Bryant F, 580J*08--14D appendix 580J**12, 579

Page 76

580J

FAN PERFORMANCE (cont.)

580J**12

 

 

 

3 PHASE

 

10 TON HORIZONTAL SUPPLY

 

 

 

 

 

 

 

 

 

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

CFM

 

0.2

0.4

 

 

0.6

0.8

 

 

1.0

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

 

 

Field---Supplied Drive1

 

 

Standard Static Option

 

 

Medium Static Option

3000

579

0.70

660

0.89

732

1.09

799

1.29

860

1.50

3250

613

0.85

690

1.06

760

1.27

823

1.49

883

1.71

3500

648

1.03

721

1.25

788

1.48

850

1.71

907

1.95

3750

683

1.23

753

1.47

817

1.71

877

1.96

933

2.21

4000

719

1.45

786

1.71

848

1.97

905

2.23

959

2.50

4250

756

1.71

819

1.98

879

2.26

934

2.53

987

2.81

4500

792

1.99

 

 

910

2.57

964

2.87

1015

3.16

853

2.28

4750

830

2.31

888

2.62

943

2.92

995

3.23

1044

3.54

5000

 

 

923

2.98

976

3.30

1026

3.63

 

 

867

2.66

1074

3.95

 

 

 

 

 

 

 

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

CFM

 

1.2

1.4

 

 

1.6

1.8

 

 

2.0

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

 

 

 

 

Medium Static Option

 

 

 

High Static Option

3000

917

1.70

970

1.91

1021

2.13

1070

2.34

1117

2.56

3250

938

1.93

991

2.16

1041

2.38

1089

2.61

1134

2.85

3500

961

2.18

1013

2.42

1062

2.66

1108

2.91

1153

3.15

3750

985

2.46

1035

2.71

1083

2.97

1129

3.23

1173

3.49

4000

1011

2.76

1059

3.03

 

 

1151

3.58

1194

3.85

1106

3.30

4250

1037

3.09

1084

3.38

1130

3.66

1174

3.95

1216

4.24

4500

1064

3.46

1110

3.76

1155

4.06

1198

4.36

1239

4.66

4750

1091

3.85

1137

4.16

1180

4.48

-

-

-

-

5000

1120

4.28

1164

4.61

-

-

---

---

---

---

NOTE: For more information, see General Fan Performance Notes.

Boldface indicates field-supplied drive is required.

1.Recommend using field-supplied fan pulley (part no. KR11AD912) and belt (part no. KR29AF051).

2.Recommend using field-supplied motor pulley (part no. KR11HY410).

580J**12

 

 

 

3 PHASE

 

10 TON VERTICAL SUPPLY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

CFM

 

0.2

 

0.4

 

0.6

0.8

 

 

1.0

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

 

 

 

 

 

Standard Static Option

 

 

Medium Static Option

3000

616

0.79

689

0.97

757

1.16

821

1.36

882

1.57

3250

655

0.96

724

1.16

788

1.37

849

1.58

907

1.80

3500

695

1.17

760

1.38

821

1.60

879

1.83

934

2.06

3750

736

1.41

797

1.63

 

 

910

2.10

963

2.35

855

1.86

4000

777

1.68

834

1.91

889

2.16

942

2.41

993

2.67

4250

818

1.98

 

 

925

2.49

976

2.75

1025

3.02

873

2.23

4500

860

2.32

912

2.58

962

2.85

1010

3.13

1057

3.41

4750

902

2.69

951

2.97

999

3.26

1046

3.55

1091

3.84

5000

944

3.11

991

3.40

1037

3.70

1082

4.00

1125

4.31

 

 

 

 

 

 

 

 

 

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

CFM

 

1.2

 

1.4

 

1.6

1.8

 

 

2.0

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

 

 

 

 

Medium Static Option

 

 

 

High Static Option

 

3000

939

1.79

994

2.01

1047

2.24

1098

2.47

1147

2.71

3250

962

2.03

1015

2.26

1066

2.50

1115

2.75

1163

3.00

3500

987

2.30

1038

2.54

 

 

1135

3.05

1181

3.32

1088

2.80

3750

1014

2.60

1063

2.86

1111

3.12

1157

3.39

1202

3.66

4000

1042

2.93

 

 

1136

3.48

1180

3.76

1224

4.04

1090

3.20

4250

1072

3.30

1118

3.58

1162

3.87

1205

4.16

-

-

4500

1103

3.70

1147

4.00

1190

4.29

1232

4.60

-

-

4750

1135

4.14

1177

4.45

-

-

-

-

---

---

5000

1167

4.63

-

-

---

---

---

---

---

---

NOTE: For more information, see General Fan Performance Notes. Boldface indicates field-supplied drive is required.

1. Recommend using field-supplied motor pulley (part no. KR11HY410).

76

Image 76
Contents Table of Contents Safety ConsiderationsGeneral Unit Arrangement and AccessWhat to do if you smell gas Routine Maintenance Seasonal MaintenanceSupply Fan Belt-Drive Supply FAN Blower SectionManual Outside Air Hood Screen Adjustable-Pitch Pulley on Motor Supply-Fan Pulley Adjustment BearingsCoil Maintenance and Cleaning Recommendation CoolingCondenser Coil Evaporator CoilRoutine Cleaning of Novation Condenser Coil Surfaces Routine Cleaning of Evaporator Coil SurfacesRefrigerant System Pressure Access Ports Puronr R-410A RefrigerantEvaporator Coil Metering Devices Refrigerant ChargeSeatcore Cooling Charging Charts Cooling Charging Charts 08D,F Both CircuitsCooling Charging Charts 12D,F Both Circuits TON Circuit TON Circuit Cooling Service Analysis Problem Cause RemedyCondenser-Fan Adjustment 08D-12D,F size Condenser-Fan Adjustment 14D,F sizeTroubleshooting Cooling System CompressorsInstalling Weatherproof Cover Non-Powered TypeUnit-Powered Type Convenience OutletsSmoke Detectors Smoke Detector Locations SensorSupply Air Completing Installation of Return Air Smoke Sensor Fiop Smoke Detector Wiring and ResponseReturn Air Without Economizer All UnitsSensor and Controller Tests Controller Alarm Test Controller Alarm Test ProcedureDirty Controller Test Procedure Dirty Sensor Test ProcedureDetector Cleaning SD-TRK4 Remote Alarm Test ProcedureRemote Test/Reset Station Dirty Sensor Test Dirty Sensor Test Using an SD-TRK4Troubleshooting Protective Devices Compressor ProtectionControl Circuit GAS Heating SystemFuel Types and Pressures Supply Pressure Switch Flue Gas PassagewaysCombustion-Air Blower Liquid Propane Supply Line Pressure RangesMain Burners Burners and IgnitersOrifice Projection Check Unit Operation and Make Necessary Adjustments Cleaning and AdjustmentLimit Switch LED Indication Error Code Description LED Error Code DescriptionBurner Ignition Orifice Replacement Gas ValveRed LED-Status Altitude Compensation Orifice SizesLP Orifice Minimum Heating Entering Air Temperature Troubleshooting Heating SystemHeating Service Analysis IGC Board LED Alarm Codes IGCCondenser Coil Service Repairing Novation Condenser Tube LeaksRTU-MP Control System Replacing Novation Condenser CoilRTU-MP Multi-Protocol Control Board Typical RTU-MP System Control Wiring Diagram Supply Air Temperature SAT Sensor Outdoor Air Temperature OAT SensorRTU-MP Controller Inputs and Outputs OutputsEconoMi$er Space Temperature SPT SensorsConnect T-55 Economizer Controls Outdoor Air Enthalpy Control PNO HH57AC077Wiring the Indoor Air Quality Sensor Differential Enthalpy ControlReturn Air Enthalpy Sensor Indoor Air Quality CO2 SensorConnecting Discrete Inputs Outdoor Air Quality Sensor PNO 33ZCSENCO2 plusWeatherproof Enclosure Filter StatusPower Exhaust output Communication Wiring ProtocolsRTU-MP Troubleshooting Communication LEDsProtocol DS8 DS7 DS6 DS5 DS4 DS3 DS2 DS1 Baud Rate DS2 DS1LEDs LEDs on the RTU-MP show the status of certain functionsTroubleshooting Alarms Alarms BACnet MS/TPModule Status Report Modstat Example Basic Protocol Troubleshooting ModbusManufacture Date Code Name MeaningECONOMI$ER Systems EconoMi$er IV Component LocationsEconoMi$er IV Wiring EconoMi$er IV Input/Output Logic EconoMi$er IV Functional ViewSupply Air Temperature SAT Sensor Outdoor Air Lockout SensorEconoMi$er IV Control Modes Outdoor Dry Bulb ChangeoverDifferential Dry Bulb Control Outdoor Enthalpy ChangeoverIndoor Air Quality IAQ Sensor Input Exhaust Setpoint AdjustmentMinimum Position Control Thermostats Damper MovementDemand Control Ventilation DCV CO2 Sensor Standard Settings CO2 Sensor ConfigurationAnalog CO2 DCV Demand Controlled Ventilation and Power Exhaust EconoMi$er IV Sensor UsageEconoMi$er IV Preparation Differential EnthalpyWiring Diagrams EconoMi$er IV Troubleshooting CompletionDCV Minimum and Maximum Position Supply-Air Sensor Input580J Typical Unit Wiring Diagram Power 08D,F, 208/230-3-60 C09157 PRE-START-UP START-UP, GeneralUnit Preparation Gas PipingInternal Wiring Refrigerant Service PortsReturn-Air Filters Outdoor-Air Inlet ScreensField Service Test ConfigurationUnit Start Delay START-UP, RTU-MP ControlFilter Service Hours Supply Fan Service HoursCompressor1 Service Hours Compressor2 Service HoursInput Space Sensor TypeInput 1 Function Input 2 FunctionOperating Sequences Base Unit Controls Cooling, Units Without EconomizerHeating, Units Without Economizer Cooling, Unit With EconoMi$erHeating With EconoMi$er Demand Controlled VentilationSupplemental Controls RTU-MP Sequence of OperationAlways Occupied Default Occupancy SchedulingLocal Schedule BACnet ScheduleCooling Power ExhaustEconomizer Fastener Torque Values Indoor Air QualityDemand Limit Torque ValuesAppendix I. Model Number Significance Model Number NomenclatureSerial Number Format Position Number Physical Data Appendix II. Physical Data 12.5TONS Heat Anticipator Setting Amps Physical Data Heating 12.5TONS580J**08 580J**12 580J**14 Gas Connection Natural Gas Heat, Liquid Propane Heat580J**08 Appendix III. FAN PerformanceCFM RPM BHP 580J**12 579580J**14 RPM BHPGeneral fan performance notes 1260Pulley Adjustment Unit MOTOR/DRIVE Motor Pulley Turns Open ComboElectrical Information Unit Combustion Power NOM IFM FAN Motor Exhaust No P.EType DISC. Size MocpAppendix IV. Wiring Diagram List Wiring DiagramsAppendix V. Motormaster Sensor Locations Catalog No.SM580J---02580J Unit START-UP Checklist Preliminary Information