Component Operation and Maintenance

6.4.8Compressor Functional Check

The following diagnostic procedure should be used to evaluate whether the compressor is working properly.

1.Proper voltage to the unit should be verified.

2.The normal checks of motor winding continuity and short to ground should be made to determine if the inherent overload motor protector has opened or if an internal motor short or ground fault has developed. If the protector has opened, the compressor must be allowed to cool sufficiently to allow it to reset.

3.Proper indoor and outdoor blower/fan operation should be verified. Condenser glycol flow should be verified.

4.With service gauges connected to suction and discharge pressure fittings, turn on the compressor. If suction pressure falls below normal levels, the system is either low on charge or there is a flow blockage in the system.

5.If suction pressure does not drop and discharge pressure does not rise to normal levels, reverse any two of the compressor power leads and reapply power to make sure compressor was not wired to run in reverse direction. If pressures still do not move to normal values, system is properly charged and solenoid valves function, the compressor is faulty. Reconnect the compressor leads as originally configured and use normal diagnostic procedures to check operation of the reversing valve.

6.To test if the compressor is pumping properly, the compressor current draw must be compared to published compressor performance curves using the operating pressures and voltage of the system. If the measured average current deviates more than ±15% from published values, a faulty compressor may be indicated. A current imbalance exceeding 15% of the average on the three phases should be investigated further.

7.Before replacing or returning a compressor: Be certain that the compressor is actually defective. At a minimum, recheck a compressor returned from the field in the shop or depot for Hipot, winding resistance and ability to start before returning. More than one-third of compressors returned for warranty analysis are determined to have nothing wrong. They were misdiagnosed in the field as being defective. Replacing working compressors unnecessarily costs everyone.

6.4.9Compressor Replacement

Infrequently a fault in the motor insulation may result in a motor burn, but burnouts rarely occur in a properly installed system. Of those that do, most are the effects of mechanical or lubrication fail- ures, resulting in the burnout as a secondary consequence.

If problems that can cause compressor failures are detected and corrected early, a large percentage can be prevented. Periodic maintenance inspections by alert service personnel on the lookout for abnormal operation can be a major factor in reducing maintenance costs. It is easier and far less costly to take the steps necessary to ensure proper system operation than it is to allow a compressor to fail and require replacement.

When troubleshooting a compressor, check all electrical components for proper operation.

1.Check all fuses and circuit breakers.

2.Check Hi-Lo Pressure switch operation.

3.If a compressor failure has occurred, determine whether it is an electrical or mechanical failure.

Mechanical Failure

A mechanical compressor failure will be not be indicated by a burned odor. The motor will attempt to run. If you have determined that a mechanical failure has occurred, the compressor must be replaced.

If a burnout does occur, correct the problem that caused the burnout and clean the system. It is important to note that successive burnouts of the same system are usually caused by improper clean- ing.

51

Image 59
Contents Liebert Challenger Page Table of Contents Run Diagnostics Component Operation and Maintenance Alarm DescriptionsHumidifier Figures Page Chilled Water Systems System DescriptionsCompressorized Systems Glycool Chilled Glycol Cooling SystemsStart-Up Procedure Advanced microprocessor control panel BasicsAdvanced microprocessor a control for Challenger Main Menu MENU/ESC Status/Alarm DataStatus Display Analog Sensors Setpoints/SetupDefault setpoints and ranges Run Hours LogSetup Operation Setup SystemCalibrate Sensors Show DIP SwitchesSelect Options Alarm Delay seconds Setup AlarmsAlarm default time delays Default TimeHumidity HUM Control Method Standard Custom Alarm MessagesCalibrate Actuator Analog SetupSet Status Display Test Control Board Run DiagnosticsShow Inputs Test OutputsLCD Display Contrast Change PasswordsDate and Time Control Circuit BoardControl output LEDs DIP SwitchesNon-Volatile Memory Control OutputsOperation with Advanced Microprocessor with Graphics Control Advanced microprocessor with graphics control menu See 3.7.7 Set Status Display View/Set AlarmsSetup Alarms View Water Detect Floor Plan for Optional LTM1000/LT750 Setup Custom AlarmsSetup Water Detect Floor Plan View/Set Control Setpoints System SetupCold Start Delay Operating StatusChilled Water/Hot Water/Econ-O-Coil Flush Auto Restart DelayDefault Settings and Ranges IR Flush Overfill infrared humidifiers onlySelect Control Algorithm Chilled Water and SCR Reheats only Calibrate Valve ActuatorSelect Humidity Sensing Mode Run DiagnosticsShow Inputs Modify Plot Scales Setting optionsPlot Graphs View Run Hours Log Analog/Digital InputsLCD Contrast View 24 Hour Run Time HistoryView Total Run Hours Nonvolatile Memory PID Control Chilled Water or SCR Reheats only Temperature ControlCooling/Heating Required, in Percent % Response to Control Types Proportional ControlCooling/dehumidification load status response Glycool CoolingDual Cooling Source Chilled Water CoolingSCR Electric Reheat Requires Special Control Software Humidity ControlHeating Operation Electric Reheat Hot Water ReheatProportional Control Control TypesHumidification Operation System Activation Time between peaks x 5% Short Cycle Control Load Control FeaturesAdditional Features Connecting the Analog SensorsLT750 Environmental Unit Installation-LT750 DIP Switch SettingsFault Water Detection DisplayCalibration SetupPhysical Connections Liebert Monitoring Devices and Software CommunicationsChange Filter Standard AlarmsHigh Head Pressure Custom AlarmsHigh Temperature Compressor OverloadLow Temperature High Temperature and Low Temperature SimultaneouslyHumidifier Problem Infrared Humidifiers Loss of PowerOptional/Custom Alarms System Testing Liebert unit Recommended Liquitect location Floor drain FirestatSmoke Detector Water Detection SensorDistance From Unit Zone leak detection kit installation scenariosFilters Remote ShutdownAir Distribution Blower PackageFan Impellers and Bearings BeltSuperheat Refrigeration SystemSuction Pressure Discharge PressureHot Gas Bypass Valve Operation AdjustmentThermostatic Expansion Valve Operation Air Cooled Condenser Outdoor fan/condenser configurationValve spring guide Water/Glycol Cooled Condensers Coaxial CondenserRegulating Valve Adjusting Collar Nut Glycol Solution MaintenanceMechanical Failure Compressor ReplacementCompressor Functional Check Electrical Failure Compressor Replacement ProcedureRemoving the Pan Cleaning the PanHumidifier Infrared HumidifierSteam Generating Humidifier Autoflush Infrared Humidifier Cleaning SystemAutoflush Operation Autoflush ControlsControls Operation200-460 Replacing the CanisterHumidifier canister part numbers Part Capacity Number Voltage Lbs/hr kg/hrDrain Tempering Feature Circuit Board AdjustmentsSymptom Possible Cause Check or Remedy Blower troubleshootingChilled water troubleshooting Compressor and refrigeration system troubleshooting Compressor and refrigeration system troubleshooting See 6.4.8 Compressor Functional Check and Table Dehumidification troubleshootingGlycol pump troubleshooting Infrared humidifier troubleshootingSteam generating humidifier troubleshooting Reheat troubleshooting Air Cooled Condenser if applicable Filters Steam Generating HumidifierBlower Section CompressorElectrical Panel FiltersWater/Glycol Condenser if applicable Glycol PumpSemiannual Maintenance Inspection Checklist Page That Ne tIti Ti n
Related manuals
Manual 76 pages 48.63 Kb Manual 59 pages 52.87 Kb

3000 specifications

The Liebert 3000 is a cutting-edge power protection solution designed to provide reliable and efficient backup power for critical applications. This uninterruptible power supply (UPS) system is engineered to safeguard sensitive electronic equipment from power disturbances, ensuring uninterrupted operations in data centers, telecommunications, and industrial environments.

One of the standout features of the Liebert 3000 is its high-efficiency design. With an efficiency rating of up to 94%, the system minimizes energy loss, resulting in lower operational costs and a reduced carbon footprint. This is particularly important in today's environmentally conscious climate, as organizations strive to meet sustainability goals while maintaining top-tier performance.

The Liebert 3000 employs advanced technologies to enhance its functionality. It incorporates online double-conversion technology, which provides a continuous supply of clean and regulated power. This technology ensures that connected loads receive stable voltage and frequency, shielding them from voltage spikes, sags, and outages. Additionally, the UPS offers features such as automatic battery testing, which helps ensure peak battery performance and reliability.

Another key characteristic of the Liebert 3000 is its modular design, allowing for flexible scalability. This means that organizations can easily expand the capacity of their UPS system as their power needs grow, without the need for extensive system overhauls. The modular architecture also facilitates simplified maintenance and reduces downtime, as individual modules can be serviced without interrupting power to the critical load.

The system is equipped with comprehensive monitoring and management capabilities. The Liebert 3000 provides real-time data on power usage, battery status, and system performance, enabling facility managers to make informed decisions and proactively address potential issues. The integration of remote management tools allows for seamless monitoring from anywhere, providing peace of mind for operators.

Overall, the Liebert 3000 combines high efficiency, advanced technology, and flexible design to deliver a robust power protection solution. Its reliability and performance make it a preferred choice for organizations seeking to protect their critical infrastructure while enhancing operational efficiency and sustainability. As businesses continue to rely on technology for their everyday operations, the Liebert 3000 stands out as a dependable safeguard against the uncertainties of power quality.