Goodman Mfg MH95/ACSH96/AMEH96/ GCH95/GME95/GCH9, GAS-FIRED WARM AIR FURNACE XIX. Maintenance

Page 40

XIX. MAINTENANCE

WARNING

HIGH VOLTAGE!

TO AVOID PERSONAL INJURY OR DEATH DUE TO ELECTRICAL SHOCK, DISCONNECT ELECTRICAL POWER BEFORE PERFORMING ANY MAINTENANCE. IF YOU MUST HANDLE THE IGNITER, HANDLE WITH CARE. TOUCHING THE IGNITER ELEMENT WITH BARE FINGERS, ROUGH HANDLING OR VIBRATION COULD DAMAGE THE IGNITER RESULTING IN PREMATURE FAILURE. ONLY A QUALIFIED SERVICER SHOULD EVER HANDLE THE IGNITER.

ANNUAL INSPECTION

The furnace should be inspected by a qualified installer, or service agency at least once per year. This check should be performed at the beginning of the heating season. This will ensure that all furnace com- ponents are in proper working order and that the heating system func- tions appropriately. Pay particular attention to the following items. Re- pair or service as necessary.

Flue pipe system. Check for blockage and/or leakage. Check the outside termination and the connections at and internal to the furnace.

Heat exchanger. Check for corrosion and/or buildup within the heat exchanger passageways.

Burners. Check for proper ignition, burner flame, and flame sense.

Drainage system. Check for blockage and/or leakage. Check hose connections at and internal to furnace.

Wiring. Check electrical connections for tightness and/or corrosion. Check wires for damage.

Filters.

FILTERS

CAUTION

TO ENSURE PROPER UNIT PERFORMANCE, ADHERE TO THE FILTER SIZES GIVEN IN THE RECOMMENDED MINIMUM FILTER SIZE TABLE OR SPECIFICATION SHEET APPLICABLE TO YOUR MODEL*

*NOTE: Please contact your distributor or our website for the applicable Specification Sheet referred to in this manual.

MAINTENANCE

Improper filter maintenance is the most common cause of inad- equate heating or cooling performance. Filters should be cleaned (permanent) or replaced (disposable) every two months or as re- quired. When replacing a filter, it must be replaced with a filter of the same type and size.

FILTER REMOVAL

Depending on the installation, differing filter arrangements can be applied. Filters can be installed in either the central return register or a side panel external filter rack (upflow only). A media air filter or electronic air cleaner can be used as an alternate filter. Follow the filter sizes given in the Recommended Minimum Filter size table to ensure proper unit performance.

To remove filters from an external filter rack in an upright upflow instal- lation, follow the directions provided with external filter rack kit.

HORIZONTAL UNIT FILTER REMOVAL

Filters in horizontal installations are located in the central return regis- ter or the ductwork near the furnace.

To remove:

1.Turn OFF electrical power to furnace.

2.Remove filter(s) from the central return register or ductwork.

3.Replace filter(s) by reversing the procedure for removal.

4.Turn ON electrical power to furnace.

MEDIA AIR FILTER OR ELECTRONIC AIR CLEANER REMOVAL

Follow the manufacturer’s directions for service.

BURNERS

Visually inspect the burner flames periodically during the heating sea- son. Turn on the furnace at the thermostat and allow several minutes for flames to stabilize, since any dislodged dust will alter the flames normal appearance. Flames should be stable, quiet, soft, and blue (dust may cause orange tips but they must not be yellow). They should extend directly outward from the burners without curling, floating, or lifting off. Flames must not impinge on the sides of the heat exchanger firing tubes.

INDUCED DRAFT AND CIRCULATOR BLOWERS

The bearings in the induced draft blower and circulator blower motors are permanently lubricated by the manufacturer. No further lubrication is required. Check motor windings for accumulation of dust which may cause overheating. Clean as necessary.

CONDENSATE TRAP AND DRAIN SYSTEM (QUALIFIED SERVICER ONLY)

Annually inspect the drain tubes, drain trap, and field-supplied drain line for proper condensate drainage. Check drain system for hose connection tightness, blockage, and leaks. Clean or repair as necessary.

FLAME SENSOR (QUALIFIED SERVICER ONLY)

Under some conditions, the fuel or air supply can create a nearly invisible coating on the flame sensor. This coating acts as an insulator causing a drop in the flame sense signal. If the flame sense signal drops too low the furnace will not sense flame and will lock out. The flame sensor should be carefully cleaned by a qualified servicer using emery cloth or steel wool. Following clean- ing, the flame sense signal should be 1 to 6 microamps at 115 volts.

IGNITER (QUALIFIED SERVICER ONLY)

If the igniter and the surrounding air are at about 70°F and the igniter wires are not connected to any other electrical components, the resistance of the igniter should not exceed 75 ohms. If it does, the igniter should be replaced.

FLUE PASSAGES (QUALIFIED SERVICER ONLY)

The heat exchanger flue passageways should be inspected at the beginning of each heating season. If necessary, clean the pas- sageways as outlined below.

1.Turn OFF the electrical power and gas supply to the furnace.

2.Disconnect the gas line and remove the burner/ manifold assembly by removing the screws securing the assembly to the partition panel.

3.Disconnect the flue pipe system from the induced draft blower.

4.Remove the induced draft blower and, drain and pressure tap hoses from the recuperator coil front cover.

5.Remove the recuperator coil front cover to expose the coil tubes and turbulators.

40

Image 40
Contents GCH95/GME95/GCH9 Table of Contents XIV. Startup Procedure & Adjustment XVII. Safety Circuit DescriptionXVIII. Troubleshooting XIX. MaintenanceCarbon Monoxide Poisoning Hazard Upflow/Horizontal Component IdentificationII. Safety Considerations What to do if YOU Smell GASElectrostatic Discharge ESD Precautions III. Product ApplicationIV. Location Requirements & Considerations GeneralClearances and Accessibility Suspended FurnaceFurnace Suspension Existing Furnace RemovalCombustion & Ventilation AIR Requirements Thermostat InfluencesThermostat Location See 5.3.3-a VII. Horizontal Applications & Considerations VI. Installation PositionsHorizontal Furnace Recommended Installation Positions VIII. Propane GAS /HIGH Altitude InstallationsAlternate Electrical and GAS Line Connections Drain PANDirect Vent Terminal Clearances IX. VENT/FLUE Pipe & Combustion AIR Pipe Dual Certification NON-DIRECT/DIRECT VentMaterials and Joining Methods Proper VENT/FLUE and Combustion AIR Piping PracticesIncreased Clearance Configuration Termination LocationsCanadian Venting Requirements Standard Furnace ConnectionsVent/Flue Pipe Cuts Alternate Furnace ConnectionsAlternate Vent/Flue Location NON-DIRECT Vent Single Pipe PipingDirect Vent Dual Pipe Piping Alternate Horizontal Vent Termination Dual Pipe Termination of Multiple Direct Vent FurnacesCondensate Drain Lines & Drain Trap Concentric Vent TerminationHose and Tube Identification Standard Right or Left Side Drain Hose ConnectionsDrain Trap Alternate VENT/FLUE Drain Hose ConnectionsUpright INSTALLATIONS-TRAP on Left Side Upright Standard Connections Left SideHorizontal Installations Right Side Down Upright Drain Trap Mounting Left or Right Side PanelLeft Side Down Horizontal Drain Trap Mounting Left or Right Side PanelWiring Harness XI. Electrical ConnectionsJunction Box Relocation Junction BOX RelocationThermostat Diagram Field Wiring for GME95 /AMEH96 Furnacewith 2-StageVolt Thermostat Wiring GME95/AMEH96 Furnace with 2-STAGE Condenser Field WiringVolt Humidifier Nals XII. GAS Supply and PipingGAS Piping Connections Rack, manifold or gas valve Horizontal Upflow Model Gas Piping ConnectionsPropane Gas Installation Typ Propane Gas Piping ChartXIII. Circulating AIR & Filters Propane GAS Tanks and PipingChecking Static Pressure 80% Furnace Shown, 90% Similar Duct Flange Cut OutsChecking Duct Static Bottom Return AIR Opening Upflow ModelsXIV. Startup Procedure & Adjustment Permanent Minimum Filter Area sq.Disposable Minimum Filter area sq. Filter LocationsWhite-Rodgers Model 36G54 Connected to Manometer White-Rodgers Model 36G54 Two-StageHoneywell Model VR9205 Connected to Manometer GAS Supply Pressure MeasurementMeasuring Inlet Gas Pressure Alt. Method GAS Manifold Pressure Measurement and AdjustmentGAS Input Rate Measurement Natural GAS only Temperature Rise Temperature Rise MeasurementCirculator Blower Speeds Circulator Blower FAN Timing Adjustment Setting Furnace Operating ModePower UP Heating ModePage XVIII. Troubleshooting XIX. Maintenance XX. Before Leaving AN Installation XXI. Repair & Replacement PartsTroubleshooting Chart No signalContinuously MH95 Blower Performance DataACSH96 AMEH96 GCH95 / GCH9115 GME95 Wiring Diagram MH950453,0704,0905D MH950703,0904,1155MH950905CX GME95 / AMEH96 GAS Vent Directly BELOW. Keep Clear of ALL Obstructions ExemptionsThis page Left Intentionally Blank This page Left Intentionally Blank This page Left Intentionally Blank Quality Makes the Difference