Bryant 580J*08--14D, F Completing Installation of Return Air Smoke Sensor, All Units, Highlight a

Page 19

Return Air Without Economizer

The sampling tube is located across the return air opening on the unit basepan. (See Fig. 22.) The holes in the sampling tube face downward, into the return air stream. The sampling tube is connected via tubing to the return air sensor that is mounted on a bracket high on the partition between return filter and controller location. (This sensor is shipped in a flat-mounting location. Installation requires that this sensor be relocated to its operating location and the tubing to the sampling tube be connected. See installation steps.)

Return Air Detector module (shipping position shown)*

Controller module

Return Air Detector Sampling Tube

*RA detector must be moved from shipping position to operating position by installer

C07307

Fig. 22 - Typical Return Air Detector Location

Return Air With Economizer

The sampling tube is inserted through the side plates of the economizer housing, placing it across the return air opening on the unit basepan. (See Fig. 23.) The holes in the sampling tube face downward, into the return air stream. The sampling tube is connected via tubing to the return air sensor that is mounted on a bracket high on the partition between return filter and controller location. (This sensor is shipped in a flat-mounting location. Installation requires that this sensor be relocated to its operating location and the tubing to the sampling tube be connected. See installation steps.)

Return Air

Sampling Tube

C08129

Fig. 23 - Return Air Sampling Tube Location

Completing Installation of Return Air Smoke Sensor

1.Unscrew the two screws holding the Return Air Sensor detector plate. (See Fig. 24.) Save the screws.

2.Remove the Return Air Sensor and its detector plate.

3.Rotate the detector plate so the sensor is facing out- wards and the sampling tube connection is on the bot- tom. (See Fig. 25.)

SCREWS

EXHAUST

TUBE

FLEXIBLE

EXTENSION

TUBE

SAMPLING

C08126

Fig. 24 - Return Air Detector Shipping Position

4.Screw the sensor and detector plate into its operating position using screws from Step 1. Make sure the sampling tube connection is on the bottom and the ex- haust tube is on the top. (See Fig. 24.)

5.Connect the flexible tube on the sampling inlet to the sampling tube on the basepan.

6.For units with an economizer, the sampling tube is in- tegrated into the economizer housing but the connec- tion of the flexible tubing to the sampling tube is the same.

C08127

Fig. 25 - Return Air Sensor Operating Position

FIOP Smoke Detector Wiring and Response

All Units

FIOP smoke detector is configured to automatically shut down all unit operations when smoke condition is detected. See Fig. 26, Smoke Detector Wiring.

Highlight A

JMP 3 is factory-cut, transferring unit control to smoke detector.

580J

19

Image 19
Contents Safety Considerations Table of ContentsGeneral Unit Arrangement and AccessWhat to do if you smell gas Seasonal Maintenance Routine MaintenanceSupply Fan Belt-Drive Supply FAN Blower SectionManual Outside Air Hood Screen Supply-Fan Pulley Adjustment Bearings Adjustable-Pitch Pulley on MotorEvaporator Coil Coil Maintenance and Cleaning RecommendationCooling Condenser CoilRoutine Cleaning of Evaporator Coil Surfaces Routine Cleaning of Novation Condenser Coil SurfacesRefrigerant Charge Refrigerant System Pressure Access PortsPuronr R-410A Refrigerant Evaporator Coil Metering DevicesSeatcore Cooling Charging Charts 08D,F Both Circuits Cooling Charging ChartsCooling Charging Charts 12D,F Both Circuits TON Circuit TON Circuit Problem Cause Remedy Cooling Service AnalysisCompressors Condenser-Fan Adjustment 08D-12D,F sizeCondenser-Fan Adjustment 14D,F size Troubleshooting Cooling SystemConvenience Outlets Installing Weatherproof CoverNon-Powered Type Unit-Powered TypeSmoke Detectors Smoke Detector Locations SensorSupply Air All Units Completing Installation of Return Air Smoke SensorFiop Smoke Detector Wiring and Response Return Air Without EconomizerSensor and Controller Tests Dirty Sensor Test Procedure Controller Alarm TestController Alarm Test Procedure Dirty Controller Test ProcedureDirty Sensor Test Using an SD-TRK4 Detector CleaningSD-TRK4 Remote Alarm Test Procedure Remote Test/Reset Station Dirty Sensor TestTroubleshooting Compressor Protection Protective DevicesControl Circuit GAS Heating SystemFuel Types and Pressures Liquid Propane Supply Line Pressure Ranges Supply Pressure SwitchFlue Gas Passageways Combustion-Air BlowerMain Burners Burners and IgnitersOrifice Projection Check Unit Operation and Make Necessary Adjustments Cleaning and AdjustmentLimit Switch LED Indication Error Code Description LED Error Code DescriptionBurner Ignition Gas Valve Orifice ReplacementRed LED-Status Altitude Compensation Orifice SizesLP Orifice Minimum Heating Entering Air Temperature Troubleshooting Heating SystemHeating Service Analysis IGC IGC Board LED Alarm CodesReplacing Novation Condenser Coil Condenser Coil ServiceRepairing Novation Condenser Tube Leaks RTU-MP Control SystemRTU-MP Multi-Protocol Control Board Typical RTU-MP System Control Wiring Diagram Outputs Supply Air Temperature SAT SensorOutdoor Air Temperature OAT Sensor RTU-MP Controller Inputs and OutputsEconoMi$er Space Temperature SPT SensorsConnect T-55 Outdoor Air Enthalpy Control PNO HH57AC077 Economizer ControlsIndoor Air Quality CO2 Sensor Wiring the Indoor Air Quality SensorDifferential Enthalpy Control Return Air Enthalpy SensorFilter Status Connecting Discrete InputsOutdoor Air Quality Sensor PNO 33ZCSENCO2 plus Weatherproof EnclosureCommunication Wiring Protocols Power Exhaust outputBaud Rate DS2 DS1 RTU-MP TroubleshootingCommunication LEDs Protocol DS8 DS7 DS6 DS5 DS4 DS3 DS2 DS1LEDs on the RTU-MP show the status of certain functions LEDsTroubleshooting Alarms BACnet MS/TP AlarmsModule Status Report Modstat Example Code Name Meaning Basic Protocol TroubleshootingModbus Manufacture DateEconoMi$er IV Component Locations ECONOMI$ER SystemsEconoMi$er IV Wiring EconoMi$er IV Functional View EconoMi$er IV Input/Output LogicOutdoor Dry Bulb Changeover Supply Air Temperature SAT SensorOutdoor Air Lockout Sensor EconoMi$er IV Control ModesOutdoor Enthalpy Changeover Differential Dry Bulb ControlIndoor Air Quality IAQ Sensor Input Exhaust Setpoint AdjustmentMinimum Position Control Thermostats Damper MovementDemand Control Ventilation DCV CO2 Sensor Standard Settings CO2 Sensor ConfigurationAnalog CO2 Differential Enthalpy DCV Demand Controlled Ventilation and Power ExhaustEconoMi$er IV Sensor Usage EconoMi$er IV PreparationSupply-Air Sensor Input Wiring DiagramsEconoMi$er IV Troubleshooting Completion DCV Minimum and Maximum Position580J Typical Unit Wiring Diagram Power 08D,F, 208/230-3-60 C09157 Gas Piping PRE-START-UPSTART-UP, General Unit PreparationOutdoor-Air Inlet Screens Internal WiringRefrigerant Service Ports Return-Air FiltersSTART-UP, RTU-MP Control Field Service TestConfiguration Unit Start DelayCompressor2 Service Hours Filter Service HoursSupply Fan Service Hours Compressor1 Service HoursInput 2 Function InputSpace Sensor Type Input 1 FunctionCooling, Unit With EconoMi$er Operating SequencesBase Unit Controls Cooling, Units Without Economizer Heating, Units Without EconomizerRTU-MP Sequence of Operation Heating With EconoMi$erDemand Controlled Ventilation Supplemental ControlsBACnet Schedule Always Occupied Default OccupancyScheduling Local ScheduleCooling Power ExhaustEconomizer Torque Values Fastener Torque ValuesIndoor Air Quality Demand LimitPosition Number Appendix I. Model Number SignificanceModel Number Nomenclature Serial Number FormatPhysical Data Appendix II. Physical Data12.5TONS Natural Gas Heat, Liquid Propane Heat Heat Anticipator Setting AmpsPhysical Data Heating 12.5TONS 580J**08 580J**12 580J**14 Gas Connection580J**08 Appendix III. FAN PerformanceCFM RPM BHP 579 580J**12RPM BHP 580J**141260 General fan performance notesUnit MOTOR/DRIVE Motor Pulley Turns Open Combo Pulley AdjustmentElectrical Information Mocp Unit Combustion PowerNOM IFM FAN Motor Exhaust No P.E Type DISC. SizeWiring Diagrams Appendix IV. Wiring Diagram ListCatalog No.SM580J---02 Appendix V. Motormaster Sensor Locations580J Preliminary Information Unit START-UP Checklist

580J*08--14D, F specifications

The Bryant F,580J*08--14D is an advanced heating and cooling system engineered for optimal performance and energy efficiency in residential and commercial applications. This innovative unit is designed to provide exceptional climate control while reducing operational costs, making it an ideal choice for those seeking reliable HVAC solutions.

One of the standout features of the Bryant F,580J*08--14D is its versatile heating and cooling capabilities. This system employs a two-stage compressor, which allows for precise temperature regulation and improved energy efficiency. This dual-stage operation ensures that the system can adapt to varying environmental conditions, providing enhanced comfort without excessive energy use.

The system is equipped with advanced inverter technology, which enables smoother operation and quieter performance. This technology adjusts the compressor speed based on the heating or cooling demand, leading to increased efficiency and reduced energy consumption. Additionally, the inverter system contributes to less noise during operation, creating a serene indoor environment.

The Bryant F,580J*08--14D also features a user-friendly thermostat that allows for easy temperature adjustments and scheduling. This smart thermostat is compatible with mobile devices, enabling users to monitor and control their HVAC system remotely. This feature provides added convenience and ensures that the system is operating efficiently, even when homeowners are away.

Energy efficiency is a hallmark of the Bryant F,580J*08--14D. The system meets and often exceeds ENERGY STARĀ® standards, making it one of the more eco-friendly options available in the market today. By utilizing energy-saving technologies and innovative designs, the system helps to lower utility bills and reduce the environmental impact.

Durability and reliability are key characteristics of the Bryant F,580J*08--14D. Constructed with high-quality materials and components, this unit is designed to withstand the rigors of changing weather conditions while maintaining consistent performance. Additionally, it comes equipped with a robust warranty, providing peace of mind for users investing in this heating and cooling solution.

In summary, the Bryant F,580J*08--14D is a top-tier HVAC system that boasts advanced technologies, exceptional energy efficiency, and user-friendly features. Its combination of reliable performance and modern conveniences makes it a standout choice for anyone looking to enhance their home's or business's climate control system, providing comfort and savings for years to come.