Bryant 580J*08--14D appendix GAS Heating System, Control Circuit, Fuel Types and Pressures

Page 25

Troubleshooting Supply Fan Motor Overload Trips

The supply fan used in 580J units is a forward-curved centrifugal wheel. At a constant wheel speed, this wheel has a characteristic that causes the fan shaft load to DECREASE when the static pressure in the unit-duct system increases and to INCREASE when the static pressure in the unit-duct system decreases (and fan airflow rate increases). Motor overload conditions typically develop when the unit is operated with an access panel removed, with unfinished duct work, in an economizer-open mode, or a leak develops in the duct system that allows a bypass back to unit return opening.

Condenser Fan Motor Protection

The condenser fan motor is internally protected against overtemperature.

Control Circuit, 24-V

The control circuit is protected against overcurrent conditions by a circuit breaker mounted on control transformer TRAN. Reset is manual.

GAS HEATING SYSTEM

General

The heat exchanger system consists of a gas valve feeding multiple inshot burners off a manifold. The burners fire into matching primary tubes. The primary tubes discharge into combustion plenum where gas flow converges into secondary tubes. The secondary tubes exit into the induced draft fan wheel inlet. The induced fan wheel discharges into a flue passage and flue gases exit out a flue hood on the side of the unit. The induced draft fan motor includes a Hall Effect sensor circuit that confirms adequate wheel speed via the Integrated Gas Control (IGC) board. Safety switches include a Rollout Switch (at the top of the burner compartment) and a limit switch (mounted through the fan deck, over the tubes). (See Fig. 30 and 31.)

INDUCED-

 

DRAFT

 

MOTOR

ROLLOUT

MOUNTING

SWITCH

PLATE

 

BURNER

FLUE

SECTION

EXHAUST

INDUCED-

VESTIBULE

DRAFT MOTOR

PLATE

MANIFOLD

 

PRESSURE

 

TAP

 

GAS

BLOWER

VALVE

HOUSING

 

C09153

Fig. 30 - Burner Section Details

Limit Switch

and Shield

C08284

Fig. 31 - Limit Switch Location

Fuel Types and Pressures

Natural Gas

The 580J unit is factory-equipped for use with Natural Gas fuel at elevation under 2000 ft (610 m). See section Orifice Replacement for information in modifying this unit for installation at elevations above 2000 ft (610 m).

Gas line pressure entering the unit’s main gas valve must be within specified ranges. (See Table 5.) Adjust unit gas regulator valve as required or consult local gas utility.

Table 5 – Natural Gas Supply Line Pressure Ranges

UNIT MODEL

UNIT SIZE

MIN

MAX

 

 

 

 

580J

All

4.0 in. wg

13.0 in. wg

(996 Pa)

(3240 Pa)

 

 

 

 

 

 

Manifold pressure is factory-adjusted for NG fuel use. (See Table 6.) Adjust as required to obtain best flame characteristic.

Table 6 – Natural Gas Manifold Pressure Ranges

UNIT

UNIT

HIGH

LOW

RANGE

MODEL

SIZE

FIRE

FIRE

 

 

 

 

 

 

580J

All

3.5 in. wg

1.7 in. wg

2.0--- 5.0 in. wg (Hi)

(872 Pa)

(423 Pa)

(498--- 1245 Pa)

 

 

 

 

 

 

 

Liquid Propane

Accessory packages are available for field-installation that will convert the 580J unit to operate with Liquid Propane (LP) fuels. These kits include new orifice spuds, new springs for gas valves and a supply line low pressure switch. See section on Orifice Replacement for details on orifice size selections.

Fuel line pressure entering unit gas valve must remain within specified range. (See Table 7.)

580J

25

Image 25
Contents Safety Considerations Table of ContentsGeneral Unit Arrangement and AccessWhat to do if you smell gas Seasonal Maintenance Routine MaintenanceSupply Fan Belt-Drive Supply FAN Blower SectionManual Outside Air Hood Screen Supply-Fan Pulley Adjustment Bearings Adjustable-Pitch Pulley on MotorCooling Coil Maintenance and Cleaning RecommendationCondenser Coil Evaporator CoilRoutine Cleaning of Evaporator Coil Surfaces Routine Cleaning of Novation Condenser Coil SurfacesPuronr R-410A Refrigerant Refrigerant System Pressure Access PortsEvaporator Coil Metering Devices Refrigerant ChargeSeatcore Cooling Charging Charts 08D,F Both Circuits Cooling Charging ChartsCooling Charging Charts 12D,F Both Circuits TON Circuit TON Circuit Problem Cause Remedy Cooling Service AnalysisCondenser-Fan Adjustment 14D,F size Condenser-Fan Adjustment 08D-12D,F sizeTroubleshooting Cooling System CompressorsNon-Powered Type Installing Weatherproof CoverUnit-Powered Type Convenience OutletsSmoke Detectors Smoke Detector Locations SensorSupply Air Fiop Smoke Detector Wiring and Response Completing Installation of Return Air Smoke SensorReturn Air Without Economizer All UnitsSensor and Controller Tests Controller Alarm Test Procedure Controller Alarm TestDirty Controller Test Procedure Dirty Sensor Test ProcedureSD-TRK4 Remote Alarm Test Procedure Detector CleaningRemote Test/Reset Station Dirty Sensor Test Dirty Sensor Test Using an SD-TRK4Troubleshooting Compressor Protection Protective DevicesControl Circuit GAS Heating SystemFuel Types and Pressures Flue Gas Passageways Supply Pressure SwitchCombustion-Air Blower Liquid Propane Supply Line Pressure RangesMain Burners Burners and IgnitersOrifice Projection Check Unit Operation and Make Necessary Adjustments Cleaning and AdjustmentLimit Switch LED Indication Error Code Description LED Error Code DescriptionBurner Ignition Gas Valve Orifice ReplacementRed LED-Status Altitude Compensation Orifice SizesLP Orifice Minimum Heating Entering Air Temperature Troubleshooting Heating SystemHeating Service Analysis IGC IGC Board LED Alarm CodesRepairing Novation Condenser Tube Leaks Condenser Coil ServiceRTU-MP Control System Replacing Novation Condenser CoilRTU-MP Multi-Protocol Control Board Typical RTU-MP System Control Wiring Diagram Outdoor Air Temperature OAT Sensor Supply Air Temperature SAT SensorRTU-MP Controller Inputs and Outputs OutputsEconoMi$er Space Temperature SPT SensorsConnect T-55 Outdoor Air Enthalpy Control PNO HH57AC077 Economizer ControlsDifferential Enthalpy Control Wiring the Indoor Air Quality SensorReturn Air Enthalpy Sensor Indoor Air Quality CO2 SensorOutdoor Air Quality Sensor PNO 33ZCSENCO2 plus Connecting Discrete InputsWeatherproof Enclosure Filter StatusCommunication Wiring Protocols Power Exhaust outputCommunication LEDs RTU-MP TroubleshootingProtocol DS8 DS7 DS6 DS5 DS4 DS3 DS2 DS1 Baud Rate DS2 DS1LEDs on the RTU-MP show the status of certain functions LEDsTroubleshooting Alarms BACnet MS/TP AlarmsModule Status Report Modstat Example Modbus Basic Protocol TroubleshootingManufacture Date Code Name MeaningEconoMi$er IV Component Locations ECONOMI$ER SystemsEconoMi$er IV Wiring EconoMi$er IV Functional View EconoMi$er IV Input/Output LogicOutdoor Air Lockout Sensor Supply Air Temperature SAT SensorEconoMi$er IV Control Modes Outdoor Dry Bulb ChangeoverOutdoor Enthalpy Changeover Differential Dry Bulb ControlIndoor Air Quality IAQ Sensor Input Exhaust Setpoint AdjustmentMinimum Position Control Thermostats Damper MovementDemand Control Ventilation DCV CO2 Sensor Standard Settings CO2 Sensor ConfigurationAnalog CO2 EconoMi$er IV Sensor Usage DCV Demand Controlled Ventilation and Power ExhaustEconoMi$er IV Preparation Differential EnthalpyEconoMi$er IV Troubleshooting Completion Wiring DiagramsDCV Minimum and Maximum Position Supply-Air Sensor Input580J Typical Unit Wiring Diagram Power 08D,F, 208/230-3-60 C09157 START-UP, General PRE-START-UPUnit Preparation Gas PipingRefrigerant Service Ports Internal WiringReturn-Air Filters Outdoor-Air Inlet ScreensConfiguration Field Service TestUnit Start Delay START-UP, RTU-MP ControlSupply Fan Service Hours Filter Service HoursCompressor1 Service Hours Compressor2 Service HoursSpace Sensor Type InputInput 1 Function Input 2 FunctionBase Unit Controls Cooling, Units Without Economizer Operating SequencesHeating, Units Without Economizer Cooling, Unit With EconoMi$erDemand Controlled Ventilation Heating With EconoMi$erSupplemental Controls RTU-MP Sequence of OperationScheduling Always Occupied Default OccupancyLocal Schedule BACnet ScheduleCooling Power ExhaustEconomizer Indoor Air Quality Fastener Torque ValuesDemand Limit Torque ValuesModel Number Nomenclature Appendix I. Model Number SignificanceSerial Number Format Position NumberPhysical Data Appendix II. Physical Data12.5TONS Physical Data Heating 12.5TONS Heat Anticipator Setting Amps580J**08 580J**12 580J**14 Gas Connection Natural Gas Heat, Liquid Propane Heat580J**08 Appendix III. FAN PerformanceCFM RPM BHP 579 580J**12RPM BHP 580J**141260 General fan performance notesUnit MOTOR/DRIVE Motor Pulley Turns Open Combo Pulley AdjustmentElectrical Information NOM IFM FAN Motor Exhaust No P.E Unit Combustion PowerType DISC. Size MocpWiring Diagrams Appendix IV. Wiring Diagram ListCatalog No.SM580J---02 Appendix V. Motormaster Sensor Locations580J Preliminary Information Unit START-UP Checklist

580J*08--14D, F specifications

The Bryant F,580J*08--14D is an advanced heating and cooling system engineered for optimal performance and energy efficiency in residential and commercial applications. This innovative unit is designed to provide exceptional climate control while reducing operational costs, making it an ideal choice for those seeking reliable HVAC solutions.

One of the standout features of the Bryant F,580J*08--14D is its versatile heating and cooling capabilities. This system employs a two-stage compressor, which allows for precise temperature regulation and improved energy efficiency. This dual-stage operation ensures that the system can adapt to varying environmental conditions, providing enhanced comfort without excessive energy use.

The system is equipped with advanced inverter technology, which enables smoother operation and quieter performance. This technology adjusts the compressor speed based on the heating or cooling demand, leading to increased efficiency and reduced energy consumption. Additionally, the inverter system contributes to less noise during operation, creating a serene indoor environment.

The Bryant F,580J*08--14D also features a user-friendly thermostat that allows for easy temperature adjustments and scheduling. This smart thermostat is compatible with mobile devices, enabling users to monitor and control their HVAC system remotely. This feature provides added convenience and ensures that the system is operating efficiently, even when homeowners are away.

Energy efficiency is a hallmark of the Bryant F,580J*08--14D. The system meets and often exceeds ENERGY STARĀ® standards, making it one of the more eco-friendly options available in the market today. By utilizing energy-saving technologies and innovative designs, the system helps to lower utility bills and reduce the environmental impact.

Durability and reliability are key characteristics of the Bryant F,580J*08--14D. Constructed with high-quality materials and components, this unit is designed to withstand the rigors of changing weather conditions while maintaining consistent performance. Additionally, it comes equipped with a robust warranty, providing peace of mind for users investing in this heating and cooling solution.

In summary, the Bryant F,580J*08--14D is a top-tier HVAC system that boasts advanced technologies, exceptional energy efficiency, and user-friendly features. Its combination of reliable performance and modern conveniences makes it a standout choice for anyone looking to enhance their home's or business's climate control system, providing comfort and savings for years to come.