Bryant 580J*08--14D, F appendix CO2 Sensor Configuration, CO2 Sensor Standard Settings, Analog CO2

Page 57

The same equation can be used to determine the occupied or maximum ventilation rate to the building. For example, an output of 3.6 volts to the actuator provides a base ventilation rate of 5% and an output of 6.7 volts provides the maximum ventilation rate of 20% (or base plus 15 cfm per person). Use Fig. 72 to determine the maximum setting of the CO2 sensor. For example, an 1100 ppm setpoint relates to a 15 cfm per person design. Use the 1100 ppm curve on Fig. 72 to find the point when the CO2 sensor output will be 6.7 volts. Line up the point on the graph with the left side of the chart to determine that the range configuration for the CO2 sensor should be 1800 ppm. The EconoMi$er IV controller will output the 6.7 volts from the CO2 sensor to the actuator when the CO2 concentration in the space is at 1100 ppm. The DCV setpoint may be left at 2 volts since the CO2 sensor voltage will be ignored by the EconoMi$er IV controller until it rises above the 3.6 volt setting of the minimum position potentiometer.

Once the fully occupied damper position has been determined, set the maximum damper demand control ventilation potentiometer to this position. Do not set to the maximum position as this can result in over-ventilation to the space and potential high humidity levels.

CO2 Sensor Configuration

The CO2 sensor has preset standard voltage settings that can be selected anytime after the sensor is powered up. (See Table 23.)

Use setting 1 or 2 for Bryant equipment. (See Table 23.)

1.Press Clear and Mode buttons. Hold at least 5 seconds until the sensor enters the Edit mode.

2.Press Mode twice. The STDSET Menu will appear.

580J

Table 23 – CO2 Sensor Standard Settings

 

 

 

 

 

 

 

 

 

 

 

VENTILATION

ANALOG

CO2

OPTIONAL

RELAY

SETTING

EQUIPMENT

OUTPUT

RATE

CONTROL

RELAY SETPOINT

HYSTERESIS

OUTPUT

RANGE

 

 

 

(cfm/Person)

(ppm)

(ppm)

 

 

 

 

(ppm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

Proportional

Any

0--- 10V

0--- 2000

1000

50

 

4--- 20mA

 

 

 

 

 

 

 

 

Interface w/Standard

 

 

 

 

 

 

2

Proportional

Any

2--- 10V

0--- 2000

1000

50

Building Control System

7--- 20mA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

Exponential

Any

0--- 10V

0--- 2000

1100

50

 

4--- 20mA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

 

Proportional

15

0--- 10V

0--- 1100

1100

50

 

4--- 20mA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

 

Proportional

20

0--- 10V

0--- 900

900

50

 

4--- 20mA

 

Economizer

 

 

 

 

 

 

 

 

 

 

 

 

6

Exponential

15

0--- 10V

0--- 1100

1100

50

 

 

4--- 20mA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7

 

Exponential

20

0--- 10V

0--- 900

900

50

 

4--- 20mA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8

Health & Safety

Proportional

0--- 10V

0--- 9999

5000

500

4--- 20mA

 

 

 

 

 

 

 

9

Parking/Air Intakes/

Proportional

0--- 10V

0--- 2000

700

50

Loading Docks

4--- 20mA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

57

Image 57
Contents Safety Considerations Table of ContentsUnit Arrangement and Access GeneralWhat to do if you smell gas Seasonal Maintenance Routine MaintenanceSupply FAN Blower Section Supply Fan Belt-DriveManual Outside Air Hood Screen Supply-Fan Pulley Adjustment Bearings Adjustable-Pitch Pulley on MotorCooling Coil Maintenance and Cleaning RecommendationCondenser Coil Evaporator CoilRoutine Cleaning of Evaporator Coil Surfaces Routine Cleaning of Novation Condenser Coil SurfacesPuronr R-410A Refrigerant Refrigerant System Pressure Access PortsEvaporator Coil Metering Devices Refrigerant ChargeSeatcore Cooling Charging Charts 08D,F Both Circuits Cooling Charging ChartsCooling Charging Charts 12D,F Both Circuits TON Circuit TON Circuit Problem Cause Remedy Cooling Service AnalysisCondenser-Fan Adjustment 14D,F size Condenser-Fan Adjustment 08D-12D,F sizeTroubleshooting Cooling System CompressorsNon-Powered Type Installing Weatherproof CoverUnit-Powered Type Convenience OutletsSmoke Detectors Sensor Smoke Detector LocationsSupply Air Fiop Smoke Detector Wiring and Response Completing Installation of Return Air Smoke SensorReturn Air Without Economizer All UnitsSensor and Controller Tests Controller Alarm Test Procedure Controller Alarm TestDirty Controller Test Procedure Dirty Sensor Test ProcedureSD-TRK4 Remote Alarm Test Procedure Detector CleaningRemote Test/Reset Station Dirty Sensor Test Dirty Sensor Test Using an SD-TRK4Troubleshooting Compressor Protection Protective DevicesGAS Heating System Control CircuitFuel Types and Pressures Flue Gas Passageways Supply Pressure SwitchCombustion-Air Blower Liquid Propane Supply Line Pressure RangesBurners and Igniters Main BurnersOrifice Projection Cleaning and Adjustment Check Unit Operation and Make Necessary AdjustmentsLimit Switch LED Error Code Description LED Indication Error Code DescriptionBurner Ignition Gas Valve Orifice ReplacementRed LED-Status Orifice Sizes Altitude CompensationLP Orifice Troubleshooting Heating System Minimum Heating Entering Air TemperatureHeating Service Analysis IGC IGC Board LED Alarm CodesRepairing Novation Condenser Tube Leaks Condenser Coil ServiceRTU-MP Control System Replacing Novation Condenser CoilRTU-MP Multi-Protocol Control Board Typical RTU-MP System Control Wiring Diagram Outdoor Air Temperature OAT Sensor Supply Air Temperature SAT SensorRTU-MP Controller Inputs and Outputs OutputsSpace Temperature SPT Sensors EconoMi$erConnect T-55 Outdoor Air Enthalpy Control PNO HH57AC077 Economizer ControlsDifferential Enthalpy Control Wiring the Indoor Air Quality SensorReturn Air Enthalpy Sensor Indoor Air Quality CO2 SensorOutdoor Air Quality Sensor PNO 33ZCSENCO2 plus Connecting Discrete InputsWeatherproof Enclosure Filter StatusCommunication Wiring Protocols Power Exhaust outputCommunication LEDs RTU-MP TroubleshootingProtocol DS8 DS7 DS6 DS5 DS4 DS3 DS2 DS1 Baud Rate DS2 DS1LEDs on the RTU-MP show the status of certain functions LEDsTroubleshooting Alarms BACnet MS/TP AlarmsModule Status Report Modstat Example Modbus Basic Protocol TroubleshootingManufacture Date Code Name MeaningEconoMi$er IV Component Locations ECONOMI$ER SystemsEconoMi$er IV Wiring EconoMi$er IV Functional View EconoMi$er IV Input/Output LogicOutdoor Air Lockout Sensor Supply Air Temperature SAT SensorEconoMi$er IV Control Modes Outdoor Dry Bulb ChangeoverOutdoor Enthalpy Changeover Differential Dry Bulb ControlExhaust Setpoint Adjustment Indoor Air Quality IAQ Sensor InputMinimum Position Control Damper Movement ThermostatsDemand Control Ventilation DCV CO2 Sensor Configuration CO2 Sensor Standard SettingsAnalog CO2 EconoMi$er IV Sensor Usage DCV Demand Controlled Ventilation and Power ExhaustEconoMi$er IV Preparation Differential EnthalpyEconoMi$er IV Troubleshooting Completion Wiring DiagramsDCV Minimum and Maximum Position Supply-Air Sensor Input580J Typical Unit Wiring Diagram Power 08D,F, 208/230-3-60 C09157 START-UP, General PRE-START-UPUnit Preparation Gas PipingRefrigerant Service Ports Internal WiringReturn-Air Filters Outdoor-Air Inlet ScreensConfiguration Field Service TestUnit Start Delay START-UP, RTU-MP ControlSupply Fan Service Hours Filter Service HoursCompressor1 Service Hours Compressor2 Service HoursSpace Sensor Type InputInput 1 Function Input 2 FunctionBase Unit Controls Cooling, Units Without Economizer Operating SequencesHeating, Units Without Economizer Cooling, Unit With EconoMi$erDemand Controlled Ventilation Heating With EconoMi$erSupplemental Controls RTU-MP Sequence of OperationScheduling Always Occupied Default OccupancyLocal Schedule BACnet SchedulePower Exhaust CoolingEconomizer Indoor Air Quality Fastener Torque ValuesDemand Limit Torque ValuesModel Number Nomenclature Appendix I. Model Number SignificanceSerial Number Format Position NumberAppendix II. Physical Data Physical Data12.5TONS Physical Data Heating 12.5TONS Heat Anticipator Setting Amps580J**08 580J**12 580J**14 Gas Connection Natural Gas Heat, Liquid Propane HeatAppendix III. FAN Performance 580J**08CFM RPM BHP 579 580J**12RPM BHP 580J**141260 General fan performance notesUnit MOTOR/DRIVE Motor Pulley Turns Open Combo Pulley AdjustmentElectrical Information NOM IFM FAN Motor Exhaust No P.E Unit Combustion PowerType DISC. Size MocpWiring Diagrams Appendix IV. Wiring Diagram ListCatalog No.SM580J---02 Appendix V. Motormaster Sensor Locations580J Preliminary Information Unit START-UP Checklist

580J*08--14D, F specifications

The Bryant F,580J*08--14D is an advanced heating and cooling system engineered for optimal performance and energy efficiency in residential and commercial applications. This innovative unit is designed to provide exceptional climate control while reducing operational costs, making it an ideal choice for those seeking reliable HVAC solutions.

One of the standout features of the Bryant F,580J*08--14D is its versatile heating and cooling capabilities. This system employs a two-stage compressor, which allows for precise temperature regulation and improved energy efficiency. This dual-stage operation ensures that the system can adapt to varying environmental conditions, providing enhanced comfort without excessive energy use.

The system is equipped with advanced inverter technology, which enables smoother operation and quieter performance. This technology adjusts the compressor speed based on the heating or cooling demand, leading to increased efficiency and reduced energy consumption. Additionally, the inverter system contributes to less noise during operation, creating a serene indoor environment.

The Bryant F,580J*08--14D also features a user-friendly thermostat that allows for easy temperature adjustments and scheduling. This smart thermostat is compatible with mobile devices, enabling users to monitor and control their HVAC system remotely. This feature provides added convenience and ensures that the system is operating efficiently, even when homeowners are away.

Energy efficiency is a hallmark of the Bryant F,580J*08--14D. The system meets and often exceeds ENERGY STARĀ® standards, making it one of the more eco-friendly options available in the market today. By utilizing energy-saving technologies and innovative designs, the system helps to lower utility bills and reduce the environmental impact.

Durability and reliability are key characteristics of the Bryant F,580J*08--14D. Constructed with high-quality materials and components, this unit is designed to withstand the rigors of changing weather conditions while maintaining consistent performance. Additionally, it comes equipped with a robust warranty, providing peace of mind for users investing in this heating and cooling solution.

In summary, the Bryant F,580J*08--14D is a top-tier HVAC system that boasts advanced technologies, exceptional energy efficiency, and user-friendly features. Its combination of reliable performance and modern conveniences makes it a standout choice for anyone looking to enhance their home's or business's climate control system, providing comfort and savings for years to come.