Liebert 3000 manual Compressor Overload, Custom Alarms, High Head Pressure, High Humidity

Page 47

Alarm Descriptions

5.1.2Compressor Overload

An optional tri-block overload device can be used for the compressor. Compressor overload may be manual or automatic reset, depending on your model. Overload is located at the electric connection box on the compressor.

5.1.3Custom Alarms

Custom alarm messages are programmed at the LCD display. The alarms may be specified by the customer at the time of order. Additional devices and wiring may be required at the factory or by oth- ers. The message displayed may be included in this alphabetical list of alarms, or it may be custom- ized text (for up to two alarms). If customized text is used, customer maintenance personnel should be informed of the alarm function and corrective action required.

5.1.4High Head Pressure

Compressor high head is monitored with a pressure switch. One SPDT pressure switch is used for the compressor in the unit. If head pressure exceeds 360 PSIG, the switch opens the compressor contactor and sends an input signal to the control. On a self-contained system, the head pressure switch located at the compressor requires a manual reset and the alarm condition to be acknowledged on the front display panel. On a split system, the high head pressure condition is acknowledged by pressing the alarm silence button that will clear the alarm if the high head pressure condition no longer exists. On a split system, if the compressor is off for 1 hour, the control goes into a special "cold start mode." In the cold start mode on a call for cooling or dehumidification, the Liquid Line Solenoid Valve (LLSV) is energized. If the high pressure switch does NOT trip within 10 seconds, the control returns to normal operation of monitoring the high head pressure switch for three occurrences in a 12-hour period. It is a rolling timer; and after the third high head alarm occurs and is acknowledged by the user, it will lock off the compressor. If while in the cold start mode, the high head pressure switch DOES trip within 10 seconds of the activation of the LLSV, the control does not annunciate the alarm. The con- trol will turn off the LLSV and delay 10 seconds. The control will permit this occurrence two more times or a total of three times. If on the fourth try the high head pressure switch trips within 10 sec- onds, the control will annunciate the alarm, turn off the LLSV, wait for the user to acknowledge the alarm, and hold the compressor off for three minutes, which is the normal short cycle control. On the third occurrence, the control will lock the compressor off until the control power is reset.

On air cooled systems, check for power shut off to the condenser, condenser fans not working, defec- tive head pressure control valves, closed service valves, dirty condenser coils, and crimped lines. Also, make sure that when the compressor contactor is energized, the side switch on the contactor closes to energize the control circuit on the air cooled condenser.

On water/glycol/GLYCOOL systems, check water regulating valves. Verify water/glycol flow (are pumps operating and service valves open?). Is water tower or drycooler operating? Is the coolant tem- perature entering the condenser at or below design conditions? Is relay R5 operating during cooling to turn on the drycooler?

5.1.5High Humidity

The return air humidity has increased to the High Humidity Alarm setpoint. Is the unit setup for dehumidification (check DIP switch)? Check for proper setpoints. Does the room have a vapor barrier to seal it from outdoor humidity? Are doors or windows open to outside air? Run diagnostics to make sure the cooling system is working properly (the cooling system dehumidifies).

5.1.6High Humidity and Low Humidity (Simultaneously)

If these two alarms are displayed at the same time, the humidity input signal is lost. Dashes will be displayed for the humidity reading. The control system will deactivate humidification and dehumidi- fication. Check for a disconnected cable or a failed sensor.

5.1.7High Temperature

If the return air temperature has increased to the High Temperature Alarm setpoint, check for proper setpoints. Is the room load more than the unit can handle (is the unit capacity too small)? Run diag- nostics to make sure all cooling components are operating (compressor and/or valves).

39

Image 47
Contents Liebert Challenger Page Table of Contents Run Diagnostics Component Operation and Maintenance Alarm DescriptionsHumidifier Figures Page Chilled Water Systems System DescriptionsCompressorized Systems Glycool Chilled Glycol Cooling SystemsStart-Up Procedure Advanced microprocessor control panel BasicsAdvanced microprocessor a control for Challenger Main Menu MENU/ESC Status/Alarm DataStatus Display Analog Sensors Setpoints/SetupDefault setpoints and ranges Run Hours LogSetup Operation Setup SystemCalibrate Sensors Show DIP SwitchesSelect Options Alarm Delay seconds Setup AlarmsAlarm default time delays Default TimeHumidity HUM Control Method Standard Custom Alarm MessagesCalibrate Actuator Analog SetupSet Status Display Test Control Board Run DiagnosticsShow Inputs Test OutputsLCD Display Contrast Change PasswordsDate and Time Control Circuit BoardControl output LEDs DIP SwitchesNon-Volatile Memory Control OutputsOperation with Advanced Microprocessor with Graphics Control Advanced microprocessor with graphics control menu See 3.7.7 Set Status Display View/Set AlarmsSetup Alarms View Water Detect Floor Plan for Optional LTM1000/LT750 Setup Custom AlarmsSetup Water Detect Floor Plan View/Set Control Setpoints System SetupCold Start Delay Operating StatusChilled Water/Hot Water/Econ-O-Coil Flush Auto Restart DelayDefault Settings and Ranges IR Flush Overfill infrared humidifiers onlySelect Control Algorithm Chilled Water and SCR Reheats only Calibrate Valve ActuatorSelect Humidity Sensing Mode Run DiagnosticsShow Inputs Modify Plot Scales Setting optionsPlot Graphs View Run Hours Log Analog/Digital InputsLCD Contrast View 24 Hour Run Time HistoryView Total Run Hours Nonvolatile Memory PID Control Chilled Water or SCR Reheats only Temperature ControlCooling/Heating Required, in Percent % Response to Control Types Proportional ControlCooling/dehumidification load status response Glycool CoolingDual Cooling Source Chilled Water CoolingSCR Electric Reheat Requires Special Control Software Humidity ControlHeating Operation Electric Reheat Hot Water ReheatProportional Control Control TypesHumidification Operation System Activation Time between peaks x 5% Short Cycle Control Load Control FeaturesAdditional Features Connecting the Analog SensorsLT750 Environmental Unit Installation-LT750 DIP Switch SettingsFault Water Detection DisplayCalibration SetupPhysical Connections Liebert Monitoring Devices and Software CommunicationsChange Filter Standard AlarmsHigh Head Pressure Custom AlarmsHigh Temperature Compressor OverloadLow Temperature High Temperature and Low Temperature SimultaneouslyHumidifier Problem Infrared Humidifiers Loss of PowerOptional/Custom Alarms System Testing Liebert unit Recommended Liquitect location Floor drain FirestatSmoke Detector Water Detection SensorDistance From Unit Zone leak detection kit installation scenariosFilters Remote ShutdownAir Distribution Blower PackageFan Impellers and Bearings BeltSuperheat Refrigeration SystemSuction Pressure Discharge PressureHot Gas Bypass Valve Operation AdjustmentThermostatic Expansion Valve Operation Air Cooled Condenser Outdoor fan/condenser configurationValve spring guide Water/Glycol Cooled Condensers Coaxial CondenserRegulating Valve Adjusting Collar Nut Glycol Solution MaintenanceMechanical Failure Compressor ReplacementCompressor Functional Check Electrical Failure Compressor Replacement ProcedureRemoving the Pan Cleaning the PanHumidifier Infrared HumidifierSteam Generating Humidifier Autoflush Infrared Humidifier Cleaning SystemAutoflush Operation Autoflush ControlsControls Operation200-460 Replacing the CanisterHumidifier canister part numbers Part Capacity Number Voltage Lbs/hr kg/hrDrain Tempering Feature Circuit Board AdjustmentsSymptom Possible Cause Check or Remedy Blower troubleshootingChilled water troubleshooting Compressor and refrigeration system troubleshooting Compressor and refrigeration system troubleshooting See 6.4.8 Compressor Functional Check and Table Dehumidification troubleshootingGlycol pump troubleshooting Infrared humidifier troubleshootingSteam generating humidifier troubleshooting Reheat troubleshooting Air Cooled Condenser if applicable Filters Steam Generating HumidifierBlower Section CompressorElectrical Panel FiltersWater/Glycol Condenser if applicable Glycol PumpSemiannual Maintenance Inspection Checklist Page That Ne tIti Ti n
Related manuals
Manual 76 pages 48.63 Kb Manual 59 pages 52.87 Kb

3000 specifications

The Liebert 3000 is a cutting-edge power protection solution designed to provide reliable and efficient backup power for critical applications. This uninterruptible power supply (UPS) system is engineered to safeguard sensitive electronic equipment from power disturbances, ensuring uninterrupted operations in data centers, telecommunications, and industrial environments.

One of the standout features of the Liebert 3000 is its high-efficiency design. With an efficiency rating of up to 94%, the system minimizes energy loss, resulting in lower operational costs and a reduced carbon footprint. This is particularly important in today's environmentally conscious climate, as organizations strive to meet sustainability goals while maintaining top-tier performance.

The Liebert 3000 employs advanced technologies to enhance its functionality. It incorporates online double-conversion technology, which provides a continuous supply of clean and regulated power. This technology ensures that connected loads receive stable voltage and frequency, shielding them from voltage spikes, sags, and outages. Additionally, the UPS offers features such as automatic battery testing, which helps ensure peak battery performance and reliability.

Another key characteristic of the Liebert 3000 is its modular design, allowing for flexible scalability. This means that organizations can easily expand the capacity of their UPS system as their power needs grow, without the need for extensive system overhauls. The modular architecture also facilitates simplified maintenance and reduces downtime, as individual modules can be serviced without interrupting power to the critical load.

The system is equipped with comprehensive monitoring and management capabilities. The Liebert 3000 provides real-time data on power usage, battery status, and system performance, enabling facility managers to make informed decisions and proactively address potential issues. The integration of remote management tools allows for seamless monitoring from anywhere, providing peace of mind for operators.

Overall, the Liebert 3000 combines high efficiency, advanced technology, and flexible design to deliver a robust power protection solution. Its reliability and performance make it a preferred choice for organizations seeking to protect their critical infrastructure while enhancing operational efficiency and sustainability. As businesses continue to rely on technology for their everyday operations, the Liebert 3000 stands out as a dependable safeguard against the uncertainties of power quality.