Goodman Mfg GAS-FIRED WARM AIR FURNACE Measuring Inlet Gas Pressure Alt. Method

Page 35

NOTE: If measuring gas pressure at the drip leg or Honeywell VR9205 gas valve, a field-supplied hose barb fitting must be installed prior to making the hose connection. If using the inlet pressure tap on the White-Rodgers 36G54 gas valve, then use the 36G Valve Pressure Check Kit, Goodman Part No. 0151K00000S.

3.Turn ON the gas supply and operate the furnace and all other gas consuming appliances on the same gas supply line.

4.Measure furnace gas supply pressure with burners firing. Supply pressure must be within the range specified in the Inlet Gas Supply Pressure table.

Inlet Gas Supply Pressure

Natural Gas

Minimum:

4.5" w.c.

Maximum:

10.0" w.c.

Propane Gas

Minimum:

11.0" w.c.

Maximum:

13.0" w.c.

If supply pressure differs from table, make the necessary adjust- ments to pressure regulator, gas piping size, etc., and/or consult with local gas utility.

5.Turn OFF gas to furnace at the manual shutoff valve and disconnect manometer. Reinstall plug before turning on gas to furnace.

6.Turn OFF any unnecessary gas appliances stated in step 3.

Gas Line

Gas

Shutoff

Valve

Gas Line

To Furnace

Open To

Atmosphere

Drip Leg Cap

With Fitting

Manometer Hose

Manometer

Measuring Inlet Gas Pressure (Alt. Method)

GAS MANIFOLD PRESSURE MEASUREMENT AND ADJUSTMENT

CAUTION

TO PREVENT UNRELIABLE OPERATION OR EQUIPMENT DAMAGE, THE GAS MANIFOLD PRESSURE MUST BE AS SPECIFIED ON THE UNIT RATING PLATE. ONLY MINOR ADJUSTMENTS SHOULD BE MADE BY ADJUSTING THE GAS VALVE PRESSURE REGULATOR.

Only small variations in gas pressure should be made by adjust- ing the gas valve pressure regulator. The manifold pressure must be measured with the burners operating. To measure and adjust the manifold pressure, use the following procedure.

1.Turn OFF gas to furnace at the manual gas shutoff valve external to the furnace.

2.Turn off all electrical power to the system.

3.Outlet pressure tap connections:

a.Honeywell VR9205 valve: Remove the outlet pressure tap plug. Install an 1/8" NPT hose barb fitting into the outlet pressure tap.

b.White-Rodgers 36G54 valve: Back outlet pressure test screw (inlet/outlet pressure tap) out one turn (counterclockwise, not more than one turn).

4.Attach a hose and manometer to the outlet pressure barb fitting (Honeywell valve) or outlet pressure tap (White-Rodgers valve).

5.Turn ON the gas supply.

6.Turn on power and close thermostat “R” and “W1” contacts to provide a call for low stage heat.

7.Measure the gas manifold pressure with burners firing. Adjust manifold pressure using the Manifold Gas Pressure table shown below.

8.Remove regulator cover screw from the low (LO) outlet pressure regulator adjust tower and turn screw clockwise to increase pressure or counterclockwise to decrease pressure. Replace regulator cover screw.

9.Close thermostat “R” and “W2” contacts to provide a call for high stage heat.

10.Remove regulator cover screw from the high (HI) outlet pressure regulator adjust tower and turn screw clockwise to increase pressure or counterclockwise to decrease pressure. Replace regulator cover screw.

11.Turn off all electrical power and gas supply to the system.

12.Remove the manometer hose from the hose barb fitting or outlet pressure tap.

13.Replace outlet pressure tap:

a.Honeywell VR9205 valve: Remove the 1/8" NPT hose barb fitting from the outlet pressure tap. Replace the outlet pressure tap plug and seal with a high quality thread sealer.

b.White-Rodgers 36G54 valve: Turn outlet pressure test screw in to seal pressure port (clockwise, 7 in-lb minimum).

14.Turn on electrical power and gas supply to the system.

15.Close thermostat contacts “R” and “W1/W2” to energize the valve.

Using a leak detection solution or soap suds, check for leaks at outlet pressure boss plug (Honeywell valve) or screw (White-Rodg- ers valve). Bubbles forming indicate a leak. SHUT OFF GAS AND REPAIR ALL LEAKS IMMEDIATELY!

NOTE: For gas to gas conversion, consult your dealer for appropriate conversion.

Manifold Gas Pressure

Gas

Rate

Range

Nominal

 

 

 

 

Natural

Low Stage

1.7 to 2.3" w.c.

2.0" w.c.

High Stage

3.2 to 3.8" w.c.

3.5" w.c.

 

Propane

Low Stage

5.7 to 6.3" w.c.

6.0" w.c.

High Stage

9.7 to 10.3" w.c.

10.0" w.c.

 

GAS INPUT RATE MEASUREMENT (NATURAL GAS ONLY)

The gas input rate to the furnace must never be greater than that specified on the unit rating plate. To measure natural gas input using the gas meter, use the following procedure.

1.Turn OFF the gas supply to all other gas-burning appliances except the furnace.

2.While the furnace is operating, time and record one complete revolution of the smallest gas meter dial.

35

Image 35
Contents GCH95/GME95/GCH9 Table of Contents XIX. Maintenance XIV. Startup Procedure & AdjustmentXVII. Safety Circuit Description XVIII. TroubleshootingCarbon Monoxide Poisoning Hazard Component Identification Upflow/HorizontalWhat to do if YOU Smell GAS II. Safety ConsiderationsIII. Product Application Electrostatic Discharge ESD PrecautionsGeneral IV. Location Requirements & ConsiderationsExisting Furnace Removal Clearances and AccessibilitySuspended Furnace Furnace SuspensionThermostat Location Thermostat InfluencesCombustion & Ventilation AIR Requirements See 5.3.3-a Horizontal Furnace VI. Installation PositionsVII. Horizontal Applications & Considerations Drain PAN Recommended Installation PositionsVIII. Propane GAS /HIGH Altitude Installations Alternate Electrical and GAS Line ConnectionsDirect Vent Terminal Clearances Proper VENT/FLUE and Combustion AIR Piping Practices IX. VENT/FLUE Pipe & Combustion AIR PipeDual Certification NON-DIRECT/DIRECT Vent Materials and Joining MethodsStandard Furnace Connections Increased Clearance ConfigurationTermination Locations Canadian Venting RequirementsAlternate Furnace Connections Vent/Flue Pipe CutsNON-DIRECT Vent Single Pipe Piping Alternate Vent/Flue LocationDirect Vent Dual Pipe Piping Concentric Vent Termination Alternate Horizontal Vent Termination Dual PipeTermination of Multiple Direct Vent Furnaces Condensate Drain Lines & Drain TrapStandard Right or Left Side Drain Hose Connections Hose and Tube IdentificationAlternate VENT/FLUE Drain Hose Connections Drain TrapUpright Standard Connections Left Side Upright INSTALLATIONS-TRAP on Left SideUpright Drain Trap Mounting Left or Right Side Panel Horizontal Installations Right Side DownHorizontal Drain Trap Mounting Left or Right Side Panel Left Side DownJunction BOX Relocation Wiring HarnessXI. Electrical Connections Junction Box RelocationGME95/AMEH96 Furnace with 2-STAGE Condenser Field Wiring Thermostat DiagramField Wiring for GME95 /AMEH96 Furnacewith 2-Stage Volt Thermostat WiringGAS Piping Connections Nals XII. GAS Supply and PipingVolt Humidifier Rack, manifold or gas valve Gas Piping Connections Horizontal Upflow ModelPropane GAS Tanks and Piping Propane Gas Installation TypPropane Gas Piping Chart XIII. Circulating AIR & FiltersBottom Return AIR Opening Upflow Models Checking Static Pressure 80% Furnace Shown, 90% SimilarDuct Flange Cut Outs Checking Duct StaticFilter Locations XIV. Startup Procedure & AdjustmentPermanent Minimum Filter Area sq. Disposable Minimum Filter area sq.GAS Supply Pressure Measurement White-Rodgers Model 36G54 Connected to ManometerWhite-Rodgers Model 36G54 Two-Stage Honeywell Model VR9205 Connected to ManometerGAS Input Rate Measurement Natural GAS only GAS Manifold Pressure Measurement and AdjustmentMeasuring Inlet Gas Pressure Alt. Method Circulator Blower Speeds Temperature Rise MeasurementTemperature Rise Heating Mode Circulator Blower FAN Timing AdjustmentSetting Furnace Operating Mode Power UPPage XVIII. Troubleshooting XIX. Maintenance XXI. Repair & Replacement Parts XX. Before Leaving AN InstallationNo signal Troubleshooting ChartContinuously Blower Performance Data MH95ACSH96 AMEH96 GCH95 / GCH9115 GME95 MH950453,0704,0905D MH950703,0904,1155 Wiring DiagramMH950905CX GME95 / AMEH96 Exemptions GAS Vent Directly BELOW. Keep Clear of ALL ObstructionsThis page Left Intentionally Blank This page Left Intentionally Blank This page Left Intentionally Blank Quality Makes the Difference