 48.63 Kb Manual 59 pages 52.87 Kb

3000 specifications

The Liebert 3000 is a cutting-edge power protection solution designed to provide reliable and efficient backup power for critical applications. This uninterruptible power supply (UPS) system is engineered to safeguard sensitive electronic equipment from power disturbances, ensuring uninterrupted operations in data centers, telecommunications, and industrial environments.

One of the standout features of the Liebert 3000 is its high-efficiency design. With an efficiency rating of up to 94%, the system minimizes energy loss, resulting in lower operational costs and a reduced carbon footprint. This is particularly important in today's environmentally conscious climate, as organizations strive to meet sustainability goals while maintaining top-tier performance.

The Liebert 3000 employs advanced technologies to enhance its functionality. It incorporates online double-conversion technology, which provides a continuous supply of clean and regulated power. This technology ensures that connected loads receive stable voltage and frequency, shielding them from voltage spikes, sags, and outages. Additionally, the UPS offers features such as automatic battery testing, which helps ensure peak battery performance and reliability.

Another key characteristic of the Liebert 3000 is its modular design, allowing for flexible scalability. This means that organizations can easily expand the capacity of their UPS system as their power needs grow, without the need for extensive system overhauls. The modular architecture also facilitates simplified maintenance and reduces downtime, as individual modules can be serviced without interrupting power to the critical load.

The system is equipped with comprehensive monitoring and management capabilities. The Liebert 3000 provides real-time data on power usage, battery status, and system performance, enabling facility managers to make informed decisions and proactively address potential issues. The integration of remote management tools allows for seamless monitoring from anywhere, providing peace of mind for operators.

Overall, the Liebert 3000 combines high efficiency, advanced technology, and flexible design to deliver a robust power protection solution. Its reliability and performance make it a preferred choice for organizations seeking to protect their critical infrastructure while enhancing operational efficiency and sustainability. As businesses continue to rely on technology for their everyday operations, the Liebert 3000 stands out as a dependable safeguard against the uncertainties of power quality.