Bryant F appendix Heating With EconoMi$er, Demand Controlled Ventilation, Supplemental Controls

Page 68

580J

When free cooling is available as determined by the appropriate changeover command (dry bulb, outdoor enthalpy, differential dry bulb or differential enthalpy), a call for cooling (Y1 closes at the thermostat) will cause the economizer control to modulate the dampers open and closed to maintain the unit supply air temperature at 50 to 55_F. Compressor will not run.

During free cooling operation, a supply air temperature (SAT) above 50_F will cause the dampers to modulate between Minimum Position setpoint and 100% open. With SAT from 50_F to 45_F, the dampers will maintain at the Minimum Position setting. With SAT below 45_F, the outside air dampers will be closed. When SAT rises to 48_F, the dampers will re-open to Minimum Position setting.

Should 100% outside air not be capable of satisfying the space temperature, space temperature will rise until Y2 is closed. The economizer control will call for compressor operation. Dampers will modulate to maintain SAT at 50 to 55_F concurrent with Compressor 1 operation. The Low Ambient Lockout Thermostat will block compressor operation with economizer operation below 42_F outside air temperature.

When space temperature demand is satisfied (thermostat Y1 opens), the dampers will return to Minimum Damper position if indoor fan is running or fully closed if fan is off.

If accessory power exhaust is installed, the power exhaust fan motors will be energized by the economizer control as the dampers open above the PE-On setpoint and will be de-energized as the dampers close below the PE-On setpoint.

Damper movement from full closed to full open (or vice versa) will take between 1-1/2 and 2-1/2 minutes.

Heating With EconoMi$er IV

During Occupied mode operation, indoor fan operation will be accompanied by economizer dampers moving to Minimum Position setpoint for ventilation. If indoor fan is off, dampers will close. During Unoccupied mode operation, dampers will remain closed unless a DCV demand is received.

When the room temperature calls for heat (W1 closes), the heating controls are energized as described in Heating, Unit Without Economizer above.

Demand Controlled Ventilation

If a field-installed CO2 sensor is connected to the Economize IV control, a Demand Controlled Ventilation strategy will operate automatically. As the CO2 level in the space increases above the setpoint (on the EconoMi$er IV controller), the minimum position of the dampers will be increased proportionally, until the Maximum Ventilation setting is reached. As the space CO2 level decreases because of the increase in fresh air, the outdoor-damper will follow the higher demand condition from the DCV mode or from the free-cooling mode.

DCV operation is available in Occupied and Unoccupied periods with EconoMi$er IV. However, a control modification will be required on the 580J unit to implement the Unoccupied period function.

Supplemental Controls

Compressor Lockout Relay (CLO) - The CLO is available as a factory-installed option or as a field-installed accessory. Each compressor has a CLO. The CLO compares the demand for compressor operation (via a 24-v input from Y at CLO terminal 2) to operation of the compressor (determined via compressor current signal input at the CLO’s current transformer loop); if the compressor current signal is lost while the demand input still exists, the CLO will trip open and prevent the compressor from restarting until the CLO has been manually reset. In the lockout condition, 24-v will be available at terminal X. Reset is accomplished by removing the input signal at terminal 2; open the thermostat briefly or cycle the main power to the unit.

Phase Monitor Relay (PMR) - The PMR protects the unit in the event of a loss of a phase or a reversal of power line phase in the three-phase unit power supply. In normal operation, the relay K1 is energized (contact set closed) and red LED indicator is on steady. If the PMR detects a loss of a phase or a phase sequence reversal, the relay K1 is energized, its contact set is opened and unit operation is stopped; red LED indicator will blink during lockout condition. Reset of the PMR is automatic when all phases are restored and phase sequence is correct. If no 24-v control power is available to the PMR, the red LED will be off. Smoke Detectors - Factory-installed smoke detectors are discussed in detail starting on page 17.

RTU-MP Sequence of Operation

The RTU-MP will control the compressor, economizer and heating outputs based on its own space temperature input and setpoints. An optional CO2 IAQ sensor mounted in the space can influence the economizer minimum position. The RTU-MP has its own hardware clock that is set automatically when the software is installed on the board. The RTU-MP’s default is to control to occupied setpoints all the time, until a type of occupancy control is set. Occupancy types are described in the scheduling section. The following sections describe the operation for the functions of the RTU-MP. All point objects that are referred to in this sequence will be in reference to the objects as viewed in BACview6 Handheld.

68

Image 68
Contents Table of Contents Safety ConsiderationsWhat to do if you smell gas Unit Arrangement and AccessGeneral Routine Maintenance Seasonal MaintenanceManual Outside Air Hood Screen Supply FAN Blower SectionSupply Fan Belt-Drive Adjustable-Pitch Pulley on Motor Supply-Fan Pulley Adjustment BearingsCoil Maintenance and Cleaning Recommendation CoolingCondenser Coil Evaporator CoilRoutine Cleaning of Novation Condenser Coil Surfaces Routine Cleaning of Evaporator Coil SurfacesRefrigerant System Pressure Access Ports Puronr R-410A RefrigerantEvaporator Coil Metering Devices Refrigerant ChargeSeatcore Cooling Charging Charts Cooling Charging Charts 08D,F Both CircuitsCooling Charging Charts 12D,F Both Circuits TON Circuit TON Circuit Cooling Service Analysis Problem Cause RemedyCondenser-Fan Adjustment 08D-12D,F size Condenser-Fan Adjustment 14D,F sizeTroubleshooting Cooling System CompressorsInstalling Weatherproof Cover Non-Powered TypeUnit-Powered Type Convenience OutletsSmoke Detectors Supply Air SensorSmoke Detector Locations Completing Installation of Return Air Smoke Sensor Fiop Smoke Detector Wiring and ResponseReturn Air Without Economizer All UnitsSensor and Controller Tests Controller Alarm Test Controller Alarm Test ProcedureDirty Controller Test Procedure Dirty Sensor Test ProcedureDetector Cleaning SD-TRK4 Remote Alarm Test ProcedureRemote Test/Reset Station Dirty Sensor Test Dirty Sensor Test Using an SD-TRK4Troubleshooting Protective Devices Compressor ProtectionFuel Types and Pressures GAS Heating SystemControl Circuit Supply Pressure Switch Flue Gas PassagewaysCombustion-Air Blower Liquid Propane Supply Line Pressure RangesOrifice Projection Burners and IgnitersMain Burners Limit Switch Cleaning and AdjustmentCheck Unit Operation and Make Necessary Adjustments Burner Ignition LED Error Code DescriptionLED Indication Error Code Description Orifice Replacement Gas ValveRed LED-Status LP Orifice Orifice SizesAltitude Compensation Heating Service Analysis Troubleshooting Heating SystemMinimum Heating Entering Air Temperature IGC Board LED Alarm Codes IGCCondenser Coil Service Repairing Novation Condenser Tube LeaksRTU-MP Control System Replacing Novation Condenser CoilRTU-MP Multi-Protocol Control Board Typical RTU-MP System Control Wiring Diagram Supply Air Temperature SAT Sensor Outdoor Air Temperature OAT SensorRTU-MP Controller Inputs and Outputs OutputsConnect T-55 Space Temperature SPT SensorsEconoMi$er Economizer Controls Outdoor Air Enthalpy Control PNO HH57AC077Wiring the Indoor Air Quality Sensor Differential Enthalpy ControlReturn Air Enthalpy Sensor Indoor Air Quality CO2 SensorConnecting Discrete Inputs Outdoor Air Quality Sensor PNO 33ZCSENCO2 plusWeatherproof Enclosure Filter StatusPower Exhaust output Communication Wiring ProtocolsRTU-MP Troubleshooting Communication LEDsProtocol DS8 DS7 DS6 DS5 DS4 DS3 DS2 DS1 Baud Rate DS2 DS1LEDs LEDs on the RTU-MP show the status of certain functionsTroubleshooting Alarms Alarms BACnet MS/TPModule Status Report Modstat Example Basic Protocol Troubleshooting ModbusManufacture Date Code Name MeaningECONOMI$ER Systems EconoMi$er IV Component LocationsEconoMi$er IV Wiring EconoMi$er IV Input/Output Logic EconoMi$er IV Functional ViewSupply Air Temperature SAT Sensor Outdoor Air Lockout SensorEconoMi$er IV Control Modes Outdoor Dry Bulb ChangeoverDifferential Dry Bulb Control Outdoor Enthalpy ChangeoverMinimum Position Control Exhaust Setpoint AdjustmentIndoor Air Quality IAQ Sensor Input Demand Control Ventilation DCV Damper MovementThermostats Analog CO2 CO2 Sensor ConfigurationCO2 Sensor Standard Settings DCV Demand Controlled Ventilation and Power Exhaust EconoMi$er IV Sensor UsageEconoMi$er IV Preparation Differential EnthalpyWiring Diagrams EconoMi$er IV Troubleshooting CompletionDCV Minimum and Maximum Position Supply-Air Sensor Input580J Typical Unit Wiring Diagram Power 08D,F, 208/230-3-60 C09157 PRE-START-UP START-UP, GeneralUnit Preparation Gas PipingInternal Wiring Refrigerant Service PortsReturn-Air Filters Outdoor-Air Inlet ScreensField Service Test ConfigurationUnit Start Delay START-UP, RTU-MP ControlFilter Service Hours Supply Fan Service HoursCompressor1 Service Hours Compressor2 Service HoursInput Space Sensor TypeInput 1 Function Input 2 FunctionOperating Sequences Base Unit Controls Cooling, Units Without EconomizerHeating, Units Without Economizer Cooling, Unit With EconoMi$erHeating With EconoMi$er Demand Controlled VentilationSupplemental Controls RTU-MP Sequence of OperationAlways Occupied Default Occupancy SchedulingLocal Schedule BACnet ScheduleEconomizer Power ExhaustCooling Fastener Torque Values Indoor Air QualityDemand Limit Torque ValuesAppendix I. Model Number Significance Model Number NomenclatureSerial Number Format Position Number12.5TONS Appendix II. Physical DataPhysical Data Heat Anticipator Setting Amps Physical Data Heating 12.5TONS580J**08 580J**12 580J**14 Gas Connection Natural Gas Heat, Liquid Propane HeatCFM RPM BHP Appendix III. FAN Performance580J**08 580J**12 579580J**14 RPM BHPGeneral fan performance notes 1260Pulley Adjustment Unit MOTOR/DRIVE Motor Pulley Turns Open ComboElectrical Information Unit Combustion Power NOM IFM FAN Motor Exhaust No P.EType DISC. Size MocpAppendix IV. Wiring Diagram List Wiring DiagramsAppendix V. Motormaster Sensor Locations Catalog No.SM580J---02580J Unit START-UP Checklist Preliminary Information

580J*08--14D, F specifications

The Bryant F,580J*08--14D is an advanced heating and cooling system engineered for optimal performance and energy efficiency in residential and commercial applications. This innovative unit is designed to provide exceptional climate control while reducing operational costs, making it an ideal choice for those seeking reliable HVAC solutions.

One of the standout features of the Bryant F,580J*08--14D is its versatile heating and cooling capabilities. This system employs a two-stage compressor, which allows for precise temperature regulation and improved energy efficiency. This dual-stage operation ensures that the system can adapt to varying environmental conditions, providing enhanced comfort without excessive energy use.

The system is equipped with advanced inverter technology, which enables smoother operation and quieter performance. This technology adjusts the compressor speed based on the heating or cooling demand, leading to increased efficiency and reduced energy consumption. Additionally, the inverter system contributes to less noise during operation, creating a serene indoor environment.

The Bryant F,580J*08--14D also features a user-friendly thermostat that allows for easy temperature adjustments and scheduling. This smart thermostat is compatible with mobile devices, enabling users to monitor and control their HVAC system remotely. This feature provides added convenience and ensures that the system is operating efficiently, even when homeowners are away.

Energy efficiency is a hallmark of the Bryant F,580J*08--14D. The system meets and often exceeds ENERGY STARĀ® standards, making it one of the more eco-friendly options available in the market today. By utilizing energy-saving technologies and innovative designs, the system helps to lower utility bills and reduce the environmental impact.

Durability and reliability are key characteristics of the Bryant F,580J*08--14D. Constructed with high-quality materials and components, this unit is designed to withstand the rigors of changing weather conditions while maintaining consistent performance. Additionally, it comes equipped with a robust warranty, providing peace of mind for users investing in this heating and cooling solution.

In summary, the Bryant F,580J*08--14D is a top-tier HVAC system that boasts advanced technologies, exceptional energy efficiency, and user-friendly features. Its combination of reliable performance and modern conveniences makes it a standout choice for anyone looking to enhance their home's or business's climate control system, providing comfort and savings for years to come.