Liebert 3000 manual Run Diagnostics, Select Humidity Sensing Mode

Page 31

Operation with Advanced Microprocessor with Graphics Control

3.7.6Select Humidity Sensing Mode

The user may select between RELATIVE (direct) and ABSOLUTE (predictive) humidity control. If relative is selected, the RH control is taken directly from the RH sensor. If absolute is selected, the RH control is automatically adjusted as the return air temperature deviates from the desired temper- ature setpoint. This results in a predictive humidity control. The display will indicate % RH for both methods of control, but the adjusted humidity reading will be displayed if absolute is selected. With absolute humidity control, the humidity control is automatically adjusted approximately 2% RH for each degree difference between the return air temperature and the temperature setpoint.

With relative humidity control, unnecessary dehumidification can result when overcooling occurs dur- ing a dehumidification cycle. This is because a higher than normal RH reading is caused by overcool- ing the room (about 2% RH for each degree of overcooling). This extends the dehumidification cycle.

Later, when the dehumidification ends and the temperature rises to the setpoint, the RH reading falls. The final RH reading will then be lower than actually desired. If the overcooling was significant enough, the RH could be low enough to activate the humidifier.

If absolute humidity control is selected, over-dehumidification is avoided. When overcooling occurs, causing an increase in the RH reading, the humidity control program “predicts” what the RH will be when the dehumidification cycle ends and temperature returns to the setpoint. This allows the dehu- midification cycle to end at the proper time. The predictive humidity control can reduce energy con- sumption by minimizing compressor and reheat operation, and eliminating unnecessary humidifier operation.

3.7.7Set Status Display

The Status Display can be set to display the return air temperature and humidity SENSOR READ- INGS or the temperature and humidity control SETPOINTS through this selection. When setpoints are selected, the status display indicates so by also displaying “SETPOINTS.” If SENSOR READ- INGS is selected, the Status Display will show the return air sensor readings.

3.7.8Change Passwords

Selecting CHANGE PASSWORDS will prompt the user to select one of the following:

SETPOINT PASSWORD

SETUP PASSWORD

The display prompts you to enter a three digit password when making changes. The system includes two (2) passwords, one for setpoints and one for system setup. The system allows the passwords to be changed by first entering the present password, factory set as “123” for setpoints and “321” for setup. The password function provides system security, so only personnel authorized to make changes should know the passwords. If unauthorized changes are being made, the passwords may be compro- mised and new ones should be selected. The password function can be disabled by setting DIP switch 8 to OFF.

3.8Run Diagnostics

By selecting RUN DIAGNOSTICS, maintenance personnel can check system inputs, outputs, and complete a test of the microcontroller circuit board, all from the front panel. Review of the system inputs and the microcontroller test can be done without interrupting normal operation.

23

Image 31
Contents Liebert Challenger Page Table of Contents Run Diagnostics Component Operation and Maintenance Alarm DescriptionsHumidifier Figures Page Chilled Water Systems System DescriptionsCompressorized Systems Glycool Chilled Glycol Cooling SystemsStart-Up Procedure Advanced microprocessor control panel BasicsAdvanced microprocessor a control for Challenger Status Display Status/Alarm DataMain Menu MENU/ESC Analog Sensors Setpoints/SetupDefault setpoints and ranges Run Hours LogSetup Operation Setup SystemSelect Options Show DIP SwitchesCalibrate Sensors Alarm Delay seconds Setup AlarmsAlarm default time delays Default TimeHumidity HUM Control Method Standard Custom Alarm MessagesSet Status Display Analog SetupCalibrate Actuator Test Control Board Run DiagnosticsShow Inputs Test OutputsLCD Display Contrast Change PasswordsDate and Time Control Circuit BoardControl output LEDs DIP SwitchesNon-Volatile Memory Control OutputsOperation with Advanced Microprocessor with Graphics Control Advanced microprocessor with graphics control menu See 3.7.7 Set Status Display View/Set AlarmsSetup Alarms Setup Water Detect Floor Plan Setup Custom AlarmsView Water Detect Floor Plan for Optional LTM1000/LT750 View/Set Control Setpoints System SetupCold Start Delay Operating StatusChilled Water/Hot Water/Econ-O-Coil Flush Auto Restart DelayDefault Settings and Ranges IR Flush Overfill infrared humidifiers onlySelect Control Algorithm Chilled Water and SCR Reheats only Calibrate Valve ActuatorSelect Humidity Sensing Mode Run DiagnosticsShow Inputs Plot Graphs Setting optionsModify Plot Scales View Run Hours Log Analog/Digital InputsView Total Run Hours View 24 Hour Run Time HistoryLCD Contrast Nonvolatile Memory PID Control Chilled Water or SCR Reheats only Temperature ControlCooling/Heating Required, in Percent % Response to Control Types Proportional ControlCooling/dehumidification load status response Glycool CoolingDual Cooling Source Chilled Water CoolingSCR Electric Reheat Requires Special Control Software Humidity ControlHeating Operation Electric Reheat Hot Water ReheatHumidification Operation System Activation Control TypesProportional Control Time between peaks x 5% Short Cycle Control Load Control FeaturesAdditional Features Connecting the Analog SensorsLT750 Environmental Unit Installation-LT750 DIP Switch SettingsFault Water Detection DisplayPhysical Connections SetupCalibration Liebert Monitoring Devices and Software CommunicationsChange Filter Standard AlarmsHigh Head Pressure Custom AlarmsHigh Temperature Compressor OverloadLow Temperature High Temperature and Low Temperature SimultaneouslyHumidifier Problem Infrared Humidifiers Loss of PowerOptional/Custom Alarms System Testing Liebert unit Recommended Liquitect location Floor drain FirestatSmoke Detector Water Detection SensorDistance From Unit Zone leak detection kit installation scenariosFilters Remote ShutdownAir Distribution Blower PackageFan Impellers and Bearings BeltSuperheat Refrigeration SystemSuction Pressure Discharge PressureThermostatic Expansion Valve Operation AdjustmentHot Gas Bypass Valve Operation Air Cooled Condenser Outdoor fan/condenser configurationRegulating Valve Water/Glycol Cooled Condensers Coaxial CondenserValve spring guide Adjusting Collar Nut Glycol Solution MaintenanceCompressor Functional Check Compressor ReplacementMechanical Failure Electrical Failure Compressor Replacement ProcedureRemoving the Pan Cleaning the PanHumidifier Infrared HumidifierSteam Generating Humidifier Autoflush Infrared Humidifier Cleaning SystemAutoflush Operation Autoflush ControlsControls Operation200-460 Replacing the CanisterHumidifier canister part numbers Part Capacity Number Voltage Lbs/hr kg/hrDrain Tempering Feature Circuit Board AdjustmentsChilled water troubleshooting Blower troubleshootingSymptom Possible Cause Check or Remedy Compressor and refrigeration system troubleshooting Compressor and refrigeration system troubleshooting See 6.4.8 Compressor Functional Check and Table Dehumidification troubleshootingGlycol pump troubleshooting Infrared humidifier troubleshootingSteam generating humidifier troubleshooting Reheat troubleshooting Air Cooled Condenser if applicable Filters Steam Generating HumidifierBlower Section CompressorElectrical Panel FiltersWater/Glycol Condenser if applicable Glycol PumpSemiannual Maintenance Inspection Checklist Page That Ne tIti Ti n
Related manuals
Manual 76 pages 48.63 Kb Manual 59 pages 52.87 Kb

3000 specifications

The Liebert 3000 is a cutting-edge power protection solution designed to provide reliable and efficient backup power for critical applications. This uninterruptible power supply (UPS) system is engineered to safeguard sensitive electronic equipment from power disturbances, ensuring uninterrupted operations in data centers, telecommunications, and industrial environments.

One of the standout features of the Liebert 3000 is its high-efficiency design. With an efficiency rating of up to 94%, the system minimizes energy loss, resulting in lower operational costs and a reduced carbon footprint. This is particularly important in today's environmentally conscious climate, as organizations strive to meet sustainability goals while maintaining top-tier performance.

The Liebert 3000 employs advanced technologies to enhance its functionality. It incorporates online double-conversion technology, which provides a continuous supply of clean and regulated power. This technology ensures that connected loads receive stable voltage and frequency, shielding them from voltage spikes, sags, and outages. Additionally, the UPS offers features such as automatic battery testing, which helps ensure peak battery performance and reliability.

Another key characteristic of the Liebert 3000 is its modular design, allowing for flexible scalability. This means that organizations can easily expand the capacity of their UPS system as their power needs grow, without the need for extensive system overhauls. The modular architecture also facilitates simplified maintenance and reduces downtime, as individual modules can be serviced without interrupting power to the critical load.

The system is equipped with comprehensive monitoring and management capabilities. The Liebert 3000 provides real-time data on power usage, battery status, and system performance, enabling facility managers to make informed decisions and proactively address potential issues. The integration of remote management tools allows for seamless monitoring from anywhere, providing peace of mind for operators.

Overall, the Liebert 3000 combines high efficiency, advanced technology, and flexible design to deliver a robust power protection solution. Its reliability and performance make it a preferred choice for organizations seeking to protect their critical infrastructure while enhancing operational efficiency and sustainability. As businesses continue to rely on technology for their everyday operations, the Liebert 3000 stands out as a dependable safeguard against the uncertainties of power quality.