Bryant Connecting Discrete Inputs, Outdoor Air Quality Sensor PNO 33ZCSENCO2 plus, Fan Status

Page 42

To connect the sensor to the control, identify the positive (4 to 20 mA) and ground (SIG COM) terminals on the sensor. (See Fig. 52.) Connect the 4-20 mA terminal to RTU-MP J4-2 and connect the SIG COM terminal to RTU-MP J4-3. (See Fig. 53.)

 

IAQ Sensor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SEN

J4-2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COM

 

 

 

 

 

 

 

 

 

J4-3

 

 

 

24 VAC

 

 

 

 

 

 

 

 

 

C08462

 

 

 

Fig. 53 - RTU-MP / Indoor CO2 Sensor

 

 

 

 

 

 

(33ZCSENCO2) Connections

 

 

 

 

 

 

 

 

580J

Outdoor Air Quality Sensor (PNO 33ZCSENCO2 plus

Weatherproof Enclosure)

 

 

 

 

 

 

The outdoor air CO2 sensor is designed to monitor carbon

 

dioxide (CO2) levels in the outside ventilation air and

 

interface with the ventilation damper in an HVAC system.

 

The OAQ sensor is packaged with an outdoor cover. (See

 

Fig. 54.) The outdoor air CO2 sensor must be located in

 

the economizer outside air hood.

 

 

COVER REMOVED

SIDE VIEW

C07135

Fig. 54 - Outdoor Air Quality Sensor Cover

Wiring the Outdoor Air CO2 Sensor

A dedicated power supply is required for this sensor. A two-wire cable is required to wire the dedicated power supply for the sensor. The two wires should be connected to the power supply and terminals 1 and 2.

To connect the sensor to the control, identify the positive (4 to 20 mA) and ground (SIG COM) terminals on the OAQ sensor. (See Fig. 52.) Connect the 4 to 20 mA terminal to RTU-MP J4-5. Connect the SIG COM terminal to RTU-MP J4-6. (See Fig. 55.)

OAQ Sensor/RH Sensor

SEN J4-5

COM J4-6

24 VAC

C08463

Fig. 55 - RTU-MP / Outdoor CO2 Sensor

(33ZCSENCO2) Connections

On 580J units equipped with factory-installed Smoke Detector(s), the smoke detector controller implements the unit shutdown through its NC contact set connected to the unit’s LCTB input. The FSD function is initiated via the smoke detector’s Alarm NO contact set. The RTU-MP controller communicates the smoke detector’s tripped status to the BAS building control. See Fig. 26 for unit smoke detector wiring.

The Fire Shutdown Switch configuration, MENUConfigInputsinput 5, identifies the normally open status of this input when there is no fire alarm.

Alarm state is reset when the smoke detector alarm condition is cleared and reset at the smoke detector in the unit.

Connecting Discrete Inputs

Filter Status

The filter status accessory is a field-installed accessory. This accessory detects plugged filters. When installing this accessory, the unit must be configured for filter status by setting MENUConfigInputsinput 3, 5, 8, or 9 to Filter Status and normally open (N/O) or normally closed (N/C). Input 8 or 9 is recommended for easy of installation. Refer to Fig. 42 and 43 for wire terminations at J5.

Fan Status

The fan status accessory is a field-installed accessory. This accessory detects when the indoor fan is blowing air. When installing this accessory, the unit must be

configured for fan status by setting MENUConfigInputsinput 3, 5, 8, or 9 to Fan Status and normally open (N/O) or normally closed (N/C). Input 8 or 9 is recommended for easy of installation. Refer to Fig. 42 and 43 for wire terminations at J5.

42

Image 42
Contents Table of Contents Safety ConsiderationsUnit Arrangement and Access GeneralWhat to do if you smell gas Routine Maintenance Seasonal MaintenanceSupply FAN Blower Section Supply Fan Belt-DriveManual Outside Air Hood Screen Adjustable-Pitch Pulley on Motor Supply-Fan Pulley Adjustment BearingsCondenser Coil Coil Maintenance and Cleaning RecommendationCooling Evaporator CoilRoutine Cleaning of Novation Condenser Coil Surfaces Routine Cleaning of Evaporator Coil SurfacesEvaporator Coil Metering Devices Refrigerant System Pressure Access PortsPuronr R-410A Refrigerant Refrigerant ChargeSeatcore Cooling Charging Charts Cooling Charging Charts 08D,F Both CircuitsCooling Charging Charts 12D,F Both Circuits TON Circuit TON Circuit Cooling Service Analysis Problem Cause RemedyTroubleshooting Cooling System Condenser-Fan Adjustment 08D-12D,F sizeCondenser-Fan Adjustment 14D,F size CompressorsUnit-Powered Type Installing Weatherproof CoverNon-Powered Type Convenience OutletsSmoke Detectors Sensor Smoke Detector LocationsSupply Air Return Air Without Economizer Completing Installation of Return Air Smoke SensorFiop Smoke Detector Wiring and Response All UnitsSensor and Controller Tests Dirty Controller Test Procedure Controller Alarm TestController Alarm Test Procedure Dirty Sensor Test ProcedureRemote Test/Reset Station Dirty Sensor Test Detector CleaningSD-TRK4 Remote Alarm Test Procedure Dirty Sensor Test Using an SD-TRK4Troubleshooting Protective Devices Compressor ProtectionGAS Heating System Control CircuitFuel Types and Pressures Combustion-Air Blower Supply Pressure SwitchFlue Gas Passageways Liquid Propane Supply Line Pressure RangesBurners and Igniters Main BurnersOrifice Projection Cleaning and Adjustment Check Unit Operation and Make Necessary AdjustmentsLimit Switch LED Error Code Description LED Indication Error Code DescriptionBurner Ignition Orifice Replacement Gas ValveRed LED-Status Orifice Sizes Altitude CompensationLP Orifice Troubleshooting Heating System Minimum Heating Entering Air TemperatureHeating Service Analysis IGC Board LED Alarm Codes IGCRTU-MP Control System Condenser Coil ServiceRepairing Novation Condenser Tube Leaks Replacing Novation Condenser CoilRTU-MP Multi-Protocol Control Board Typical RTU-MP System Control Wiring Diagram RTU-MP Controller Inputs and Outputs Supply Air Temperature SAT SensorOutdoor Air Temperature OAT Sensor OutputsSpace Temperature SPT Sensors EconoMi$erConnect T-55 Economizer Controls Outdoor Air Enthalpy Control PNO HH57AC077Return Air Enthalpy Sensor Wiring the Indoor Air Quality SensorDifferential Enthalpy Control Indoor Air Quality CO2 SensorWeatherproof Enclosure Connecting Discrete InputsOutdoor Air Quality Sensor PNO 33ZCSENCO2 plus Filter StatusPower Exhaust output Communication Wiring ProtocolsProtocol DS8 DS7 DS6 DS5 DS4 DS3 DS2 DS1 RTU-MP TroubleshootingCommunication LEDs Baud Rate DS2 DS1LEDs LEDs on the RTU-MP show the status of certain functionsTroubleshooting Alarms Alarms BACnet MS/TPModule Status Report Modstat Example Manufacture Date Basic Protocol TroubleshootingModbus Code Name MeaningECONOMI$ER Systems EconoMi$er IV Component LocationsEconoMi$er IV Wiring EconoMi$er IV Input/Output Logic EconoMi$er IV Functional ViewEconoMi$er IV Control Modes Supply Air Temperature SAT SensorOutdoor Air Lockout Sensor Outdoor Dry Bulb ChangeoverDifferential Dry Bulb Control Outdoor Enthalpy ChangeoverExhaust Setpoint Adjustment Indoor Air Quality IAQ Sensor InputMinimum Position Control Damper Movement ThermostatsDemand Control Ventilation DCV CO2 Sensor Configuration CO2 Sensor Standard SettingsAnalog CO2 EconoMi$er IV Preparation DCV Demand Controlled Ventilation and Power ExhaustEconoMi$er IV Sensor Usage Differential EnthalpyDCV Minimum and Maximum Position Wiring DiagramsEconoMi$er IV Troubleshooting Completion Supply-Air Sensor Input580J Typical Unit Wiring Diagram Power 08D,F, 208/230-3-60 C09157 Unit Preparation PRE-START-UPSTART-UP, General Gas PipingReturn-Air Filters Internal WiringRefrigerant Service Ports Outdoor-Air Inlet ScreensUnit Start Delay Field Service TestConfiguration START-UP, RTU-MP ControlCompressor1 Service Hours Filter Service HoursSupply Fan Service Hours Compressor2 Service HoursInput 1 Function InputSpace Sensor Type Input 2 FunctionHeating, Units Without Economizer Operating SequencesBase Unit Controls Cooling, Units Without Economizer Cooling, Unit With EconoMi$erSupplemental Controls Heating With EconoMi$erDemand Controlled Ventilation RTU-MP Sequence of OperationLocal Schedule Always Occupied Default OccupancyScheduling BACnet SchedulePower Exhaust CoolingEconomizer Demand Limit Fastener Torque ValuesIndoor Air Quality Torque ValuesSerial Number Format Appendix I. Model Number SignificanceModel Number Nomenclature Position NumberAppendix II. Physical Data Physical Data12.5TONS 580J**08 580J**12 580J**14 Gas Connection Heat Anticipator Setting AmpsPhysical Data Heating 12.5TONS Natural Gas Heat, Liquid Propane HeatAppendix III. FAN Performance 580J**08CFM RPM BHP 580J**12 579580J**14 RPM BHPGeneral fan performance notes 1260Pulley Adjustment Unit MOTOR/DRIVE Motor Pulley Turns Open ComboElectrical Information Type DISC. Size Unit Combustion PowerNOM IFM FAN Motor Exhaust No P.E MocpAppendix IV. Wiring Diagram List Wiring DiagramsAppendix V. Motormaster Sensor Locations Catalog No.SM580J---02580J Unit START-UP Checklist Preliminary Information

580J*08--14D, F specifications

The Bryant F,580J*08--14D is an advanced heating and cooling system engineered for optimal performance and energy efficiency in residential and commercial applications. This innovative unit is designed to provide exceptional climate control while reducing operational costs, making it an ideal choice for those seeking reliable HVAC solutions.

One of the standout features of the Bryant F,580J*08--14D is its versatile heating and cooling capabilities. This system employs a two-stage compressor, which allows for precise temperature regulation and improved energy efficiency. This dual-stage operation ensures that the system can adapt to varying environmental conditions, providing enhanced comfort without excessive energy use.

The system is equipped with advanced inverter technology, which enables smoother operation and quieter performance. This technology adjusts the compressor speed based on the heating or cooling demand, leading to increased efficiency and reduced energy consumption. Additionally, the inverter system contributes to less noise during operation, creating a serene indoor environment.

The Bryant F,580J*08--14D also features a user-friendly thermostat that allows for easy temperature adjustments and scheduling. This smart thermostat is compatible with mobile devices, enabling users to monitor and control their HVAC system remotely. This feature provides added convenience and ensures that the system is operating efficiently, even when homeowners are away.

Energy efficiency is a hallmark of the Bryant F,580J*08--14D. The system meets and often exceeds ENERGY STARĀ® standards, making it one of the more eco-friendly options available in the market today. By utilizing energy-saving technologies and innovative designs, the system helps to lower utility bills and reduce the environmental impact.

Durability and reliability are key characteristics of the Bryant F,580J*08--14D. Constructed with high-quality materials and components, this unit is designed to withstand the rigors of changing weather conditions while maintaining consistent performance. Additionally, it comes equipped with a robust warranty, providing peace of mind for users investing in this heating and cooling solution.

In summary, the Bryant F,580J*08--14D is a top-tier HVAC system that boasts advanced technologies, exceptional energy efficiency, and user-friendly features. Its combination of reliable performance and modern conveniences makes it a standout choice for anyone looking to enhance their home's or business's climate control system, providing comfort and savings for years to come.