Liebert 3000 manual Infrared Humidifier, Removing the Pan, Cleaning the Pan

Page 61

Component Operation and Maintenance

6.5Humidifier

6.5.1Infrared Humidifier

During normal humidifier operation, deposits of mineral solids will collect in the humidifier pan. This should be cleaned out periodically to ensure efficient operation. Each water supply has different char- acteristics, so the time interval between cleanings must be determined locally. A monthly check (and cleaning if necessary) is recommended.

Removing the Pan

To remove humidifier pan, first open disconnect switch and open front panel. Allow time for pan and water to cool. Unlatch front retainer clip (or remove screw from bracket on some units). Pull pan for- ward. Remove stand pipe to allow pan to drain. Disconnect drain line. Pull pan forward to remove it.

! CAUTION

Before removing pan, be sure power to unit is disconnected and water in the humidifier pan is no hotter than lukewarm.

Cleaning the Pan

An autoflush system can greatly increase the time between cleanings but does not eliminate the need for periodic checks and maintenance.

Scale on the side and bottom can be loosened with a stiff brush. Flush with water and replace pan in humidifier.

Changing Humidifier Lamps

1.Open disconnect switch.

2.Open front panel.

3.Remove screws securing line voltage compartment cover, then remove the cover.

4.In line voltage compartment, disconnect one end of the purple jumpers, then locate the burned out bulb with a continuity meter.

5.Remove humidifier pan. Refer to Removing the Pan on page 53.

6.Remove lamp brackets (2) under lamps.

Figure 12 Infrared humidifier lamps

Humidifier Lamps

7.Loosen two screws securing bulb wires to junction block.

8.Pull bulb straight down.

9.Replace bulb. Wrap wires once loosely around bulb. This will support the bulb and also allow for thermal expansion. Make sure lamp wires are secure in the junction block.

! CAUTION

Do not touch the quartz lamps with your bare hands. Oily deposits such as fingerprints will severely shorten bulb life. Use clean cotton gloves at all times.

10. Reverse Steps 1 through 6 to reassemble.

53

Image 61
Contents Liebert Challenger Page Table of Contents Run Diagnostics Component Operation and Maintenance Alarm DescriptionsHumidifier Figures Page Compressorized Systems System DescriptionsGlycool Chilled Glycol Cooling Systems Chilled Water SystemsStart-Up Procedure Advanced microprocessor control panel BasicsAdvanced microprocessor a control for Challenger Status Display Status/Alarm DataMain Menu MENU/ESC Default setpoints and ranges Setpoints/SetupRun Hours Log Analog SensorsSetup Operation Setup SystemSelect Options Show DIP SwitchesCalibrate Sensors Alarm default time delays Setup AlarmsDefault Time Alarm Delay secondsHumidity HUM Control Method Standard Custom Alarm MessagesSet Status Display Analog SetupCalibrate Actuator Show Inputs Run DiagnosticsTest Outputs Test Control BoardDate and Time Change PasswordsControl Circuit Board LCD Display ContrastNon-Volatile Memory DIP SwitchesControl Outputs Control output LEDsOperation with Advanced Microprocessor with Graphics Control Advanced microprocessor with graphics control menu See 3.7.7 Set Status Display View/Set AlarmsSetup Alarms Setup Water Detect Floor Plan Setup Custom AlarmsView Water Detect Floor Plan for Optional LTM1000/LT750 Cold Start Delay System SetupOperating Status View/Set Control SetpointsDefault Settings and Ranges Auto Restart DelayIR Flush Overfill infrared humidifiers only Chilled Water/Hot Water/Econ-O-Coil FlushSelect Control Algorithm Chilled Water and SCR Reheats only Calibrate Valve ActuatorSelect Humidity Sensing Mode Run DiagnosticsShow Inputs Plot Graphs Setting optionsModify Plot Scales View Run Hours Log Analog/Digital InputsView Total Run Hours View 24 Hour Run Time HistoryLCD Contrast Nonvolatile Memory Cooling/Heating Required, in Percent % Temperature ControlResponse to Control Types Proportional Control PID Control Chilled Water or SCR Reheats onlyDual Cooling Source Glycool CoolingChilled Water Cooling Cooling/dehumidification load status responseHeating Operation Electric Reheat Humidity ControlHot Water Reheat SCR Electric Reheat Requires Special Control SoftwareHumidification Operation System Activation Control TypesProportional Control Time between peaks x 5% Additional Features Load Control FeaturesConnecting the Analog Sensors Short Cycle ControlFault Installation-LT750 DIP Switch SettingsWater Detection Display LT750 Environmental UnitPhysical Connections SetupCalibration Liebert Monitoring Devices and Software CommunicationsChange Filter Standard AlarmsHigh Temperature Custom AlarmsCompressor Overload High Head PressureHumidifier Problem Infrared Humidifiers High Temperature and Low Temperature SimultaneouslyLoss of Power Low TemperatureOptional/Custom Alarms System Testing Smoke Detector FirestatWater Detection Sensor Liebert unit Recommended Liquitect location Floor drainFilters Zone leak detection kit installation scenariosRemote Shutdown Distance From UnitFan Impellers and Bearings Blower PackageBelt Air DistributionSuction Pressure Refrigeration SystemDischarge Pressure SuperheatThermostatic Expansion Valve Operation AdjustmentHot Gas Bypass Valve Operation Air Cooled Condenser Outdoor fan/condenser configurationRegulating Valve Water/Glycol Cooled Condensers Coaxial CondenserValve spring guide Adjusting Collar Nut Glycol Solution MaintenanceCompressor Functional Check Compressor ReplacementMechanical Failure Electrical Failure Compressor Replacement ProcedureHumidifier Cleaning the PanInfrared Humidifier Removing the PanAutoflush Operation Autoflush Infrared Humidifier Cleaning SystemAutoflush Controls Steam Generating HumidifierControls OperationHumidifier canister part numbers Replacing the CanisterPart Capacity Number Voltage Lbs/hr kg/hr 200-460Drain Tempering Feature Circuit Board AdjustmentsChilled water troubleshooting Blower troubleshootingSymptom Possible Cause Check or Remedy Compressor and refrigeration system troubleshooting Compressor and refrigeration system troubleshooting Glycol pump troubleshooting Dehumidification troubleshootingInfrared humidifier troubleshooting See 6.4.8 Compressor Functional Check and TableSteam generating humidifier troubleshooting Reheat troubleshooting Blower Section Filters Steam Generating HumidifierCompressor Air Cooled Condenser if applicableWater/Glycol Condenser if applicable FiltersGlycol Pump Electrical PanelSemiannual Maintenance Inspection Checklist Page Iti Ne tTi n That
Related manuals
Manual 76 pages 48.63 Kb Manual 59 pages 52.87 Kb

3000 specifications

The Liebert 3000 is a cutting-edge power protection solution designed to provide reliable and efficient backup power for critical applications. This uninterruptible power supply (UPS) system is engineered to safeguard sensitive electronic equipment from power disturbances, ensuring uninterrupted operations in data centers, telecommunications, and industrial environments.

One of the standout features of the Liebert 3000 is its high-efficiency design. With an efficiency rating of up to 94%, the system minimizes energy loss, resulting in lower operational costs and a reduced carbon footprint. This is particularly important in today's environmentally conscious climate, as organizations strive to meet sustainability goals while maintaining top-tier performance.

The Liebert 3000 employs advanced technologies to enhance its functionality. It incorporates online double-conversion technology, which provides a continuous supply of clean and regulated power. This technology ensures that connected loads receive stable voltage and frequency, shielding them from voltage spikes, sags, and outages. Additionally, the UPS offers features such as automatic battery testing, which helps ensure peak battery performance and reliability.

Another key characteristic of the Liebert 3000 is its modular design, allowing for flexible scalability. This means that organizations can easily expand the capacity of their UPS system as their power needs grow, without the need for extensive system overhauls. The modular architecture also facilitates simplified maintenance and reduces downtime, as individual modules can be serviced without interrupting power to the critical load.

The system is equipped with comprehensive monitoring and management capabilities. The Liebert 3000 provides real-time data on power usage, battery status, and system performance, enabling facility managers to make informed decisions and proactively address potential issues. The integration of remote management tools allows for seamless monitoring from anywhere, providing peace of mind for operators.

Overall, the Liebert 3000 combines high efficiency, advanced technology, and flexible design to deliver a robust power protection solution. Its reliability and performance make it a preferred choice for organizations seeking to protect their critical infrastructure while enhancing operational efficiency and sustainability. As businesses continue to rely on technology for their everyday operations, the Liebert 3000 stands out as a dependable safeguard against the uncertainties of power quality.