Liebert 3000 manual Steam generating humidifier troubleshooting

Page 70

 

 

Troubleshooting

Table 27 Steam generating humidifier troubleshooting

 

 

 

Symptom

Possible Cause

Check or Remedy

 

 

 

 

 

Check drain valve to ensure that it drains freely. Check and

 

 

replace if defective.

 

Foaming

 

False canister full indication

Check water supply. If commercially softened, reconnect to

 

 

raw water supply. If connected to hot water reconnect to

 

 

cold water.

Main 24 VAC fuse or circuit

Shorts or loose connections

Check the wiring connections of the 24 VAC circuit.

breaker trips

Faulty circuit board

Replace the circuit board.

 

 

 

Main fuses blow

Faulty solenoid

Check for magnetic field at coil.

approximately 15 seconds

Conductivity too high

Check amp draw of humidifier on startup. If it exceeds rated

after unit is activated

amps, increase setting of the % pot on the circuit board

 

 

 

 

Mineral deposits obstruct

Check drain valve for obstructions and clean if necessary.

Main fuses blow when

drain valve

 

drain valve is activated.

Faulty solenoid

Check for magnetic field at coil.

 

 

 

 

Faulty circuit board

Replace circuit board.

 

 

 

 

 

Verify that RUN/DRAIN switch is in the RUN position.

 

 

 

Unit ON, humidifier will not

Humidifier not receiving power

Check fuses or CBs and replace or reset if necessary.

operate

 

 

Make sure molex connector is securely plugged into circuit

 

 

 

 

board and that no wires are loose.

 

 

 

 

No water available to unit

Check external shut-off valves.

 

 

 

Contactor pulled in, but no

Clogged fill line strainer

Clean or replace fill line strainer.

 

 

Wiring breaks or loose

 

water enters canister

Check for faulty wiring and loose connections.

 

connections

 

 

Faulty circuit board

Replace circuit board.

 

 

 

 

Foaming

Check drain valve and water supply.

 

 

 

 

 

Check connection on component plate in humidifier cabinet.

 

 

Terminal #1 on the square block interface device must be

 

 

connected to L2 of the power terminal block. L2 must also

 

 

be connected to the electrode closest to the steam outlet

 

Canister interface connections

port.

 

incorrect

Verify that the red wire from terminal #2 on the interface

 

 

Water enters canister, but

 

connects to the red top terminal on the canister. This is the

canister full circuit activates

 

one farthest from the steam outlet port and is the high water

at a low water level

 

sensor probe.

 

 

Remove red canister full wire from canister. If normal

 

Full isolation has broken down

operation resumes, canister must be replaced. Remove the

 

wire from terminal #3 on the interface. If normal operation

 

 

 

 

resumes, canister full interface must be replaced.

 

 

 

 

Drain assembly not operating

Check and replace coil or valve if necessary.

 

freely

 

 

 

Faulty circuit board

Replace circuit board

 

 

 

Canister fills but overflows

Canister full circuit does not

Check wiring of canister full interface. Replace circuit board.

activate

 

 

62

Image 70
Contents Liebert Challenger Page Table of Contents Run Diagnostics Alarm Descriptions Component Operation and MaintenanceHumidifier Figures Page Glycool Chilled Glycol Cooling Systems System DescriptionsCompressorized Systems Chilled Water SystemsStart-Up Procedure Basics Advanced microprocessor control panelAdvanced microprocessor a control for Challenger Status Display Status/Alarm DataMain Menu MENU/ESC Run Hours Log Setpoints/SetupDefault setpoints and ranges Analog SensorsSetup System Setup OperationSelect Options Show DIP SwitchesCalibrate Sensors Default Time Setup AlarmsAlarm default time delays Alarm Delay secondsStandard Custom Alarm Messages Humidity HUM Control MethodSet Status Display Analog SetupCalibrate Actuator Test Outputs Run DiagnosticsShow Inputs Test Control BoardControl Circuit Board Change PasswordsDate and Time LCD Display ContrastControl Outputs DIP SwitchesNon-Volatile Memory Control output LEDsOperation with Advanced Microprocessor with Graphics Control Advanced microprocessor with graphics control menu View/Set Alarms See 3.7.7 Set Status DisplaySetup Alarms Setup Water Detect Floor Plan Setup Custom AlarmsView Water Detect Floor Plan for Optional LTM1000/LT750 Operating Status System SetupCold Start Delay View/Set Control SetpointsIR Flush Overfill infrared humidifiers only Auto Restart DelayDefault Settings and Ranges Chilled Water/Hot Water/Econ-O-Coil FlushCalibrate Valve Actuator Select Control Algorithm Chilled Water and SCR Reheats onlyRun Diagnostics Select Humidity Sensing ModeShow Inputs Plot Graphs Setting optionsModify Plot Scales Analog/Digital Inputs View Run Hours LogView Total Run Hours View 24 Hour Run Time HistoryLCD Contrast Nonvolatile Memory Response to Control Types Proportional Control Temperature ControlCooling/Heating Required, in Percent % PID Control Chilled Water or SCR Reheats onlyChilled Water Cooling Glycool CoolingDual Cooling Source Cooling/dehumidification load status responseHot Water Reheat Humidity ControlHeating Operation Electric Reheat SCR Electric Reheat Requires Special Control SoftwareHumidification Operation System Activation Control TypesProportional Control Time between peaks x 5% Connecting the Analog Sensors Load Control FeaturesAdditional Features Short Cycle ControlWater Detection Display Installation-LT750 DIP Switch SettingsFault LT750 Environmental UnitPhysical Connections SetupCalibration Communications Liebert Monitoring Devices and SoftwareStandard Alarms Change FilterCompressor Overload Custom AlarmsHigh Temperature High Head PressureLoss of Power High Temperature and Low Temperature SimultaneouslyHumidifier Problem Infrared Humidifiers Low TemperatureOptional/Custom Alarms System Testing Water Detection Sensor FirestatSmoke Detector Liebert unit Recommended Liquitect location Floor drainRemote Shutdown Zone leak detection kit installation scenariosFilters Distance From UnitBelt Blower PackageFan Impellers and Bearings Air DistributionDischarge Pressure Refrigeration SystemSuction Pressure SuperheatThermostatic Expansion Valve Operation AdjustmentHot Gas Bypass Valve Operation Outdoor fan/condenser configuration Air Cooled CondenserRegulating Valve Water/Glycol Cooled Condensers Coaxial CondenserValve spring guide Glycol Solution Maintenance Adjusting Collar NutCompressor Functional Check Compressor ReplacementMechanical Failure Compressor Replacement Procedure Electrical FailureInfrared Humidifier Cleaning the PanHumidifier Removing the PanAutoflush Controls Autoflush Infrared Humidifier Cleaning SystemAutoflush Operation Steam Generating HumidifierOperation ControlsPart Capacity Number Voltage Lbs/hr kg/hr Replacing the CanisterHumidifier canister part numbers 200-460Circuit Board Adjustments Drain Tempering FeatureChilled water troubleshooting Blower troubleshootingSymptom Possible Cause Check or Remedy Compressor and refrigeration system troubleshooting Compressor and refrigeration system troubleshooting Infrared humidifier troubleshooting Dehumidification troubleshootingGlycol pump troubleshooting See 6.4.8 Compressor Functional Check and TableSteam generating humidifier troubleshooting Reheat troubleshooting Compressor Filters Steam Generating HumidifierBlower Section Air Cooled Condenser if applicableGlycol Pump FiltersWater/Glycol Condenser if applicable Electrical PanelSemiannual Maintenance Inspection Checklist Page Ti n Ne tIti That
Related manuals
Manual 76 pages 48.63 Kb Manual 59 pages 52.87 Kb

3000 specifications

The Liebert 3000 is a cutting-edge power protection solution designed to provide reliable and efficient backup power for critical applications. This uninterruptible power supply (UPS) system is engineered to safeguard sensitive electronic equipment from power disturbances, ensuring uninterrupted operations in data centers, telecommunications, and industrial environments.

One of the standout features of the Liebert 3000 is its high-efficiency design. With an efficiency rating of up to 94%, the system minimizes energy loss, resulting in lower operational costs and a reduced carbon footprint. This is particularly important in today's environmentally conscious climate, as organizations strive to meet sustainability goals while maintaining top-tier performance.

The Liebert 3000 employs advanced technologies to enhance its functionality. It incorporates online double-conversion technology, which provides a continuous supply of clean and regulated power. This technology ensures that connected loads receive stable voltage and frequency, shielding them from voltage spikes, sags, and outages. Additionally, the UPS offers features such as automatic battery testing, which helps ensure peak battery performance and reliability.

Another key characteristic of the Liebert 3000 is its modular design, allowing for flexible scalability. This means that organizations can easily expand the capacity of their UPS system as their power needs grow, without the need for extensive system overhauls. The modular architecture also facilitates simplified maintenance and reduces downtime, as individual modules can be serviced without interrupting power to the critical load.

The system is equipped with comprehensive monitoring and management capabilities. The Liebert 3000 provides real-time data on power usage, battery status, and system performance, enabling facility managers to make informed decisions and proactively address potential issues. The integration of remote management tools allows for seamless monitoring from anywhere, providing peace of mind for operators.

Overall, the Liebert 3000 combines high efficiency, advanced technology, and flexible design to deliver a robust power protection solution. Its reliability and performance make it a preferred choice for organizations seeking to protect their critical infrastructure while enhancing operational efficiency and sustainability. As businesses continue to rely on technology for their everyday operations, the Liebert 3000 stands out as a dependable safeguard against the uncertainties of power quality.