New Buck Corporation installation instructions Model 21 minimum clearance to combustibles

Page 19
Manual background

B. Vertical wall exit using (6" Single Wall minimum 24 ga. blued or black pipe with elbow, and any listed 2100° UL 103 HT.

TYPE Chimney and Listed 2100° UL HT. T-Box assembly). Without optional close clearance shield and pipe shield.

Model 21 minimum clearance to combustibles.

BACK WALL

Figure 9.

B

H D FF

B

G

SIDE WALL

E

PROTECTOR

 

G

 

E

 

 

 

A

 

CC Manual backgroundManual backgroundC

A B C D E F G

MODEL 21 25” 13" 19" 15.5" 8" 3" 16"

NOTE: All clearances are to combustibles without close clearance shields and pipe shield, 6" Single Wall minimum 24 ga. blued or black pipe with elbow, and minimum floor protector.Clearances above may be reduced. Follow NFPA-211codes if available or follow instructions on (Pages 20, and 21, or Pages 24, and 25).

CEILING

SINGLE WALL

CONNECTOR

ELBOW PIPE

Figure 10.

IN

SIDE

WALL

LISTED 2100° UL 103 HT TYP.

CHIMNEY REEFER TO

MANUFACTURES INSTALLATION INSTRUCTION

LISTED 2100° UL 103 HT

TYP. CHIMNEY T-BOX

ASSEMBLY REEFER TO

MANUFACTURES

INSTALLATION

INSTRUCTION

WALL

PASS-THROUGH

CONNECTOR

17

Image 19
Contents MODEL NON-CAT MODEL NON-CATALYTICUNITBuck Stove Page TABLE OF CONTENTS MAINTENANCE INSTRUCTIONS MODEL INSTALLATION, OPERATION, ANDREAD THIS FIRST IMPORTANT INSTRUCTIONS INTRODUCTION SECTIONSECTION MASONRY INSERT INSTALLATIONMODEL Floor Protection INSTALLATION PREPARATION POSSIBLE TOOLS NEEDED FOR INSTALLATIONMASONRY INSERT INSTALLATION OPTIONS FRONT OF STOVE UNIT WITH INSULATION OR HIGH AIRTIGHT INSU LATED CLEAN OUT REMOVE DAMPEROR WIRE IT OPEN STARTER PIPE SEAL TRIM PANELS AND UNDERFIGURE 3 MOUNTING TRIM PANELS POSITIONING THE HEATERPOSITIONING MOUNTING THE TRIM PANELSFINAL CHECK Page SECTION PRE-FABINSERT INSTALLATION Chimney PREPARING THE STOVE FOR INSTALLATIONFloor Protection 1. Convert specification to R-valueCHIMNEY HOW TO LOCATE CHIMNEY EXIT, AND INSTALLResidential Installation PREPARING THE ROOM HEATER LOCATIONModel 21 minimum clearance to combustibles Residential Installation HOW TO LOCATE CHIMNEY EXIT, AND INSTALLNOTE For minimum clearances See Page 17, Figure Model 21 minimum clearance to combustibles NOTE For minimum clearances See Page 19, Figure Residential and Mobile Home InstallationHOW TO LOCATE CHIMNEY EXIT, AND INSTALL Without close clearance shield and pipe shieldModel 21 minimum clearance to combustibles any listed 2100 UL 103 HT. TYPE ChimneyResidential and Mobile Home Installation HOW TO LOCATE CHIMNEY EXIT, AND INSTALLD. Vertical Wall Exit using 6 DVL Close Clearance Pipe, and Elbow, and any Listed 2100 UL HT chimney and Listed 2100 UL HT T-Boxassembly Model 21 minimum clearance to combustibles Listed 2100 UL HT T-BoxassemblyResidential and Mobile Home Installation HOW TO LOCATE CHIMNEY EXIT, AND INSTALLNOTE For minimum clearances See Page 23, Figure Model 21 minimum clearance to combustibles any listed 2100 UL 103 HT. TYPE ChimneyResidential and Mobile Home Installation HOW TO LOCATE CHIMNEY EXIT, AND INSTALLNOTE For minimum clearances See Page 25, Figure Listed 2100 UL HT T-Boxassembly OUT SIDE AIR INSTALLATION Page FINAL CHECK PREPARING THE STOVE FOR INSTALLATION SECTION ALCOVE INSTALLATION AND CLEARANCESChimney Floor Protection 1. Convert specification to R-valueHOW TO LOCATE CHIMNEY EXIT, AND INSTALL Alcove Installationany listed 2100 UL 103 HT. TYPE Chimney ALCOVE INSTALLATION AND CLEARANCESModel 21 minimum clearance to combustibles 13/16” TYP 1” TYP 1/4” TYP Installation of Optional Close Clearance ShieldsInstallation of Optional Pipe Shield Pipe Shield Loosen these top shield screwsFINAL CHECK SECTION WOOD HEATER SAFETY BUILDING A FIRE SECTION OPERATIONPOSSIBLE CAUSE SECTION TROUBLESHOOTINGPROBLEM SOLUTIONSOLUTION PROBLEMPOSSIBLE CAUSE PRODUCTS COVERED WARRANTY TIME PERIODSPROCEDURE NEW BUCK CORPORATION NBCOTHER RIGHTS CONDITIONS AND EXCLUSIONS