Bryant F Convenience Outlets, Installing Weatherproof Cover, Non-Powered Type, Unit-Powered Type

Page 16

CONVENIENCE OUTLETS

 

 

!

WARNING

 

 

 

 

ELECTRICAL OPERATION HAZARD

 

 

 

 

Failure to follow this warning could result in personal

 

 

 

injury or death.

 

 

 

 

 

Units with convenience outlet circuits may use

 

 

 

multiple disconnects. Check convenience outlet for

 

 

 

power status before opening unit for service. Locate

 

 

 

its disconnect switch, if appropriate, and

open it.

 

 

 

Tag-out this switch, if necessary.

 

 

 

 

 

 

 

 

Two types of convenience outlets are offered on 580J

 

 

models: Non-powered and unit-powered. Both types

580J

 

 

provide a 125-volt GFCI (ground-fault circuit-interrupter)

 

duplex receptacle

rated at 15-A behind

a hinged

 

 

waterproof access cover, located on the end panel of the

 

 

unit. (See Fig. 16.)

 

 

 

 

 

 

 

 

Pwd-CO Transformer

Conv Outlet

GFCI

Pwd-CO

Fuse

Switch

C08128

Fig. 16 - Convenience Outlet Location

Installing Weatherproof Cover

Aweatherproof while-in-use cover for the factory-installed convenience outlets is now required by UL standards. This cover cannot be factory-mounted due to its depth. It must be installed at unit installation. For shipment, the convenience outlet is covered with a blank cover plate.

The weatherproof cover kit is shipped in the unit’s control box. The kit includes the hinged cover, a backing plate and gasket.

IMPORTANT: Disconnect all power to unit and convenience outlet.

1.Remove the blank cover plate at the convenience out- let; discard the blank cover.

2.Loosen the two screws at the GFCI duplex outlet, un- til approximately 1/2-in (13 mm) under screw heads are exposed.

3.Press the gasket over the screw heads. Slip the back- ing plate over the screw heads at the keyhole slots and align with the gasket. Tighten the two screws un- til snug (do not over-tighten).

4.Mount the weatherproof cover to the backing plate as shown in Fig. 17.

COVER - WHILE-IN-USE

WEATHERPROOF

BASE PLATE FOR

GFCI RECEPTACLE

C09244

Fig. 17 - Weatherproof Cover Installation

5.Remove two slot fillers in the bottom of the cover to permit service tool cords to exit the cover. Check for full closing and latching.

Non-Powered Type

This type requires the field installation of a general-purpose 125-volt 15-A circuit powered from a source elsewhere in the building. Observe national and local codes when selecting wire size, fuse or breaker requirements and disconnect switch size and location. Route 125-v power supply conductors into the bottom of the utility box containing the duplex receptacle.

Unit-Powered Type

Aunit-mounted transformer is factory-installed to stepdown the main power supply voltage to the unit to 115-v at the duplex receptacle. This option also includes a manual switch with fuse, located in a utility box and mounted on a bracket behind the convenience outlet; access is through the unit’s control box access panel. (See Fig. 16.)

The primary leads to the convenience outlet transformer are not factory-connected. Selection of primary power source is a customer-option. If local codes permit, the transformer primary leads can be connected at the line-side terminals on a unit-mounted non-fused disconnect or circuit-breaker switch; this will provide service power to the unit when the unit disconnect switch or circuit-breaker is open. Other connection methods will result in the convenience outlet circuit being de-energized when the unit disconnect or circuit-breaker is open. (See Fig. 18.)

16

Image 16
Contents Table of Contents Safety ConsiderationsGeneral Unit Arrangement and AccessWhat to do if you smell gas Routine Maintenance Seasonal MaintenanceSupply Fan Belt-Drive Supply FAN Blower SectionManual Outside Air Hood Screen Adjustable-Pitch Pulley on Motor Supply-Fan Pulley Adjustment BearingsCoil Maintenance and Cleaning Recommendation CoolingCondenser Coil Evaporator CoilRoutine Cleaning of Novation Condenser Coil Surfaces Routine Cleaning of Evaporator Coil SurfacesRefrigerant System Pressure Access Ports Puronr R-410A RefrigerantEvaporator Coil Metering Devices Refrigerant ChargeSeatcore Cooling Charging Charts Cooling Charging Charts 08D,F Both CircuitsCooling Charging Charts 12D,F Both Circuits TON Circuit TON Circuit Cooling Service Analysis Problem Cause RemedyCondenser-Fan Adjustment 08D-12D,F size Condenser-Fan Adjustment 14D,F sizeTroubleshooting Cooling System CompressorsInstalling Weatherproof Cover Non-Powered TypeUnit-Powered Type Convenience OutletsSmoke Detectors Smoke Detector Locations SensorSupply Air Completing Installation of Return Air Smoke Sensor Fiop Smoke Detector Wiring and ResponseReturn Air Without Economizer All UnitsSensor and Controller Tests Controller Alarm Test Controller Alarm Test ProcedureDirty Controller Test Procedure Dirty Sensor Test ProcedureDetector Cleaning SD-TRK4 Remote Alarm Test ProcedureRemote Test/Reset Station Dirty Sensor Test Dirty Sensor Test Using an SD-TRK4Troubleshooting Protective Devices Compressor ProtectionControl Circuit GAS Heating SystemFuel Types and Pressures Supply Pressure Switch Flue Gas PassagewaysCombustion-Air Blower Liquid Propane Supply Line Pressure RangesMain Burners Burners and IgnitersOrifice Projection Check Unit Operation and Make Necessary Adjustments Cleaning and AdjustmentLimit Switch LED Indication Error Code Description LED Error Code DescriptionBurner Ignition Orifice Replacement Gas ValveRed LED-Status Altitude Compensation Orifice SizesLP Orifice Minimum Heating Entering Air Temperature Troubleshooting Heating SystemHeating Service Analysis IGC Board LED Alarm Codes IGCCondenser Coil Service Repairing Novation Condenser Tube LeaksRTU-MP Control System Replacing Novation Condenser CoilRTU-MP Multi-Protocol Control Board Typical RTU-MP System Control Wiring Diagram Supply Air Temperature SAT Sensor Outdoor Air Temperature OAT SensorRTU-MP Controller Inputs and Outputs OutputsEconoMi$er Space Temperature SPT SensorsConnect T-55 Economizer Controls Outdoor Air Enthalpy Control PNO HH57AC077Wiring the Indoor Air Quality Sensor Differential Enthalpy ControlReturn Air Enthalpy Sensor Indoor Air Quality CO2 SensorConnecting Discrete Inputs Outdoor Air Quality Sensor PNO 33ZCSENCO2 plusWeatherproof Enclosure Filter StatusPower Exhaust output Communication Wiring ProtocolsRTU-MP Troubleshooting Communication LEDsProtocol DS8 DS7 DS6 DS5 DS4 DS3 DS2 DS1 Baud Rate DS2 DS1LEDs LEDs on the RTU-MP show the status of certain functionsTroubleshooting Alarms Alarms BACnet MS/TPModule Status Report Modstat Example Basic Protocol Troubleshooting ModbusManufacture Date Code Name MeaningECONOMI$ER Systems EconoMi$er IV Component LocationsEconoMi$er IV Wiring EconoMi$er IV Input/Output Logic EconoMi$er IV Functional ViewSupply Air Temperature SAT Sensor Outdoor Air Lockout SensorEconoMi$er IV Control Modes Outdoor Dry Bulb ChangeoverDifferential Dry Bulb Control Outdoor Enthalpy ChangeoverIndoor Air Quality IAQ Sensor Input Exhaust Setpoint AdjustmentMinimum Position Control Thermostats Damper MovementDemand Control Ventilation DCV CO2 Sensor Standard Settings CO2 Sensor ConfigurationAnalog CO2 DCV Demand Controlled Ventilation and Power Exhaust EconoMi$er IV Sensor UsageEconoMi$er IV Preparation Differential EnthalpyWiring Diagrams EconoMi$er IV Troubleshooting CompletionDCV Minimum and Maximum Position Supply-Air Sensor Input580J Typical Unit Wiring Diagram Power 08D,F, 208/230-3-60 C09157 PRE-START-UP START-UP, GeneralUnit Preparation Gas PipingInternal Wiring Refrigerant Service PortsReturn-Air Filters Outdoor-Air Inlet ScreensField Service Test ConfigurationUnit Start Delay START-UP, RTU-MP ControlFilter Service Hours Supply Fan Service HoursCompressor1 Service Hours Compressor2 Service HoursInput Space Sensor TypeInput 1 Function Input 2 FunctionOperating Sequences Base Unit Controls Cooling, Units Without EconomizerHeating, Units Without Economizer Cooling, Unit With EconoMi$erHeating With EconoMi$er Demand Controlled VentilationSupplemental Controls RTU-MP Sequence of OperationAlways Occupied Default Occupancy SchedulingLocal Schedule BACnet ScheduleCooling Power ExhaustEconomizer Fastener Torque Values Indoor Air QualityDemand Limit Torque ValuesAppendix I. Model Number Significance Model Number NomenclatureSerial Number Format Position NumberPhysical Data Appendix II. Physical Data12.5TONS Heat Anticipator Setting Amps Physical Data Heating 12.5TONS580J**08 580J**12 580J**14 Gas Connection Natural Gas Heat, Liquid Propane Heat580J**08 Appendix III. FAN PerformanceCFM RPM BHP 580J**12 579580J**14 RPM BHPGeneral fan performance notes 1260Pulley Adjustment Unit MOTOR/DRIVE Motor Pulley Turns Open ComboElectrical Information Unit Combustion Power NOM IFM FAN Motor Exhaust No P.EType DISC. Size MocpAppendix IV. Wiring Diagram List Wiring DiagramsAppendix V. Motormaster Sensor Locations Catalog No.SM580J---02580J Unit START-UP Checklist Preliminary Information

580J*08--14D, F specifications

The Bryant F,580J*08--14D is an advanced heating and cooling system engineered for optimal performance and energy efficiency in residential and commercial applications. This innovative unit is designed to provide exceptional climate control while reducing operational costs, making it an ideal choice for those seeking reliable HVAC solutions.

One of the standout features of the Bryant F,580J*08--14D is its versatile heating and cooling capabilities. This system employs a two-stage compressor, which allows for precise temperature regulation and improved energy efficiency. This dual-stage operation ensures that the system can adapt to varying environmental conditions, providing enhanced comfort without excessive energy use.

The system is equipped with advanced inverter technology, which enables smoother operation and quieter performance. This technology adjusts the compressor speed based on the heating or cooling demand, leading to increased efficiency and reduced energy consumption. Additionally, the inverter system contributes to less noise during operation, creating a serene indoor environment.

The Bryant F,580J*08--14D also features a user-friendly thermostat that allows for easy temperature adjustments and scheduling. This smart thermostat is compatible with mobile devices, enabling users to monitor and control their HVAC system remotely. This feature provides added convenience and ensures that the system is operating efficiently, even when homeowners are away.

Energy efficiency is a hallmark of the Bryant F,580J*08--14D. The system meets and often exceeds ENERGY STARĀ® standards, making it one of the more eco-friendly options available in the market today. By utilizing energy-saving technologies and innovative designs, the system helps to lower utility bills and reduce the environmental impact.

Durability and reliability are key characteristics of the Bryant F,580J*08--14D. Constructed with high-quality materials and components, this unit is designed to withstand the rigors of changing weather conditions while maintaining consistent performance. Additionally, it comes equipped with a robust warranty, providing peace of mind for users investing in this heating and cooling solution.

In summary, the Bryant F,580J*08--14D is a top-tier HVAC system that boasts advanced technologies, exceptional energy efficiency, and user-friendly features. Its combination of reliable performance and modern conveniences makes it a standout choice for anyone looking to enhance their home's or business's climate control system, providing comfort and savings for years to come.