Bryant Flue Gas Passageways, Combustion-Air Blower, Liquid Propane Supply Line Pressure Ranges

Page 26

580J

Table 7 – Liquid Propane Supply Line Pressure Ranges

UNIT MODEL

UNIT SIZE

MIN

MAX

580J

All

11.0 in. wg

13.0 in. wg

(2740 Pa)

(3240 Pa)

 

 

 

 

 

 

Manifold pressure for LP fuel use must be adjusted to specified range. (See Table 8.) Follow instructions in the accessory kit to make initial readjustment.

Table 8 – Liquid Propane Manifold Pressure Ranges

UNIT MODEL

UNIT SIZE

HIGH FIRE

LOW FIRE

 

 

 

 

580J

All

10.0 in. wg

5.0 in. wg

(2490 Pa)

(1245 Pa)

 

 

 

 

 

 

Supply Pressure Switch

The LP conversion kit includes a supply low pressure switch. The switch contacts (from terminal C to terminal NO) will open the gas valve power whenever the supply line pressure drops below the setpoint. (See Fig. 32 and 33.) If the low pressure remains open for 15 minutes during a call for heat, the IGC circuit will initiate a Ignition Fault (5 flashes) lockout. Reset of the low pressure switch is automatic on rise in supply line pressure. Reset of the IGC requires a recycle of unit power after the low pressure switch has closed.

580JD08 only

C08238

 

C08239

All 580J*D except DD08

Fig. 32 - LP Low Pressure Switch (Installed)

IGC

LP LPS

 

 

 

 

 

BRN

C

NO

BRN

J2-11

 

 

C

 

 

 

IGC

 

 

MGV

 

 

 

J2-12

GRA

 

 

 

 

 

TSTAT

 

 

 

W2

PNK

 

 

C08285

Fig. 33 - LP Supply Line Low Pressure Switch Wiring

This switch also prevents operation when the propane tank level is low which can result in gas with a high concentration of impurities, additives, and residues that have settled to the bottom of the tank. Operation under these conditions can cause harm to the heat exchanger system. Contact your fuel supplier if this condition is suspected.

Flue Gas Passageways

To inspect the flue collector box and upper areas of the heat exchanger:

1.Remove the combustion blower wheel and motor as- sembly according to directions in Combustion-Air Blower section. (See Fig. 34.)

2.Remove the flue cover to inspect the heat exchanger.

3.Clean all surfaces as required using a wire brush.

Combustion-Air Blower

Clean periodically to assure proper airflow and heating efficiency. Inspect blower wheel every fall and periodically during heating season. For the first heating season, inspect blower wheel bi-monthly to determine proper cleaning frequency.

To access burner section, slide the sliding burner partition out of the unit.

To inspect blower wheel, shine a flashlight into draft hood opening. If cleaning is required, remove motor and wheel as follows:

1.Slide burner access panel out.

2.Remove the 7 screws that attach induced-draft motor housing to vestibule plate. (See Fig. 34.)

3.The blower wheel can be cleaned at this point. If ad- ditional cleaning is required, continue with Steps 4 and 5.

4.To remove blower from the motor shaft, remove 2 setscrews.

5.To remove motor, remove the 4 screws that hold the motor to mounting plate. Remove the motor cooling fan by removing one setscrew. Then remove nuts that hold motor to mounting plate.

6.To reinstall, reverse the procedure outlined above.

26

Image 26
Contents Table of Contents Safety ConsiderationsWhat to do if you smell gas Unit Arrangement and AccessGeneral Routine Maintenance Seasonal MaintenanceManual Outside Air Hood Screen Supply FAN Blower SectionSupply Fan Belt-Drive Adjustable-Pitch Pulley on Motor Supply-Fan Pulley Adjustment BearingsCondenser Coil Coil Maintenance and Cleaning RecommendationCooling Evaporator CoilRoutine Cleaning of Novation Condenser Coil Surfaces Routine Cleaning of Evaporator Coil SurfacesEvaporator Coil Metering Devices Refrigerant System Pressure Access PortsPuronr R-410A Refrigerant Refrigerant ChargeSeatcore Cooling Charging Charts Cooling Charging Charts 08D,F Both CircuitsCooling Charging Charts 12D,F Both Circuits TON Circuit TON Circuit Cooling Service Analysis Problem Cause RemedyTroubleshooting Cooling System Condenser-Fan Adjustment 08D-12D,F sizeCondenser-Fan Adjustment 14D,F size CompressorsUnit-Powered Type Installing Weatherproof CoverNon-Powered Type Convenience OutletsSmoke Detectors Supply Air SensorSmoke Detector Locations Return Air Without Economizer Completing Installation of Return Air Smoke SensorFiop Smoke Detector Wiring and Response All UnitsSensor and Controller Tests Dirty Controller Test Procedure Controller Alarm TestController Alarm Test Procedure Dirty Sensor Test ProcedureRemote Test/Reset Station Dirty Sensor Test Detector CleaningSD-TRK4 Remote Alarm Test Procedure Dirty Sensor Test Using an SD-TRK4Troubleshooting Protective Devices Compressor ProtectionFuel Types and Pressures GAS Heating SystemControl Circuit Combustion-Air Blower Supply Pressure SwitchFlue Gas Passageways Liquid Propane Supply Line Pressure RangesOrifice Projection Burners and IgnitersMain Burners Limit Switch Cleaning and AdjustmentCheck Unit Operation and Make Necessary Adjustments Burner Ignition LED Error Code DescriptionLED Indication Error Code Description Orifice Replacement Gas ValveRed LED-Status LP Orifice Orifice SizesAltitude Compensation Heating Service Analysis Troubleshooting Heating SystemMinimum Heating Entering Air Temperature IGC Board LED Alarm Codes IGCRTU-MP Control System Condenser Coil ServiceRepairing Novation Condenser Tube Leaks Replacing Novation Condenser CoilRTU-MP Multi-Protocol Control Board Typical RTU-MP System Control Wiring Diagram RTU-MP Controller Inputs and Outputs Supply Air Temperature SAT SensorOutdoor Air Temperature OAT Sensor OutputsConnect T-55 Space Temperature SPT SensorsEconoMi$er Economizer Controls Outdoor Air Enthalpy Control PNO HH57AC077Return Air Enthalpy Sensor Wiring the Indoor Air Quality SensorDifferential Enthalpy Control Indoor Air Quality CO2 SensorWeatherproof Enclosure Connecting Discrete InputsOutdoor Air Quality Sensor PNO 33ZCSENCO2 plus Filter StatusPower Exhaust output Communication Wiring ProtocolsProtocol DS8 DS7 DS6 DS5 DS4 DS3 DS2 DS1 RTU-MP TroubleshootingCommunication LEDs Baud Rate DS2 DS1LEDs LEDs on the RTU-MP show the status of certain functionsTroubleshooting Alarms Alarms BACnet MS/TPModule Status Report Modstat Example Manufacture Date Basic Protocol TroubleshootingModbus Code Name MeaningECONOMI$ER Systems EconoMi$er IV Component LocationsEconoMi$er IV Wiring EconoMi$er IV Input/Output Logic EconoMi$er IV Functional ViewEconoMi$er IV Control Modes Supply Air Temperature SAT SensorOutdoor Air Lockout Sensor Outdoor Dry Bulb ChangeoverDifferential Dry Bulb Control Outdoor Enthalpy ChangeoverMinimum Position Control Exhaust Setpoint AdjustmentIndoor Air Quality IAQ Sensor Input Demand Control Ventilation DCV Damper MovementThermostats Analog CO2 CO2 Sensor ConfigurationCO2 Sensor Standard Settings EconoMi$er IV Preparation DCV Demand Controlled Ventilation and Power ExhaustEconoMi$er IV Sensor Usage Differential EnthalpyDCV Minimum and Maximum Position Wiring DiagramsEconoMi$er IV Troubleshooting Completion Supply-Air Sensor Input580J Typical Unit Wiring Diagram Power 08D,F, 208/230-3-60 C09157 Unit Preparation PRE-START-UPSTART-UP, General Gas PipingReturn-Air Filters Internal WiringRefrigerant Service Ports Outdoor-Air Inlet ScreensUnit Start Delay Field Service TestConfiguration START-UP, RTU-MP ControlCompressor1 Service Hours Filter Service HoursSupply Fan Service Hours Compressor2 Service HoursInput 1 Function InputSpace Sensor Type Input 2 FunctionHeating, Units Without Economizer Operating SequencesBase Unit Controls Cooling, Units Without Economizer Cooling, Unit With EconoMi$erSupplemental Controls Heating With EconoMi$erDemand Controlled Ventilation RTU-MP Sequence of OperationLocal Schedule Always Occupied Default OccupancyScheduling BACnet ScheduleEconomizer Power ExhaustCooling Demand Limit Fastener Torque ValuesIndoor Air Quality Torque ValuesSerial Number Format Appendix I. Model Number SignificanceModel Number Nomenclature Position Number12.5TONS Appendix II. Physical DataPhysical Data 580J**08 580J**12 580J**14 Gas Connection Heat Anticipator Setting AmpsPhysical Data Heating 12.5TONS Natural Gas Heat, Liquid Propane HeatCFM RPM BHP Appendix III. FAN Performance580J**08 580J**12 579580J**14 RPM BHPGeneral fan performance notes 1260Pulley Adjustment Unit MOTOR/DRIVE Motor Pulley Turns Open ComboElectrical Information Type DISC. Size Unit Combustion PowerNOM IFM FAN Motor Exhaust No P.E MocpAppendix IV. Wiring Diagram List Wiring DiagramsAppendix V. Motormaster Sensor Locations Catalog No.SM580J---02580J Unit START-UP Checklist Preliminary Information

580J*08--14D, F specifications

The Bryant F,580J*08--14D is an advanced heating and cooling system engineered for optimal performance and energy efficiency in residential and commercial applications. This innovative unit is designed to provide exceptional climate control while reducing operational costs, making it an ideal choice for those seeking reliable HVAC solutions.

One of the standout features of the Bryant F,580J*08--14D is its versatile heating and cooling capabilities. This system employs a two-stage compressor, which allows for precise temperature regulation and improved energy efficiency. This dual-stage operation ensures that the system can adapt to varying environmental conditions, providing enhanced comfort without excessive energy use.

The system is equipped with advanced inverter technology, which enables smoother operation and quieter performance. This technology adjusts the compressor speed based on the heating or cooling demand, leading to increased efficiency and reduced energy consumption. Additionally, the inverter system contributes to less noise during operation, creating a serene indoor environment.

The Bryant F,580J*08--14D also features a user-friendly thermostat that allows for easy temperature adjustments and scheduling. This smart thermostat is compatible with mobile devices, enabling users to monitor and control their HVAC system remotely. This feature provides added convenience and ensures that the system is operating efficiently, even when homeowners are away.

Energy efficiency is a hallmark of the Bryant F,580J*08--14D. The system meets and often exceeds ENERGY STARĀ® standards, making it one of the more eco-friendly options available in the market today. By utilizing energy-saving technologies and innovative designs, the system helps to lower utility bills and reduce the environmental impact.

Durability and reliability are key characteristics of the Bryant F,580J*08--14D. Constructed with high-quality materials and components, this unit is designed to withstand the rigors of changing weather conditions while maintaining consistent performance. Additionally, it comes equipped with a robust warranty, providing peace of mind for users investing in this heating and cooling solution.

In summary, the Bryant F,580J*08--14D is a top-tier HVAC system that boasts advanced technologies, exceptional energy efficiency, and user-friendly features. Its combination of reliable performance and modern conveniences makes it a standout choice for anyone looking to enhance their home's or business's climate control system, providing comfort and savings for years to come.