Liebert 3000 manual Select Control Type, Setup Alarms, Alarm default time delays, Default Time

Page 17

Operation with Advanced Microprocessor Controls

Select Control Type

Intelligent (Chilled Water only)

Proportional (all unit types)

Tunable PID (Chilled Water or SCR Reheats only)

The type of system control method used by the microprocessor can be selected from the front panel. The default setting is Intelligent, which approximates the actions that a human operator would take to maintain precise, stable control. The control logic uses Artificial Intelligence techniques including “fuzzy logic” and “expert systems” methods to maintain precise, stable control and increase reliability by reducing component cycles. Proportional is a standard control method that uses one gain factor (temperature sensitivity adjustment). Tunable PID (Proportional, Integral, and Derivative) uses three gain factors selected by the operator. PID allows precision tuning, but requires an experienced operator and seasonal adjustments. Note that if PID is selected, it is used for temperature control while humidity will continue to use Proportional control. Refer to 4.0 - System Performance with Advanced Microprocessor Controls for more detail on types of controls.

Setup Alarms

Selecting SETUP ALARMS will step to the following menu:

SET TIME DELAYS

ENABLE ALARMS

ENABLE COMMON ALARM

SET CUSTOM ALARMS

Each individual alarm can be programmed with a time delay from 0 to 255 seconds. Each individual alarm can be ENABLED or DISABLED and each individual alarm can be programmed to energize or not to energize the Common Alarm Relay.

Set Time Delays—By programming a time delay for an alarm, the system will delay the specified amount of time before recognizing the alarm. The alarm condition must be present for the amount of time programmed for that alarm before it will be annunciated. If the alarm condition goes away before the time delay has timed out, the alarm will not be recognized and the time delay timer will be reset. For software alarms such as Loss of Power, Short Cycle, and Low Suction Pressure, a time delay will only delay the annunciation of that alarm. The condition of the alarm is not applicable because the condition has already occurred. For these alarms the time delay should be left at the fac- tory default of 0. Table 5, below, shows the default time delays for each alarm.

Table 5

Alarm default time delays

 

 

Default Time

 

Alarm

Delay (seconds)

Humidifier Problem

2

High Head Pressure

2

Change Filter

2

Loss of Air flow

3

Custom Alarm #1

0

Custom Alarm #2

0

Custom Alarm #3

0

Custom Alarm #4

6

High Temperature

30

Low Temperature

30

High Humidity

30

Low Humidity

30

Low Suction Pressure

0

Short Cycle

0

Compressor Overload

2

Main Fan Overload

5

Loss of Power

0

9

Image 17
Contents Liebert Challenger Page Table of Contents Run Diagnostics Component Operation and Maintenance Alarm DescriptionsHumidifier Figures Page Compressorized Systems System DescriptionsGlycool Chilled Glycol Cooling Systems Chilled Water SystemsStart-Up Procedure Advanced microprocessor control panel BasicsAdvanced microprocessor a control for Challenger Main Menu MENU/ESC Status/Alarm DataStatus Display Default setpoints and ranges Setpoints/SetupRun Hours Log Analog SensorsSetup Operation Setup SystemCalibrate Sensors Show DIP SwitchesSelect Options Alarm default time delays Setup AlarmsDefault Time Alarm Delay secondsHumidity HUM Control Method Standard Custom Alarm MessagesCalibrate Actuator Analog SetupSet Status Display Show Inputs Run DiagnosticsTest Outputs Test Control BoardDate and Time Change PasswordsControl Circuit Board LCD Display ContrastNon-Volatile Memory DIP SwitchesControl Outputs Control output LEDsOperation with Advanced Microprocessor with Graphics Control Advanced microprocessor with graphics control menu See 3.7.7 Set Status Display View/Set AlarmsSetup Alarms View Water Detect Floor Plan for Optional LTM1000/LT750 Setup Custom AlarmsSetup Water Detect Floor Plan Cold Start Delay System SetupOperating Status View/Set Control SetpointsDefault Settings and Ranges Auto Restart DelayIR Flush Overfill infrared humidifiers only Chilled Water/Hot Water/Econ-O-Coil FlushSelect Control Algorithm Chilled Water and SCR Reheats only Calibrate Valve ActuatorSelect Humidity Sensing Mode Run DiagnosticsShow Inputs Modify Plot Scales Setting optionsPlot Graphs View Run Hours Log Analog/Digital InputsLCD Contrast View 24 Hour Run Time HistoryView Total Run Hours Nonvolatile Memory Cooling/Heating Required, in Percent % Temperature ControlResponse to Control Types Proportional Control PID Control Chilled Water or SCR Reheats onlyDual Cooling Source Glycool CoolingChilled Water Cooling Cooling/dehumidification load status responseHeating Operation Electric Reheat Humidity ControlHot Water Reheat SCR Electric Reheat Requires Special Control SoftwareProportional Control Control TypesHumidification Operation System Activation Time between peaks x 5% Additional Features Load Control FeaturesConnecting the Analog Sensors Short Cycle ControlFault Installation-LT750 DIP Switch SettingsWater Detection Display LT750 Environmental UnitCalibration SetupPhysical Connections Liebert Monitoring Devices and Software CommunicationsChange Filter Standard AlarmsHigh Temperature Custom AlarmsCompressor Overload High Head PressureHumidifier Problem Infrared Humidifiers High Temperature and Low Temperature SimultaneouslyLoss of Power Low TemperatureOptional/Custom Alarms System Testing Smoke Detector FirestatWater Detection Sensor Liebert unit Recommended Liquitect location Floor drainFilters Zone leak detection kit installation scenariosRemote Shutdown Distance From UnitFan Impellers and Bearings Blower PackageBelt Air DistributionSuction Pressure Refrigeration SystemDischarge Pressure SuperheatHot Gas Bypass Valve Operation AdjustmentThermostatic Expansion Valve Operation Air Cooled Condenser Outdoor fan/condenser configurationValve spring guide Water/Glycol Cooled Condensers Coaxial CondenserRegulating Valve Adjusting Collar Nut Glycol Solution MaintenanceMechanical Failure Compressor ReplacementCompressor Functional Check Electrical Failure Compressor Replacement ProcedureHumidifier Cleaning the PanInfrared Humidifier Removing the PanAutoflush Operation Autoflush Infrared Humidifier Cleaning SystemAutoflush Controls Steam Generating HumidifierControls OperationHumidifier canister part numbers Replacing the CanisterPart Capacity Number Voltage Lbs/hr kg/hr 200-460Drain Tempering Feature Circuit Board AdjustmentsSymptom Possible Cause Check or Remedy Blower troubleshootingChilled water troubleshooting Compressor and refrigeration system troubleshooting Compressor and refrigeration system troubleshooting Glycol pump troubleshooting Dehumidification troubleshootingInfrared humidifier troubleshooting See 6.4.8 Compressor Functional Check and TableSteam generating humidifier troubleshooting Reheat troubleshooting Blower Section Filters Steam Generating HumidifierCompressor Air Cooled Condenser if applicableWater/Glycol Condenser if applicable FiltersGlycol Pump Electrical PanelSemiannual Maintenance Inspection Checklist Page Iti Ne tTi n That
Related manuals
Manual 76 pages 48.63 Kb Manual 59 pages 52.87 Kb

3000 specifications

The Liebert 3000 is a cutting-edge power protection solution designed to provide reliable and efficient backup power for critical applications. This uninterruptible power supply (UPS) system is engineered to safeguard sensitive electronic equipment from power disturbances, ensuring uninterrupted operations in data centers, telecommunications, and industrial environments.

One of the standout features of the Liebert 3000 is its high-efficiency design. With an efficiency rating of up to 94%, the system minimizes energy loss, resulting in lower operational costs and a reduced carbon footprint. This is particularly important in today's environmentally conscious climate, as organizations strive to meet sustainability goals while maintaining top-tier performance.

The Liebert 3000 employs advanced technologies to enhance its functionality. It incorporates online double-conversion technology, which provides a continuous supply of clean and regulated power. This technology ensures that connected loads receive stable voltage and frequency, shielding them from voltage spikes, sags, and outages. Additionally, the UPS offers features such as automatic battery testing, which helps ensure peak battery performance and reliability.

Another key characteristic of the Liebert 3000 is its modular design, allowing for flexible scalability. This means that organizations can easily expand the capacity of their UPS system as their power needs grow, without the need for extensive system overhauls. The modular architecture also facilitates simplified maintenance and reduces downtime, as individual modules can be serviced without interrupting power to the critical load.

The system is equipped with comprehensive monitoring and management capabilities. The Liebert 3000 provides real-time data on power usage, battery status, and system performance, enabling facility managers to make informed decisions and proactively address potential issues. The integration of remote management tools allows for seamless monitoring from anywhere, providing peace of mind for operators.

Overall, the Liebert 3000 combines high efficiency, advanced technology, and flexible design to deliver a robust power protection solution. Its reliability and performance make it a preferred choice for organizations seeking to protect their critical infrastructure while enhancing operational efficiency and sustainability. As businesses continue to rely on technology for their everyday operations, the Liebert 3000 stands out as a dependable safeguard against the uncertainties of power quality.