Bryant 580J*08--14D, F appendix Alarms, BACnet MS/TP

Page 47

Alarms

Alarms can be checked through the network and/or the local access. All the alarms are listed in Table 18 with name, object name, action taken by control, reset method, and probable cause. There are help screens for each alarm on the local access display and listed in RTU-MP Controls, Start-Up, Operation, and Troubleshooting Instructions (Form 48-50H-T-2T), Appendix A: Help Screens. Some alarms are explained in detail below.

Safety Chain Alarm

This alarm occurs immediately if the supply-fan internal overload trips or if an electric-heat limit switch trips. The Unit Status will be Shutdown and the System Mode will be Disable. When this happens LCTB (R terminal) will not have 24 VAC, but the RTU-MP board will still be powered. All unit operations stop immediately and will not restart until the alarm automatically clears. There are no configurations for this alarm; it is all based on internal wiring. This alarm will never occur if Fire Shutdown Alarm is active.

Fire Shutdown Alarm

This alarm occurs immediately when the smoke detector senses smoke. The Unit Status will be Shutdown and the System Mode will be Disable. All unit operations stop immediately and will not restart until the alarm automatically clears. If there is not a smoke detector installed or the smoke detector did not trip, check input configurations.

Space Temp Sensor Failure

This alarm occurs if the space sensor wired to the RTU-MP is disconnected or shorted for more then 10 seconds. When this occurs the Unit Status will be Shutdown and the System Mode will be Run. Sensor, sensor connections, wiring, board connection, and configurations should be checked for faults or errors. Alarm will reset automatically when cause is fixed.

SAT Sensor Alarm

This alarm occurs immediately when the supply air temperature sensor wired to the RTU-MP is disconnected or shorted. When this occurs the Unit Status will be Shutdown and the System Mode will be Run. Sensor, sensor connections, wiring, board connection, and configurations should be checked for faults or errors. Alarm will reset automatically when cause is fixed.

Switch Configuration Alarm

This occurs if more than one binary input (inputs 3, 5, 8, and 9) is configured for the same function. When this happens the two inputs (or more) configured wrong will be disabled as an inputs. This alarm will automatically be cleared when configuration is corrected.

An example of this would be: Input 3 = Compressor Safety, input 5 = Fan Status, input 8 = Fan Status, and input 9 = Humidistat; the alarm would be active, unit would run, compressor safety and humidistat would function normally, and Fan Status (inputs 5 & 8) will be interpreted as “No Function.”

Misconfigured Analog Input

This occurs if more than one analog input (inputs 1 & 2) is configured for the same sensor. When this happens the two inputs will be disabled as inputs. This alarm will automatically be cleared when configuration is corrected.

An example of this would be: Input 1 = IAQ Sensor, input 2 = IAQ Sensor; the alarm would be active, unit would run, but the IAQ Sensor (inputs 1 & 2) will be interpreted as “No Function.”

Third Party Networking

Third party communication and networking troubleshooting should be done by or with assistance from the front end 3rd party technician. A Module Status Report (Modstat) can be run from the BACview6, see Table 19 to perform. This lists information about the board status and networking state. For basic troubleshooting, see Table 20. Refer to the RTU-MP 3rd Party Integration Guide for additional information.

BACnet MS/TP

1.Verify that the BAS and controller are both set to speak the BACnet MS/TP protocol. The protocol of the controller is set via SW3 (switches 3, 4, 5, and 6). The protocol can also be verified by getting a Modstat of the controller through the BACview. Hit the “FN” key and the ’.’ key at the same time to pull up a Modstat. Scroll to the bottom of the page and there is a section entitled “Network Communications.” The active protocol and baud rate will be shown in this section.

2.Verify that the BAS and controller are set for the same baud rate. The baud rate of the controller is set via SW3 (switches 1 and 2). The baud rate can also be verified via the BACview by obtaining a Modstat. (See Fig. 59.)

3.Verify that the BAS is configured to speak 2-wire EIA-485 to the controller. The BAS may have to configure jumper or DIP switches on their end.

4.Verify that the BAS and the controller have the same communication settings (8 data bits, No Parity, and 1 stop bit).

5.Verify that the controller has a unique MAC address on the MS/TP bus. The controller’s MS/TP MAC address is set by its rotary address switches.

6.Verify proper wiring between the BAS and the controller.

7.Verify that the BAS is reading or writing to the proper BACnet objects in the controller. Download the latest points list for the controller to verify.

8.Verify that the BAS is sending his requests to the proper MS/TP MAC address of our controller.

9.Present the BAS company with a copy of our controller’s BACnet PICS so that they know which BACnet commands are supported.

580J

47

Image 47
Contents Safety Considerations Table of ContentsWhat to do if you smell gas Unit Arrangement and AccessGeneral Seasonal Maintenance Routine MaintenanceManual Outside Air Hood Screen Supply FAN Blower SectionSupply Fan Belt-Drive Supply-Fan Pulley Adjustment Bearings Adjustable-Pitch Pulley on MotorEvaporator Coil Coil Maintenance and Cleaning RecommendationCooling Condenser CoilRoutine Cleaning of Evaporator Coil Surfaces Routine Cleaning of Novation Condenser Coil SurfacesRefrigerant Charge Refrigerant System Pressure Access PortsPuronr R-410A Refrigerant Evaporator Coil Metering DevicesSeatcore Cooling Charging Charts 08D,F Both Circuits Cooling Charging ChartsCooling Charging Charts 12D,F Both Circuits TON Circuit TON Circuit Problem Cause Remedy Cooling Service AnalysisCompressors Condenser-Fan Adjustment 08D-12D,F sizeCondenser-Fan Adjustment 14D,F size Troubleshooting Cooling SystemConvenience Outlets Installing Weatherproof CoverNon-Powered Type Unit-Powered TypeSmoke Detectors Supply Air SensorSmoke Detector Locations All Units Completing Installation of Return Air Smoke SensorFiop Smoke Detector Wiring and Response Return Air Without EconomizerSensor and Controller Tests Dirty Sensor Test Procedure Controller Alarm TestController Alarm Test Procedure Dirty Controller Test ProcedureDirty Sensor Test Using an SD-TRK4 Detector CleaningSD-TRK4 Remote Alarm Test Procedure Remote Test/Reset Station Dirty Sensor TestTroubleshooting Compressor Protection Protective DevicesFuel Types and Pressures GAS Heating SystemControl Circuit Liquid Propane Supply Line Pressure Ranges Supply Pressure SwitchFlue Gas Passageways Combustion-Air BlowerOrifice Projection Burners and IgnitersMain Burners Limit Switch Cleaning and AdjustmentCheck Unit Operation and Make Necessary Adjustments Burner Ignition LED Error Code DescriptionLED Indication Error Code Description Gas Valve Orifice ReplacementRed LED-Status LP Orifice Orifice SizesAltitude Compensation Heating Service Analysis Troubleshooting Heating SystemMinimum Heating Entering Air Temperature IGC IGC Board LED Alarm CodesReplacing Novation Condenser Coil Condenser Coil ServiceRepairing Novation Condenser Tube Leaks RTU-MP Control SystemRTU-MP Multi-Protocol Control Board Typical RTU-MP System Control Wiring Diagram Outputs Supply Air Temperature SAT SensorOutdoor Air Temperature OAT Sensor RTU-MP Controller Inputs and OutputsConnect T-55 Space Temperature SPT SensorsEconoMi$er Outdoor Air Enthalpy Control PNO HH57AC077 Economizer ControlsIndoor Air Quality CO2 Sensor Wiring the Indoor Air Quality SensorDifferential Enthalpy Control Return Air Enthalpy SensorFilter Status Connecting Discrete InputsOutdoor Air Quality Sensor PNO 33ZCSENCO2 plus Weatherproof EnclosureCommunication Wiring Protocols Power Exhaust outputBaud Rate DS2 DS1 RTU-MP TroubleshootingCommunication LEDs Protocol DS8 DS7 DS6 DS5 DS4 DS3 DS2 DS1LEDs on the RTU-MP show the status of certain functions LEDsTroubleshooting Alarms BACnet MS/TP AlarmsModule Status Report Modstat Example Code Name Meaning Basic Protocol TroubleshootingModbus Manufacture DateEconoMi$er IV Component Locations ECONOMI$ER SystemsEconoMi$er IV Wiring EconoMi$er IV Functional View EconoMi$er IV Input/Output LogicOutdoor Dry Bulb Changeover Supply Air Temperature SAT SensorOutdoor Air Lockout Sensor EconoMi$er IV Control ModesOutdoor Enthalpy Changeover Differential Dry Bulb ControlMinimum Position Control Exhaust Setpoint AdjustmentIndoor Air Quality IAQ Sensor Input Demand Control Ventilation DCV Damper MovementThermostats Analog CO2 CO2 Sensor ConfigurationCO2 Sensor Standard Settings Differential Enthalpy DCV Demand Controlled Ventilation and Power ExhaustEconoMi$er IV Sensor Usage EconoMi$er IV PreparationSupply-Air Sensor Input Wiring DiagramsEconoMi$er IV Troubleshooting Completion DCV Minimum and Maximum Position580J Typical Unit Wiring Diagram Power 08D,F, 208/230-3-60 C09157 Gas Piping PRE-START-UPSTART-UP, General Unit PreparationOutdoor-Air Inlet Screens Internal WiringRefrigerant Service Ports Return-Air FiltersSTART-UP, RTU-MP Control Field Service TestConfiguration Unit Start DelayCompressor2 Service Hours Filter Service HoursSupply Fan Service Hours Compressor1 Service HoursInput 2 Function InputSpace Sensor Type Input 1 FunctionCooling, Unit With EconoMi$er Operating SequencesBase Unit Controls Cooling, Units Without Economizer Heating, Units Without EconomizerRTU-MP Sequence of Operation Heating With EconoMi$erDemand Controlled Ventilation Supplemental ControlsBACnet Schedule Always Occupied Default OccupancyScheduling Local ScheduleEconomizer Power ExhaustCooling Torque Values Fastener Torque ValuesIndoor Air Quality Demand LimitPosition Number Appendix I. Model Number SignificanceModel Number Nomenclature Serial Number Format12.5TONS Appendix II. Physical DataPhysical Data Natural Gas Heat, Liquid Propane Heat Heat Anticipator Setting AmpsPhysical Data Heating 12.5TONS 580J**08 580J**12 580J**14 Gas ConnectionCFM RPM BHP Appendix III. FAN Performance580J**08 579 580J**12RPM BHP 580J**141260 General fan performance notesUnit MOTOR/DRIVE Motor Pulley Turns Open Combo Pulley AdjustmentElectrical Information Mocp Unit Combustion PowerNOM IFM FAN Motor Exhaust No P.E Type DISC. SizeWiring Diagrams Appendix IV. Wiring Diagram ListCatalog No.SM580J---02 Appendix V. Motormaster Sensor Locations580J Preliminary Information Unit START-UP Checklist

580J*08--14D, F specifications

The Bryant F,580J*08--14D is an advanced heating and cooling system engineered for optimal performance and energy efficiency in residential and commercial applications. This innovative unit is designed to provide exceptional climate control while reducing operational costs, making it an ideal choice for those seeking reliable HVAC solutions.

One of the standout features of the Bryant F,580J*08--14D is its versatile heating and cooling capabilities. This system employs a two-stage compressor, which allows for precise temperature regulation and improved energy efficiency. This dual-stage operation ensures that the system can adapt to varying environmental conditions, providing enhanced comfort without excessive energy use.

The system is equipped with advanced inverter technology, which enables smoother operation and quieter performance. This technology adjusts the compressor speed based on the heating or cooling demand, leading to increased efficiency and reduced energy consumption. Additionally, the inverter system contributes to less noise during operation, creating a serene indoor environment.

The Bryant F,580J*08--14D also features a user-friendly thermostat that allows for easy temperature adjustments and scheduling. This smart thermostat is compatible with mobile devices, enabling users to monitor and control their HVAC system remotely. This feature provides added convenience and ensures that the system is operating efficiently, even when homeowners are away.

Energy efficiency is a hallmark of the Bryant F,580J*08--14D. The system meets and often exceeds ENERGY STARĀ® standards, making it one of the more eco-friendly options available in the market today. By utilizing energy-saving technologies and innovative designs, the system helps to lower utility bills and reduce the environmental impact.

Durability and reliability are key characteristics of the Bryant F,580J*08--14D. Constructed with high-quality materials and components, this unit is designed to withstand the rigors of changing weather conditions while maintaining consistent performance. Additionally, it comes equipped with a robust warranty, providing peace of mind for users investing in this heating and cooling solution.

In summary, the Bryant F,580J*08--14D is a top-tier HVAC system that boasts advanced technologies, exceptional energy efficiency, and user-friendly features. Its combination of reliable performance and modern conveniences makes it a standout choice for anyone looking to enhance their home's or business's climate control system, providing comfort and savings for years to come.