Liebert 3000 manual Humidity HUM Control Method, Standard Custom Alarm Messages

Page 18

Operation with Advanced Microprocessor Controls

Enable Alarms—Each individual alarm can be selected to be ENABLED (annunciated audibly, visu- ally, and communicated to a Site Products System) or DISABLED (ignored).

Enable Common Alarm—Each individual alarm can be selected to energize or to not energize the common alarm relay. If the energize common alarm function is set to YES, the relay is energized immediately as the alarm is annunciated and de-energized when the alarm condition goes away (only after the alarm has been recognized). If the function is set to NO, the alarm has no effect on the com- mon alarm relay regardless of whether the alarm is ENABLED or DISABLED.

Set Custom Alarms—The custom alarm messages can be from a list of standard alarm messages or you can write your own message.

NOTE

A maximum of two of the alarm messages can be your own message.

They can be in any location(s) 1 through 4. The text for custom alarms can be changed at any time by selecting “SET CUSTOM ALARMS.” To change the text for a custom alarm, select “SELECT ALARM.” Then, select the alarm you would like to change, 1 through 4. Using the UP/DOWN arrows will step through the list of five standard alarm messages (see list below) and the two custom alarms.

NOTE

The two custom alarm messages will be shown with what was previously programmed in them and can be changed.

Press ENTER to make your selection. To modify the two custom alarm messages, go back one screen and select “CHANGE CUSTOM TXT 1” (or 2). Text can be up to 20 characters in length and can be any of the following characters (or a blank space):

ABCDEFGHIJKLMNOPQRSTUVWXYZ#%*-0123456789.

Standard Custom Alarm Messages

WATER UNDER FLOOR

SMOKE DETECTED

STANDBY GC PUMP ON

LOSS OF WATER FLOW

STANDBY UNIT ON

For more information concerning alarms, see 5.0 - Alarm Descriptions.

Humidity (HUM) Control Method

The user may select between relative (direct) and absolute (predictive) humidity control. If relative is selected, the RH control is taken directly from the RH sensor. If absolute is selected, the RH control is automatically adjusted as the return air temperature deviates from the desired temperature setpoint. This results in a predictive humidity control. The display will indicate % RH for both methods of con- trol, but the adjusted humidity reading will be displayed if absolute is selected. With absolute humid- ity control, the humidity control is automatically adjusted approximately 2% RH for each degree difference between the return air temperature and the temperature setpoint.

With relative humidity control, unnecessary dehumidification can result when overcooling occurs dur- ing a dehumidification cycle. This is because a higher than normal RH reading is caused by overcool- ing the room (about 2% RH for each degree of overcooling). This extends the dehumidification cycle.

Later, when the dehumidification ends and the temperature rises to the setpoint, the RH reading falls. The final RH reading will then be lower than actually desired. If the overcooling was significant enough, the RH could be low enough to activate the humidifier.

If absolute humidity control is selected, over-dehumidification is avoided. When overcooling occurs, causing an increase in the RH reading, the humidity control program “predicts” what the RH will be when the dehumidification cycle ends and temperature returns to the setpoint. This allows the dehu- midification cycle to end at the proper time. The predictive humidity control can reduce energy con- sumption by minimizing compressor and reheat operation, and eliminating unnecessary humidifier operation.

10

Image 18
Contents Liebert Challenger Page Table of Contents Run Diagnostics Alarm Descriptions Component Operation and MaintenanceHumidifier Figures Page Glycool Chilled Glycol Cooling Systems System DescriptionsCompressorized Systems Chilled Water SystemsStart-Up Procedure Basics Advanced microprocessor control panelAdvanced microprocessor a control for Challenger Status/Alarm Data Status DisplayMain Menu MENU/ESC Run Hours Log Setpoints/SetupDefault setpoints and ranges Analog SensorsSetup System Setup OperationShow DIP Switches Select OptionsCalibrate Sensors Default Time Setup AlarmsAlarm default time delays Alarm Delay secondsStandard Custom Alarm Messages Humidity HUM Control MethodAnalog Setup Set Status DisplayCalibrate Actuator Test Outputs Run DiagnosticsShow Inputs Test Control BoardControl Circuit Board Change PasswordsDate and Time LCD Display ContrastControl Outputs DIP SwitchesNon-Volatile Memory Control output LEDsOperation with Advanced Microprocessor with Graphics Control Advanced microprocessor with graphics control menu View/Set Alarms See 3.7.7 Set Status DisplaySetup Alarms Setup Custom Alarms Setup Water Detect Floor PlanView Water Detect Floor Plan for Optional LTM1000/LT750 Operating Status System SetupCold Start Delay View/Set Control SetpointsIR Flush Overfill infrared humidifiers only Auto Restart DelayDefault Settings and Ranges Chilled Water/Hot Water/Econ-O-Coil FlushCalibrate Valve Actuator Select Control Algorithm Chilled Water and SCR Reheats onlyRun Diagnostics Select Humidity Sensing ModeShow Inputs Setting options Plot GraphsModify Plot Scales Analog/Digital Inputs View Run Hours LogView 24 Hour Run Time History View Total Run HoursLCD Contrast Nonvolatile Memory Response to Control Types Proportional Control Temperature ControlCooling/Heating Required, in Percent % PID Control Chilled Water or SCR Reheats onlyChilled Water Cooling Glycool CoolingDual Cooling Source Cooling/dehumidification load status responseHot Water Reheat Humidity ControlHeating Operation Electric Reheat SCR Electric Reheat Requires Special Control SoftwareControl Types Humidification Operation System ActivationProportional Control Time between peaks x 5% Connecting the Analog Sensors Load Control FeaturesAdditional Features Short Cycle ControlWater Detection Display Installation-LT750 DIP Switch SettingsFault LT750 Environmental UnitSetup Physical ConnectionsCalibration Communications Liebert Monitoring Devices and SoftwareStandard Alarms Change FilterCompressor Overload Custom AlarmsHigh Temperature High Head PressureLoss of Power High Temperature and Low Temperature SimultaneouslyHumidifier Problem Infrared Humidifiers Low TemperatureOptional/Custom Alarms System Testing Water Detection Sensor FirestatSmoke Detector Liebert unit Recommended Liquitect location Floor drainRemote Shutdown Zone leak detection kit installation scenariosFilters Distance From UnitBelt Blower PackageFan Impellers and Bearings Air DistributionDischarge Pressure Refrigeration SystemSuction Pressure SuperheatAdjustment Thermostatic Expansion Valve OperationHot Gas Bypass Valve Operation Outdoor fan/condenser configuration Air Cooled CondenserWater/Glycol Cooled Condensers Coaxial Condenser Regulating ValveValve spring guide Glycol Solution Maintenance Adjusting Collar NutCompressor Replacement Compressor Functional CheckMechanical Failure Compressor Replacement Procedure Electrical FailureInfrared Humidifier Cleaning the PanHumidifier Removing the PanAutoflush Controls Autoflush Infrared Humidifier Cleaning SystemAutoflush Operation Steam Generating HumidifierOperation ControlsPart Capacity Number Voltage Lbs/hr kg/hr Replacing the CanisterHumidifier canister part numbers 200-460Circuit Board Adjustments Drain Tempering FeatureBlower troubleshooting Chilled water troubleshootingSymptom Possible Cause Check or Remedy Compressor and refrigeration system troubleshooting Compressor and refrigeration system troubleshooting Infrared humidifier troubleshooting Dehumidification troubleshootingGlycol pump troubleshooting See 6.4.8 Compressor Functional Check and TableSteam generating humidifier troubleshooting Reheat troubleshooting Compressor Filters Steam Generating HumidifierBlower Section Air Cooled Condenser if applicableGlycol Pump FiltersWater/Glycol Condenser if applicable Electrical PanelSemiannual Maintenance Inspection Checklist Page Ti n Ne tIti That
Related manuals
Manual 76 pages 48.63 Kb Manual 59 pages 52.87 Kb

3000 specifications

The Liebert 3000 is a cutting-edge power protection solution designed to provide reliable and efficient backup power for critical applications. This uninterruptible power supply (UPS) system is engineered to safeguard sensitive electronic equipment from power disturbances, ensuring uninterrupted operations in data centers, telecommunications, and industrial environments.

One of the standout features of the Liebert 3000 is its high-efficiency design. With an efficiency rating of up to 94%, the system minimizes energy loss, resulting in lower operational costs and a reduced carbon footprint. This is particularly important in today's environmentally conscious climate, as organizations strive to meet sustainability goals while maintaining top-tier performance.

The Liebert 3000 employs advanced technologies to enhance its functionality. It incorporates online double-conversion technology, which provides a continuous supply of clean and regulated power. This technology ensures that connected loads receive stable voltage and frequency, shielding them from voltage spikes, sags, and outages. Additionally, the UPS offers features such as automatic battery testing, which helps ensure peak battery performance and reliability.

Another key characteristic of the Liebert 3000 is its modular design, allowing for flexible scalability. This means that organizations can easily expand the capacity of their UPS system as their power needs grow, without the need for extensive system overhauls. The modular architecture also facilitates simplified maintenance and reduces downtime, as individual modules can be serviced without interrupting power to the critical load.

The system is equipped with comprehensive monitoring and management capabilities. The Liebert 3000 provides real-time data on power usage, battery status, and system performance, enabling facility managers to make informed decisions and proactively address potential issues. The integration of remote management tools allows for seamless monitoring from anywhere, providing peace of mind for operators.

Overall, the Liebert 3000 combines high efficiency, advanced technology, and flexible design to deliver a robust power protection solution. Its reliability and performance make it a preferred choice for organizations seeking to protect their critical infrastructure while enhancing operational efficiency and sustainability. As businesses continue to rely on technology for their everyday operations, the Liebert 3000 stands out as a dependable safeguard against the uncertainties of power quality.