Bryant 580J*08--14D, F Troubleshooting Heating System, Minimum Heating Entering Air Temperature

Page 33

Minimum Heating Entering Air Temperature

Thermostat

LCTB

When operating on first stage heating, the minimum temperature of air entering the dimpled heat exchanger is 50_F continuous and 45_F intermittent for standard heat exchangers and 40_F continuous and 35_F intermittent for stainless steel heat exchangers. To operate at lower mixed-air temperatures, a field-supplied outdoor-air thermostat must be used to initiate both stages of heat when the temperature is below the minimum required temperature to ensure full fire operation. Wire the

TH1

TH2

W1

OALT

W2

C08442

Fig. 41 - OATL Connections

outdoor-air thermostat OALT (part no. HH22AG106) in series with the second stage gas valve. (See Fig. 41.) Set the outdoor-air thermostat at 35_F for stainless steel heat exchangers or 45_F for standard heat exchangers. This temperature setting will bring on the second stage of heat whenever the ambient temperature is below the thermostat setpoint. Indoor comfort may be compromised when heating is initiated using low entering air temperatures with insufficient heating temperature rise.

Troubleshooting Heating System

Refer to Table 13 and 14 for additional troubleshooting topics.

580J

 

Table 13 – Heating Service Analysis

 

 

 

PROBLEM

CAUSE

REMEDY

 

Misaligned spark electrodes.

Check flame ignition and sensor electrode positioning.

 

Adjust as needed.

 

 

 

 

 

 

 

Check gas line for air, purge as necessary. After purging

 

No gas at main burners.

gas line of air, allow gas to dissipate for at least 5 minutes

 

before attempting to relight unit.

 

 

 

 

 

 

 

Check gas valve.

Burners Will Not Ignite.

Water in gas line.

Drain water and install drip leg to trap water.

 

 

No power to furnace.

Check power supply, fuses, wiring, and circuit breaker.

 

 

No 24 v power supply to control

Check transformer. Transformers with internal overcurrent

 

circuit.

protection require a cool down period before resetting.

 

 

 

 

Miswired or loose connections.

Check all wiring and wire nut connections.

 

 

 

 

Burned---out heat anticipator in

Replace thermostat.

 

thermostat.

 

 

 

 

 

 

Broken thermostat wires.

Run continuity check. Replace wires, if necessary.

 

Dirty air filter.

Clean or replace filter as necessary.

 

 

 

 

Gas input to unit too low.

Check gas pressure at manifold. Clock gas meter for input.

 

If too low, increase manifold pressure, or replace with

 

 

correct orifices.

 

 

 

 

Unit undersized for application.

Replace with proper unit or add additional unit.

Inadequate Heating.

Restricted airflow.

Clean filter, replace filter, or remove any restrictions.

 

 

Blower speed too low.

Use high speed tap, increase fan speed, or install optional

 

 

blower, as suitable for individual units.

 

 

 

 

 

 

Limit switch cycles main burners.

Check rotation of blower, thermostat heat anticipator

 

settings, and temperature rise of unit. Adjust as needed.

 

 

 

 

 

 

Too much outdoor air.

Adjust minimum position.

 

 

 

Check economizer operation.

 

 

 

 

Check all screws around flue outlets and burner

 

Incomplete combustion (lack of

compartment. Tighten as necessary.

 

 

Poor Flame

Cracked heat exchanger.

combustion air) results in:

 

Overfired unit — reduce input, change orifices, or adjust

Characteristics.

Aldehyde odors, CO, sooting

gas line or manifold pressure.

 

flame, or floating flame.

 

 

 

Check vent for restriction. Clean as necessary.

 

 

 

 

Check orifice to burner alignment.

 

 

 

Burners Will Not Turn

Unit is locked into Heating mode

Wait until mandatory one---minute time period has elapsed

Off.

for a one minute minimum.

or reset power to unit.

 

 

 

33

Image 33
Contents Safety Considerations Table of ContentsUnit Arrangement and Access GeneralWhat to do if you smell gas Seasonal Maintenance Routine MaintenanceSupply FAN Blower Section Supply Fan Belt-DriveManual Outside Air Hood Screen Supply-Fan Pulley Adjustment Bearings Adjustable-Pitch Pulley on MotorCooling Coil Maintenance and Cleaning RecommendationCondenser Coil Evaporator CoilRoutine Cleaning of Evaporator Coil Surfaces Routine Cleaning of Novation Condenser Coil SurfacesPuronr R-410A Refrigerant Refrigerant System Pressure Access PortsEvaporator Coil Metering Devices Refrigerant ChargeSeatcore Cooling Charging Charts 08D,F Both Circuits Cooling Charging ChartsCooling Charging Charts 12D,F Both Circuits TON Circuit TON Circuit Problem Cause Remedy Cooling Service AnalysisCondenser-Fan Adjustment 14D,F size Condenser-Fan Adjustment 08D-12D,F sizeTroubleshooting Cooling System CompressorsNon-Powered Type Installing Weatherproof CoverUnit-Powered Type Convenience OutletsSmoke Detectors Sensor Smoke Detector LocationsSupply Air Fiop Smoke Detector Wiring and Response Completing Installation of Return Air Smoke SensorReturn Air Without Economizer All UnitsSensor and Controller Tests Controller Alarm Test Procedure Controller Alarm TestDirty Controller Test Procedure Dirty Sensor Test ProcedureSD-TRK4 Remote Alarm Test Procedure Detector CleaningRemote Test/Reset Station Dirty Sensor Test Dirty Sensor Test Using an SD-TRK4Troubleshooting Compressor Protection Protective DevicesGAS Heating System Control CircuitFuel Types and Pressures Flue Gas Passageways Supply Pressure SwitchCombustion-Air Blower Liquid Propane Supply Line Pressure RangesBurners and Igniters Main BurnersOrifice Projection Cleaning and Adjustment Check Unit Operation and Make Necessary AdjustmentsLimit Switch LED Error Code Description LED Indication Error Code DescriptionBurner Ignition Gas Valve Orifice ReplacementRed LED-Status Orifice Sizes Altitude CompensationLP Orifice Troubleshooting Heating System Minimum Heating Entering Air TemperatureHeating Service Analysis IGC IGC Board LED Alarm CodesRepairing Novation Condenser Tube Leaks Condenser Coil ServiceRTU-MP Control System Replacing Novation Condenser CoilRTU-MP Multi-Protocol Control Board Typical RTU-MP System Control Wiring Diagram Outdoor Air Temperature OAT Sensor Supply Air Temperature SAT SensorRTU-MP Controller Inputs and Outputs OutputsSpace Temperature SPT Sensors EconoMi$erConnect T-55 Outdoor Air Enthalpy Control PNO HH57AC077 Economizer ControlsDifferential Enthalpy Control Wiring the Indoor Air Quality SensorReturn Air Enthalpy Sensor Indoor Air Quality CO2 SensorOutdoor Air Quality Sensor PNO 33ZCSENCO2 plus Connecting Discrete InputsWeatherproof Enclosure Filter StatusCommunication Wiring Protocols Power Exhaust outputCommunication LEDs RTU-MP TroubleshootingProtocol DS8 DS7 DS6 DS5 DS4 DS3 DS2 DS1 Baud Rate DS2 DS1LEDs on the RTU-MP show the status of certain functions LEDsTroubleshooting Alarms BACnet MS/TP AlarmsModule Status Report Modstat Example Modbus Basic Protocol TroubleshootingManufacture Date Code Name MeaningEconoMi$er IV Component Locations ECONOMI$ER SystemsEconoMi$er IV Wiring EconoMi$er IV Functional View EconoMi$er IV Input/Output LogicOutdoor Air Lockout Sensor Supply Air Temperature SAT SensorEconoMi$er IV Control Modes Outdoor Dry Bulb ChangeoverOutdoor Enthalpy Changeover Differential Dry Bulb ControlExhaust Setpoint Adjustment Indoor Air Quality IAQ Sensor InputMinimum Position Control Damper Movement ThermostatsDemand Control Ventilation DCV CO2 Sensor Configuration CO2 Sensor Standard SettingsAnalog CO2 EconoMi$er IV Sensor Usage DCV Demand Controlled Ventilation and Power ExhaustEconoMi$er IV Preparation Differential EnthalpyEconoMi$er IV Troubleshooting Completion Wiring DiagramsDCV Minimum and Maximum Position Supply-Air Sensor Input580J Typical Unit Wiring Diagram Power 08D,F, 208/230-3-60 C09157 START-UP, General PRE-START-UPUnit Preparation Gas PipingRefrigerant Service Ports Internal WiringReturn-Air Filters Outdoor-Air Inlet ScreensConfiguration Field Service TestUnit Start Delay START-UP, RTU-MP ControlSupply Fan Service Hours Filter Service HoursCompressor1 Service Hours Compressor2 Service HoursSpace Sensor Type InputInput 1 Function Input 2 FunctionBase Unit Controls Cooling, Units Without Economizer Operating SequencesHeating, Units Without Economizer Cooling, Unit With EconoMi$erDemand Controlled Ventilation Heating With EconoMi$erSupplemental Controls RTU-MP Sequence of OperationScheduling Always Occupied Default OccupancyLocal Schedule BACnet SchedulePower Exhaust CoolingEconomizer Indoor Air Quality Fastener Torque ValuesDemand Limit Torque ValuesModel Number Nomenclature Appendix I. Model Number SignificanceSerial Number Format Position NumberAppendix II. Physical Data Physical Data12.5TONS Physical Data Heating 12.5TONS Heat Anticipator Setting Amps580J**08 580J**12 580J**14 Gas Connection Natural Gas Heat, Liquid Propane HeatAppendix III. FAN Performance 580J**08CFM RPM BHP 579 580J**12RPM BHP 580J**141260 General fan performance notesUnit MOTOR/DRIVE Motor Pulley Turns Open Combo Pulley AdjustmentElectrical Information NOM IFM FAN Motor Exhaust No P.E Unit Combustion PowerType DISC. Size MocpWiring Diagrams Appendix IV. Wiring Diagram ListCatalog No.SM580J---02 Appendix V. Motormaster Sensor Locations580J Preliminary Information Unit START-UP Checklist