Liebert 3000 manual Time between peaks x 5%

Page 41

System Performance with Advanced Microprocessor Controls

A suggested tuning procedure is as follows:

1.Initially adjust the integral and derivative settings to 0%/ degree-min and 0% /degree/min.

2.Starting with 20% /degree, adjust the proportional setting in small increments (10% steps) until the control sustains a constant hunting action (the temperature swings are approximately the same amplitude from one peak to the next).

3.Note the time in minutes between peaks of adjacent temperature swings and the amplitude of the temperature swing (degrees above the setpoint).

4.Adjust the proportional control setting to about 1/2 the value obtained in Step 2.

5.Adjust the integral setting to a value calculated by the following equation:

Approximate room load (in % full load)

Time between peaks x peak amplitude x 4

NOTE

If this calculation results in a value of less than 1%, then set the integral to 1%.

Adjust the derivative to a value calculated by the following equation:

time between peaks x 5%

The above tuning procedure is only an approximation for an initial set of adjustments and are based on the “average” room characteristics. Your particular settings may need to be further adjusted for optimum PID control performance. Some suggestions for additional tuning are as follows:

If cooling output overshoot is occurring on load changes, decrease the proportional setting or the derivative setting.

If system hunting occurs with constant room load, decrease the integral setting.

If the control responds too slowly, resulting in large temperature excursions on a load change, increase the proportional setting or the derivative setting.

If a constant temperature deviation exists between the temperature and setpoint, increase the integral setting.

4.3.3Intelligent Control (Chilled Water only)

The intelligent control operates from a set of general rules that define how the control output should be adjusted for different system conditions. The rules are designed to duplicate the actions that an experienced human operator would take if manually controlling the system.

Just as an operator might take several things into consideration before making a temperature control decision, the intelligent control can be programmed to do likewise. For example, not only is the cur- rent temperature used in making temperature control decisions, but also conditions such as:

How fast is the temperature changing?

What direction is the temperature changing?

What is the cooling output now?

What was the cooling output in the past?

How long ago was the cooling output changed?

and other factors.

Any number of rules can be used in an intelligent control to define the controls operation under vari- ous operating conditions. Hence, several advantages are gained from this type of control over a more standard control approach that uses a fixed mathematical equation to define the operation of the con- trol for all conditions (such as a proportional or PID control). You can expect intelligent control to be more efficient and precise for most applications, but system performance based on room conditions is not as predictable as standard approaches that use a fixed equation.

33

Image 41
Contents Liebert Challenger Page Table of Contents Run Diagnostics Component Operation and Maintenance Alarm DescriptionsHumidifier Figures Page Compressorized Systems System DescriptionsGlycool Chilled Glycol Cooling Systems Chilled Water SystemsStart-Up Procedure Advanced microprocessor control panel BasicsAdvanced microprocessor a control for Challenger Main Menu MENU/ESC Status/Alarm DataStatus Display Default setpoints and ranges Setpoints/SetupRun Hours Log Analog SensorsSetup Operation Setup SystemCalibrate Sensors Show DIP SwitchesSelect Options Alarm default time delays Setup AlarmsDefault Time Alarm Delay secondsHumidity HUM Control Method Standard Custom Alarm MessagesCalibrate Actuator Analog SetupSet Status Display Show Inputs Run DiagnosticsTest Outputs Test Control BoardDate and Time Change PasswordsControl Circuit Board LCD Display ContrastNon-Volatile Memory DIP SwitchesControl Outputs Control output LEDsOperation with Advanced Microprocessor with Graphics Control Advanced microprocessor with graphics control menu See 3.7.7 Set Status Display View/Set AlarmsSetup Alarms View Water Detect Floor Plan for Optional LTM1000/LT750 Setup Custom AlarmsSetup Water Detect Floor Plan Cold Start Delay System SetupOperating Status View/Set Control SetpointsDefault Settings and Ranges Auto Restart DelayIR Flush Overfill infrared humidifiers only Chilled Water/Hot Water/Econ-O-Coil FlushSelect Control Algorithm Chilled Water and SCR Reheats only Calibrate Valve ActuatorSelect Humidity Sensing Mode Run DiagnosticsShow Inputs Modify Plot Scales Setting optionsPlot Graphs View Run Hours Log Analog/Digital InputsLCD Contrast View 24 Hour Run Time HistoryView Total Run Hours Nonvolatile Memory Cooling/Heating Required, in Percent % Temperature ControlResponse to Control Types Proportional Control PID Control Chilled Water or SCR Reheats onlyDual Cooling Source Glycool CoolingChilled Water Cooling Cooling/dehumidification load status responseHeating Operation Electric Reheat Humidity ControlHot Water Reheat SCR Electric Reheat Requires Special Control SoftwareProportional Control Control TypesHumidification Operation System Activation Time between peaks x 5% Additional Features Load Control FeaturesConnecting the Analog Sensors Short Cycle ControlFault Installation-LT750 DIP Switch SettingsWater Detection Display LT750 Environmental UnitCalibration SetupPhysical Connections Liebert Monitoring Devices and Software CommunicationsChange Filter Standard AlarmsHigh Temperature Custom AlarmsCompressor Overload High Head PressureHumidifier Problem Infrared Humidifiers High Temperature and Low Temperature SimultaneouslyLoss of Power Low TemperatureOptional/Custom Alarms System Testing Smoke Detector FirestatWater Detection Sensor Liebert unit Recommended Liquitect location Floor drainFilters Zone leak detection kit installation scenariosRemote Shutdown Distance From UnitFan Impellers and Bearings Blower PackageBelt Air DistributionSuction Pressure Refrigeration SystemDischarge Pressure SuperheatHot Gas Bypass Valve Operation AdjustmentThermostatic Expansion Valve Operation Air Cooled Condenser Outdoor fan/condenser configurationValve spring guide Water/Glycol Cooled Condensers Coaxial CondenserRegulating Valve Adjusting Collar Nut Glycol Solution MaintenanceMechanical Failure Compressor ReplacementCompressor Functional Check Electrical Failure Compressor Replacement ProcedureHumidifier Cleaning the PanInfrared Humidifier Removing the PanAutoflush Operation Autoflush Infrared Humidifier Cleaning SystemAutoflush Controls Steam Generating HumidifierControls OperationHumidifier canister part numbers Replacing the CanisterPart Capacity Number Voltage Lbs/hr kg/hr 200-460Drain Tempering Feature Circuit Board AdjustmentsSymptom Possible Cause Check or Remedy Blower troubleshootingChilled water troubleshooting Compressor and refrigeration system troubleshooting Compressor and refrigeration system troubleshooting Glycol pump troubleshooting Dehumidification troubleshootingInfrared humidifier troubleshooting See 6.4.8 Compressor Functional Check and TableSteam generating humidifier troubleshooting Reheat troubleshooting Blower Section Filters Steam Generating HumidifierCompressor Air Cooled Condenser if applicableWater/Glycol Condenser if applicable FiltersGlycol Pump Electrical PanelSemiannual Maintenance Inspection Checklist Page Iti Ne tTi n That
Related manuals
Manual 76 pages 48.63 Kb Manual 59 pages 52.87 Kb

3000 specifications

The Liebert 3000 is a cutting-edge power protection solution designed to provide reliable and efficient backup power for critical applications. This uninterruptible power supply (UPS) system is engineered to safeguard sensitive electronic equipment from power disturbances, ensuring uninterrupted operations in data centers, telecommunications, and industrial environments.

One of the standout features of the Liebert 3000 is its high-efficiency design. With an efficiency rating of up to 94%, the system minimizes energy loss, resulting in lower operational costs and a reduced carbon footprint. This is particularly important in today's environmentally conscious climate, as organizations strive to meet sustainability goals while maintaining top-tier performance.

The Liebert 3000 employs advanced technologies to enhance its functionality. It incorporates online double-conversion technology, which provides a continuous supply of clean and regulated power. This technology ensures that connected loads receive stable voltage and frequency, shielding them from voltage spikes, sags, and outages. Additionally, the UPS offers features such as automatic battery testing, which helps ensure peak battery performance and reliability.

Another key characteristic of the Liebert 3000 is its modular design, allowing for flexible scalability. This means that organizations can easily expand the capacity of their UPS system as their power needs grow, without the need for extensive system overhauls. The modular architecture also facilitates simplified maintenance and reduces downtime, as individual modules can be serviced without interrupting power to the critical load.

The system is equipped with comprehensive monitoring and management capabilities. The Liebert 3000 provides real-time data on power usage, battery status, and system performance, enabling facility managers to make informed decisions and proactively address potential issues. The integration of remote management tools allows for seamless monitoring from anywhere, providing peace of mind for operators.

Overall, the Liebert 3000 combines high efficiency, advanced technology, and flexible design to deliver a robust power protection solution. Its reliability and performance make it a preferred choice for organizations seeking to protect their critical infrastructure while enhancing operational efficiency and sustainability. As businesses continue to rely on technology for their everyday operations, the Liebert 3000 stands out as a dependable safeguard against the uncertainties of power quality.